User Manual EE850 Duct Sensor

INTEGER 16 bit

Parameter

Unit

Scale

3)

Register number

1)

 [DEC]

Register address

2)

 [HEX]

Read register: function code 0x03

Temperature T

° C

100

4002

0xFA1

° F

50

4003

0xFA2

Relative Humidity

%

100

4011

0xFAA

CO

2

 (average)

ppm

1

4031

0xFBE

CO

2

 (raw)

ppm

1

4032

0xFBF

Water vapour partial pressure

mbar

10

4051

0xFD2

psi

1000

4052

0xFD3

Dew point temperature

°C

100

4053

0xFD4

°F

100

4054

0xFD5

Absolute humidity

g/m

3

10

4057

0xFD8

gr/ft

3

10

4058

0xFD9

Mixing ratio

g/kg

10

4061

0xFDC

gr/lb

10

4062

0xFDD

Specific enthalpy

kJ/kg

1

4063

0xFDE

ft lb/lb

1

4064

0xFDF

BTU/lb

1

4065

0xFE0

Frost point temperature

°C

100

4066

0xFE1

°F

100

4067

0xFE2

1) Register number starts from 1

2) Register address starts from 0

3) Examples: For scale 100, the reading of 2550 means a value of 25.5. For scale 50, the reading of 2550 means a value of 51.

Communication settings (INTEGER 16 bit)
Parameter

Register number

1)

 [DEC]

Protocol address

2)

 [HEX]

Write register: function code 0x06

Slave ID (Modbus address)

3)

1

0x00

Modbus protocol settings

4)

2

0x01

1) Register number starts from 1.

2) Protocol address starts from 0.

3) 

If the ID is set via DIP switch the response will be NAK.

4) For Modbus protocol settings see Application Note Modbus AN0103 (available on 

www.epluse.com/EE850

).

INFO (read register)
Parameter

Register number

1)

 [DEC]

Protocol address

2)

 [HEX]

Read register: function code 0x03 / 0x04

Serial number (as ASCII)

  1

0x00

Firmware version

  9

0x08

1) Register number starts from 1.

2) Protocol address starts from 0.

3.6  Modbus RTU Example

Example of MODBUS RTU command for reading the CO

2

 (float value) CO

2

 = 1288,34375 ppm from the 

register 0x424

Device EE850; slave ID 67  [0x43]

Reference document, chapter 6.3: http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf

Request [Hex]:   43 03 04 24 00 02 8A 12

Modbus ID 

address

Function 

code

Starting 

address Hi

Starting 

address Lo

No. of 

register Hi

No. of 

register Lo

CRC

Request [Hex]:

43

03

04

24

00

02

8A

12

Response [Hex]:  43 03 04 0B 00 44 A1 68 AB

Modbus ID 

address

Function 

code

Byte count Register 1 

value Hi

Register 1 

value Lo

Register 2 

value Hi

Register 2 

value Lo

CRC

Response [Hex]:

43

03

04

0B

00

44

A1

68

AB

Summary of Contents for EE850

Page 1: ...BA_EE850 v1 5 Modification rights reserved User Manual EE850 Duct Sensor for CO2 Humidity and Temperature...

Page 2: ...equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmf...

Page 3: ...3 Installation Start up and Operation 5 1 3 Environmental Aspects 5 2 Scope of Supply 5 3 Product Description 6 3 1 General 6 3 2 Installation 6 3 3 Electrical Connection 7 3 4 Setup and Adjustment 7...

Page 4: ...ructions 1 2 1 General Safety Instructions Avoid any unnecessary mechanical stress and inappropriate use The device shall not be exposed to extreme thermal stress Installation electrical connection ma...

Page 5: ...into operation and maintenance may be performed by qualified personnel only Such staff must be authorized by the operator of the facility to carry out the mentioned activities The qualified staff mus...

Page 6: ...n the EE850 cover Depending on the EE850 version the response time specified is only valid for direction marked with the blue arrow with respect to the cable gland position Air flow in the opposite di...

Page 7: ...are EE PCS One can change the CO2 output signal the scaling of the outputs and perform CO2 RH and T adjustment calibration Please note The EE850 may not be connected to any additional power supply whe...

Page 8: ...e scaling of the output can be changed by using USB Configuration Adapter HA011066 and Product Configuration Software EE PCS Example The initial scaling of the outputs is The output scale after the ch...

Page 9: ...address has to be set via PCS Modbus Slave device factory setting EE850 67 permitted values 1 247 BACnet Master device factory setting EE850 67 permitted values 0 127 Example Slave address is set via...

Page 10: ...code is located in the register addresses 0x00 0x07 16 bits per address The firmware version is located in the register address 0x08 bits 15 8 major release bits 7 0 minor release The beforementioned...

Page 11: ...Slave ID Modbus address 3 1 0x00 Modbus protocol settings4 2 0x01 1 Register number starts from 1 2 Protocol address starts from 0 3 If the ID is set via DIP switch the response will be NAK 4 For Modb...

Page 12: ...re Working range 20 60 C 4 140 F Accuracy at 20 C 68 F 0 3 C 0 54 F Response time t63 50 s Relative Humidity Working range 0 95 RH Accuracy at 20 C 68 F 3 RH 20 80 RH Response time t63 10 s Outputs An...

Page 13: ...lin 69130 Ecully Tel 33 4 74 72 35 82 E mail info epluse fr E E Elektronik Germany Sch ne Aussicht 8 C 61348 Bad Homburg Tel 49 6172 13881 0 E mail info epluse de E E Elektronik Italy Via Alghero 17 1...

Reviews: