28
5.4 Enter Switchpoint Overpressure
Select
in the display using „OK“. The overpressure range is from 0.8 mbar to
25 mbar and can be adjusted in steps of 0.05 mbar by turning the Wheel Shuttle. If you press
„OK“ while turning the Wheel Shuttle, the step size is 1 mbar. Save the selected value by
pressing „OK“. Factory presetting is 15.0 mbar.
The display now shows the saved value:
Confirm the displayed value by
pressing „OK“ again.
Turn the Wheel Shuttle clockwise or counterclockwise to continue the parametrization.
5.5 Enter min. Volume Flow
Select
in the display using „OK“. The minimum volume flow range is from 0.1
to 99.9 litres/sec. and can be adjusted in steps of 0.1 liters/sec. by turning the Wheel Shuttle.
If you press „OK“ while turning the Wheel Shuttle, the step size is 1 ltr/s. Save the selected
value by pressing „OK“. Factory presetting is 0.3 ltr/s.
Turn the Wheel Shuttle clockwise or counterclockwise to continue the parametrization.
5.6 Display Contrast
Select
in the display using „OK“. The factory setting of 4# can be changed by
turning the Wheel Shuttle. Save the selected value by pressing „OK“.
Turn the Wheel Shuttle clockwise or counterclockwise to continue the parametrization.
CONFIRM
OVER PRESSURE
XX:XX MBAR
SWITCHPOINT
OVERPRESSURE
XX:XX MBAR
DISPLAY
CONTRAST
# # # # - - - -
ENTER MIN.
VOLUME FLOW
XX.X L/S
4
5
6