23
9.1.2 »Configuration« configuration data of CPC20 Controller
The device configuration data for the controller consists of 17 bytes.
They will be read and written with COM = 0, channel = 0 and Index 3.
All parameters with possible conditions are described in the following table.
byte
type
range
description
Configuration data
CPC
0
byte
0xFF
bit 0 = writing via USB or web server. Allows changing of parame-
ters via the interfaces even when the bus connection is active.
Bit 1
TRUE: In the event of a bus interruption, the status of the load
outputs is maintained.
FALSE: In the event a bus interruption, all load outputs will be set
to the status OFF.
bit 2 saving mode, the LEDs will be dimmed for power reduction.
bit 3 = reserve
bit 4 = reserve
bit 5 = reserve
bit 6 = reserve
bit 7 = reserve
If not described otherwise, »True« means that the function is
active.
Control commands
lock EL-Bus 1 on
CPC channel 1 ... 16
1 HighByte
2 LowByte
Word
0xFFFF
Each bit represents a channel.
(bit 0 = channel 1; bit1 = channel 2 ...)
If the bit is set, this means that the channel is not
switched on or off via the control unit or the web server.
Control commands
lock EL-Bus 1
on CPC channel 17
... 32
3 HighByte
4 LowByte
Word
0xFFFF
Each bit represents a channel.
(bit 0 = channel 17; bit1 = channel 18 ...)
If the bit is set, this means that the channel is not
switched on or off via the control unit or the web server.
Control commands
lock EL-Bus 2 ex-
tension.
channel 1 ... 16
5 HighByte
6 LowByte
Word
0xFFFF
Each bit represents a channel.
(bit 0 = channel 1; bit1 = channel 2 ...)
If the bit is set, this means that the channel is not
switched on or off via the control unit or the web server.
Control commands
lock EL-Bus 2 ex-
tension.
channel 17 ... 32
7 HighByte
8 LowByte
Word
0xFFFF
Each bit represents a channel.
(bit 0 = channel 17; bit1 = channel 18 ...)
If the bit is set, this means that the channel is not
switched on or off via the control unit or the web server.
Control commands
lock EL-Bus 3 ex-
tension.
channel 1 ... 16
reserve
9 HighByte
10 LowByte
Word
0xFFFF
Each bit represents a channel.
(bit 0 = channel 1; bit1 = channel 2 ...)
If the bit is set, this means that the channel is not
switched on or off via the control unit or the web server.
Control commands
lock EL-Bus 3 ex-
tension.
channel 17 ... 32
reserve
11 HighByte
12 LowByte
Word
0xFFFF
Each bit represents a channel.
(bit 0 = channel 17; bit1 = channel 18 ...)
If the bit is set, this means that the channel is not
switched on or off via the control unit or the web server.
Control commands
lock EL-Bus 4 ex-
tension channel 1 ...
16 reserve
13 HighByte
14 LowByte
Word
0xFFFF
Each bit represents a channel.
(bit 0 = channel 1; bit1 = channel 2 ...)
If the bit is set, this means that the channel is not
switched on or off via the control unit or the web server.
Control commands
lock EL-Bus 4 ex-
tension channel 17
... 32 reserve
15 HighByte
16 LowByte
Word
0xFFFF
Each bit represents a channel.
(bit 0 = channel 1; bit1 = channel 2 ...)
If the bit is set, this means that the channel is not
switched on or off via the control unit or the web server.
fig. 26: Configuration data CPC
Summary of Contents for ControlPlex CPC20
Page 1: ...User Manual ControlPlex CPC20PN Controller...