15
8 Overview of Modbus registers
8.1 Voltage, current, status and control of channels
This list shows the various kinds of information and the corresponding registers.
Modbus
register
functional
code
data length
write/read
factor
description
47001
3
2 byte
read
100
load voltage F1
47002
3
2 byte
read
100
load voltage F2
47003
3
2 byte
read
100
load voltage F3
•
•
•
47016
2 byte
read
100
load voltage F16
47101
2 byte
read
100
load current F1
47102
2 byte
read
100
load current F2
47103
2 byte
read
100
load current F3
•
•
•
47116
2 byte
read
100
load voltage F16
47200
3
2 byte
status controller
47201
3
1 byte
read
status F1
47202
3
1 byte
read
status F2
47203
3
1 byte
read
status F3
•
•
•
47216
3
1 byte
read
status F16
47301
6 & 16
2 byte
write
control F1
47302
6 & 16
1 byte
write
control F2
47303
6 & 16
1 byte
write
control F3
•
•
•
47316
6 & 16
2 byte
write
control F16
fig. 16: Voltage, current, status and control of channels