8.3.23 Minimum voltage REX12D
Register 4(01..16)18 for channel 1-16, readable, functional code 3.
Contains the highest measured voltage of the channel since the last reset.
value range: 0-65535 (equals 0.0 – 655.35 V)
data length: 1 word
byte (LOW)
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
byte (HIGH)
bit 15
bit 14
bit 13
bit 12
bit 11
bit 10
bit 9
bit 8
description
32768
16384
8192
4096
2048
1024
512
256
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
fig. 33: Minimum voltage channel
The minimum voltage is made available as a standardised 16-bit-value with a resolution of 10 mV.
Example: measuring value operating voltage = 2512 ➞ real measuring value = 25.12 Volt
8.3.24 Current average REX12D
Register 4(01..16)19 for channel 1-16, readable, functional code 3.
Contains the current average of the channel since the last reset.
value range: 0-65535 (equals 0.0 – 655.35 V)
data length: 1 word
byte (LOW)
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
byte (HIGH)
bit 15
bit 14
bit 13
bit 12
bit 11
bit 10
bit 9
bit 8
description
32768
16384
8192
4096
2048
1024
512
256
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
fig. 34: Current average channel
The current average is made available as standardised 16 bit value with a resolution of 10 mA (resolution of the
channel is one decimal place, for simplification it is shown identically with the voltage with 2 decimal places).
Example: measuring value operating voltage = 710
-> real measuring value = 7.10 Ampere