background image

Instruction Manual

Controller CPC10PB

Summary of Contents for ControlPlex CPC10PB

Page 1: ...Instruction Manual Controller CPC10PB...

Page 2: ...p X41 10 4 2 2 ELBus connector sockets to power distribution system X51 X52 X53 X54 11 4 2 3 USB service and maintenance interface X61 12 4 2 4 PROFIBUS DP interface X81 12 5 Operating modes of the CP...

Page 3: ...ircuit protector 25 8 5 1 Current rating 25 8 5 2 Switch on behaviour 26 8 5 3 Overload disconnection 26 8 5 4 Trip time at overload 26 8 5 5 Trip time at short circuit 27 8 5 6 ON delay 27 8 5 7 Limi...

Page 4: ...to re use 2 2 Qualified personnel This user manual must exclusively be used by qualified personnel who are able based on their training and experience to realise arising problems when handling the pro...

Page 5: ...d offers the possibility of communication with up to 96 electronic circuit protectors Communication options comprise transmission of the operating condition of measuring values and device information...

Page 6: ...ustomers in available slot numbers of four eight twelve sixteen and twenty four electronic circuit protectors Power Distribution board 1 ELBus ELBus ELBus ELBus Power Distribution board 2 Power Distri...

Page 7: ...ctors and cables 0 V 0 V DIN rail EN 60715 35x7 5 not included fig 2 CPC10PB T1 1 Port 3 3 Dimensions of version CPC10PB T4 114 5 45 2 99 Provide space for connectors and cables COM 1 CPC10PB T4 COM 2...

Page 8: ...destruction of the device 3 4 2 Connector socket for the ELBus connector sockets X51 X52 X53 X54 These connector sockets served for connecting the communication unit CPC10 with up to four power distr...

Page 9: ...X81 The PROFIBUS DP connection is realised via a 9 pin SUB D connector It allows direct connection of the device with other PROFIBUS DP participants For mounting and special selection of cables and c...

Page 10: ...S CM CE DC 24 V X41 PWR X61 X81 NS MS CM CE DC 24 V X41 PWR bus controller CPC10PB T4 0 V 0 V 0 V 0 V fig 7 Terminals CPC10PB T1 and T4 4 2 1 Supply of terminal strip X41 Rated voltage DC 24 V 18 32 V...

Page 11: ...for second distribution board SVS201 PWR xx Cable length max 2 m Typically H07V K 1 5 mm Connector 1 ELBus ELB Data line Connector 2 ELBus DC 24 V Connector 3 ELBus GND only with CPC10PN T4 X53 COM 3...

Page 12: ...the Configuration Error Mode This operating mode only allows non cyclical data exchange Cyclical data exchange is prevented Leave this operating mode upon receipt of the correct slot parameters and c...

Page 13: ...advised to the superordinate control system and can be adopted by it or also overwritten The user can select the behaviour accordingly 5 6 Operating mode Firmware update mode The devices are supplied...

Page 14: ...nnected to a CPC10PB T4 the cycle time will comply with the 16 slot board and will thus be 530 ms for all four connected power distribution systems It is possible to choose the data quantity for the c...

Page 15: ...n his control accordingly For parameterisation of the individual electronic circuit protectors the corresponding user software ControlPlex Views is available for the USB service interface This softwar...

Page 16: ...1 0 1 reserve CPC10PB temporary error 0 1 CPC10PB hardware error 0 1 reserve reserve reserve network error 0 1 writing via USB blocked 0 1 status not set 0 status set 1 fig 11 Input data for global e...

Page 17: ...t byte circuit protector status 7 2 2 Control circuit protector Design of the output byte per circuit protector slot is as follows control circuit protector Value range switch load output on off reset...

Page 18: ...input bytes per circuit protector slot is as follows measuring value load voltage Value range 0 65535 Data length 2 byte unsigned integer Byte 2 LOW Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Des...

Page 19: ...ta type of the data to be read or written Valid value range 0 9 fig 16 Index structure Example Index for reading device information of the circuit protector in slot 2 02 1 parameter index slot number...

Page 20: ...0 1 0 1 0 1 0 1 0 1 0 1 0 1 write instruction via USB service interface 0 1 offline behaviour low freeze 0 1 power saving mode 0 1 reserve reserve reserve reserve reserve 0 1 writing via USB blocked...

Page 21: ...yte 0 holds the type version of the circuit protector Value range 80 81 Default value 80 Data length 1 byte unsigned character Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 description 128 64...

Page 22: ...0 device type 8 3 2 Serial number Byte 1 Byte 4 contain the serial number of the CPC10PB controller Value range 0 4294967295 Error Serial number not available 4294967295 Data length 4 byte unsigned lo...

Page 23: ...e information CPC10 hardware version 8 3 4 Software version Byte 7 Byte 8 contain the software version of the CPC10PB controller The software version is made available BCD coded It is coded as follows...

Page 24: ...6 2048 1024 512 256 Value 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 Byte 3 Bit 23 Bit 22 Bit 21 Bit 20 Bit 19 Bit 18 Bit 17 Bit 16 description 8388608 4194304 2097152 1048576 524288 262144 131072 65536 Value 0...

Page 25: ...re version 8 5 Device parameters circuit protector 8 5 1 Current rating The parameter in byte 0 determines the current rating of the ESX50D S100 Value range 1 A 10 A whole numbers Default value 1 A on...

Page 26: ...nal overload Value range 105 135 whole numbers Default value 120 Data length 1 byte unsigned character Byte 2 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 description 128 64 32 16 8 4 2 1 value 0 1...

Page 27: ...n of the load output of ESX50D Value range 50 ms 2 500 ms whole numbers in 10 ms steps Default value 100 ms Data length 1 byte unsigned character Byte 5 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0...

Page 28: ...ommand This will address all circuit protectors on a PWR board simultaneously The index part addressing the slot of the circuit protector has to be set to 99 in this case Value range 112 118 126 127 D...

Page 29: ...vent not available 0 event available 1 fig 40 Event messages circuit protector 8 8 Diagnostic messages circuit protector 8 8 1 Error memory Byte 0 holds the internal error memory of the circuit protec...

Page 30: ...0 1 no reason for trip available 0 0 0 0 0 0 0 0 0 trip reason short circuit 1 0 0 0 0 0 0 0 1 trip reason overload 2 0 0 0 0 0 0 1 0 reason for trip device temperature 3 0 0 0 0 0 0 1 1 reason for tr...

Page 31: ...tocol Byte 8 contains the relates latest feedback of the circuit protector to the CPC10PB controller Value range 0 255 Data length 1 byte unsigned character Byte 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2...

Page 32: ...fig 22 Configuration data reserve 22 fig 23 Device information CPC10 device type 22 fig 24 Device information CPC10 serial number 22 fig 25 Device information CPC10 hardware version 23 fig 26 Device i...

Page 33: ...counter 30 fig 43 Diagnosis circuit protector trip reason 30 fig 44 Diagnosis circuit protector operating voltage 30 fig 45 Diagnosis circuit protector device temperature 31 fig 46 Diagnosis circuit...

Page 34: ...e 2 8 90518 ALTDORF GERMANY Phone 49 9187 10 0 Fax 09187 10 397 E Mail info e t a de www e t a de Bedienungsanleitung Instruction manual CPC10PB Tx xxx D Bestell Nr Ref number Y31191401 Index a Issue...

Reviews: