E2S AlertAlight DL105X Instructions/Service Manual Download Page 1

 

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH    [email protected]        e2s.com                                             D218-00-201-IS Issue 1 27/05/2021  

INSTRUCTION & SERVICE MANUAL 
DL105X AlertAlight Combined Sounder Xenon Beacons 

 

Unit Type Code 

Nominal 

Voltage 

Voltage 

Range 

Nominal 

Sounder 

Current* 

Nominal SPL  

Max SPL 

Average SPL 

Nominal 

Beacon 

Current* 

DL105XDC012 

12 V dc  

11.5-14V dc 

17mA 

105.3dB(A) 

Tone 44 @ 1m 

110.9dB(A) 

Tone 4 @ 1m 

105.2dB(A) All 

tones @1m  

341mA 

 24V dc  

33.5mA 

DL105XDC024  

271mA 

20-28V dc 

48V dc  

113mA 

DL105XDC048 

170mA 

42-52V dc 

24-28V ac 

50/60Hz 

DL105XAC024 

24V ac  

42.5mA 

300mA 

DL105XAC048 

48V ac  

42mA 

250mA 

48V ac ± 

10% 50/60Hz 

DL105XAC115  

115V ac  

25mA 

70mA 

115V ac ± 

10% 50/60Hz 

230V ac 

17mA 

DL105XAC230  

35mA 

230V ac ± 

10% 50/60Hz 

  *Nominal current at nominal voltage, Tone 12 / 1Hz Flash Pattern 

0.4Nm

 

5mm

0.5   2.5mm 

• 

-

40°C to +66C (-40°F to 151°F) 

• 

Type 4 / 4X / 3R / 13, IP66 

• 

2.1Kg (4.62lb) 

• 

CE, All units UL Listed. 

Attention

: Installation must be carried out by an electrician in compliance with the latest codes and regulations. 

Attention

: L'installation doit être effectuée par un électricien conformément aux derniers codes et réglementations.  

Achtung

: Die Installation muss von einem Elektriker gemäß den neuesten Vorschriften und Bestimmungen durchgeführt werden.  

Attenzione

: L'installazione deve essere eseguita da un elettricista in conformità con i codici e le normative più recenti. 

Atención

: La instalación debe ser realizada por un electricista de acuerdo con los últimos códigos y regulaciones. 

Atenção: 

A instalação deve ser realizada por um eletricista de acordo com os códigos e regulamentos mais recentes. 

Внимание

: установка должна выполняться электриком в соответствии с последними нормами и правилами. 

Attention

: Disconnect from power source before installation or service to prevent electric shock  

Attention

: Débranchez-le de la source d'alimentation avant l'installation ou l'entretien pour éviter tout choc électrique. 

Achtung

: Vor Installation oder Wartung von der Stromquelle trennen, um einen Stromschlag zu vermeiden. 

Attenzione

: scollegare dall'alimentazione prima dell'installazione o dell'assistenza per evitare scosse elettriche. 

Atención

: desconéctelo de la fuente de alimentación antes de la instalación o el servicio para evitar descargas eléctricas. 

Atenção: 

Desconecte da fonte de alimentação antes da instalação ou serviço para evitar choque elétrico  

Внимание

: отключите от источника питания перед установкой или обслуживанием, чтобы предотвратить поражение электрическим током.

 

AC: 1.0 – 2.5mm

/ AWG18 – AWG12 

DC: 0.2 – 2.5mm

/ AWG24 – AWG12 

Summary of Contents for AlertAlight DL105X

Page 1: ...par un lectricien conform ment aux derniers codes et r glementations Achtung Die Installation muss von einem Elektriker gem den neuesten Vorschriften und Bestimmungen durchgef hrt werden Attenzione L...

Page 2: ...172 00 201 IS Issue 1 14 05 2021 DC See D218 06 201 AC See D218 06 205 A B C E N L E N L S2 S3 S2 S1 S2 S1 N L E E S3 S2 N L Default S2 Tone 1 Default S1 Tone 44 ON 1 OFF 0 AC DC See D221 95 001 A B C...

Page 3: ...L DL105X AlertAlight Combined Sounder Xenon Beacons 4x 1Nm For DL105XAC units wire an Earth to the E terminal on the PCBA in order to Earth the metal housing For DL105XDC units using a ring terminal f...

Page 4: ...on for EOL device values and ratings Model Nominal Voltage Voltage Range Nominal Operating Current Max Operating RMS Beacon Sounder Beacon Sounder DL105XDC012 12V dc 11 5 14Vdc 341mA 17mA 531mA 125mA...

Page 5: ...Page left Intentionally blank...

Page 6: ...0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1...

Page 7: ...Page left Intentionally blank...

Page 8: ...ING DIAGRAMS NTS 1 WIRING LINKING BEACON SOUNDER FACTORY FITTED 2 R1 R1 S2 S3 R1 S2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM...

Page 9: ...ve OUT ve OUT R1 R1 S2 R1 S2 S3 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K MIN 0 5W MIN RECOMMENDED MIN...

Page 10: ...SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D218 06 205 R S RAIT B ISARD R N POTTS OF SOUNDER XENON WIRING DI...

Page 11: ...ATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D218 06 205 R S RAIT B ISARD R N POTTS OF NTS 2 SW...

Page 12: ...Page left Intentionally blank...