27
5.1 Language
Select
in the display with „OK“ and choose from GERMAN, ENGLISH and
FRENCH by turning the Wheel Shuttle. Confirm the chosen language by pressing „OK“. The
display gets back to the language request, but this time in the selected language.
Turn the Wheel Shuttle clockwise or counterclockwise to continue the parametrization.
5.2 Enter Purge Volume
Select
in the display using „OK“. Purge volume range is from 5 ltr. to 50.000
ltr. and can be adjusted in steps of 5 litres by turning the Wheel Shuttle. If you press „OK“
while turning the Wheel Shuttle the step size is 50 litres. Save the selected value by pressing
„OK“. Factory presetting is 200 ltr.
The display now shows the saved value:
Confirm the displayed value by
pressing „OK“ again.
Turn the Wheel Shuttle clockwise or counterclockwise to continue the parametrization.
5.3 Enter Switchpoint min. Pressure
Select
in the display using „OK“. The min. pressure range is from 0.8 mbar to
25 mbar and can be adjusted in steps of 0.05 mbar by turning the Wheel Shuttle. If you press
„OK“ while turning the Wheel Shuttle, the step size is 1 mbar. Save the selected value by
pressing „OK“. Factory presetting is 0.9 mbar.
The display now shows the saved value:
Confirm the displayed value by
pressing „OK“ again.
Turn the Wheel Shuttle clockwise or counterclockwise to continue the parametrization.
LANGUAGE
?
ENTER PURGE
VOLUME
XXXXX L
CONFIRM PURGE
VOLUME
XXXXX L
CONFIRM
MIN. PRESSURE
XX:XX MBAR
SWITCHPOINT
MIN. PRESSURE
XX:XX MBAR
1
2
3