QUICK GUIDE
EE600 -
Differential Pressure Sensor
Find this document and further product information on our website at www.epluse.com/ee600.
E+E Elektronik Ges.m.b.H.
Langwiesen 7 • 4209 Engerwitzdorf • Austria
Tel: +43 7235 605-0 • Fax: +43 7235 605-8
[email protected] • www.epluse.com
LG Linz Fn 165761 t • VAT No. ATU44043101
Place of Jurisdiction: 4020 Linz • DVR0962759
QG_EE600 // v1.3 // Modification rights reserved // 350197
INFORMATION
+43 7235 605 0 / [email protected]
EE600 with Analogue Output
Installation
Pressure Connection
Use a Ø7.5 mm drill for installing the pressure connection nipples into the duct.
Installation Examples
1) Measuring range 2) Display backlight 3) These and further settings can be changed with PCS10 via USB configuration adapter (HA011066) while DIP
switch S9 = 1. Only available with version with 10 DIP switches.
S1
S2
MR
1)
S3
S4
Time
S5
S6
Unit
S7 DPB
2)
S8
Output
S9
Setting
3)
0
0
100 %
0
0
50 ms
0
0
Pa
0
on
0
0 - 10 / 4 - 20 mA
0
DIP switch
1
0
75 %
1
0
500 ms
1
0
mbar
1
off
1
0 - 5 / 0 - 20 mA
1
PCS10
0
1
50 %
0
1
2 s
0
1
inch WC
1
1
25 %
1
1
4 s
1
1
mm H
2
O
Red LED
Flashing (1s interval)
= The measured data is out of the
selected range (overload or reversed
pressure connection)
One flash (2s)
= Indicates the failure of the attempt to
adjust zero point or span point, or to
return to factory adjustment
Green LED
Flashing (1s interval)
= EE610 operates normally, the
measured data is within the selected
measuring range
One flash (2s)
= Confirms adjustment or return to
factory settings
Off
=
No power supply or
electronics failure
Fast flashing
(0.2 s interval)
= Auto-zero is executed, first time 10 s
after start / reset
Connection Diagram
V+
GND
V+
A (=D+)
RS485
B (=D-)
GND
AV
1
2
3
1
2
3
4
+
-
~
~
+
-
~
~
V / mA
Power supply
24 V AC ±20 %
15...35 V DC
Power supply
15 - 35 V DC
24 V AC ±20 %
Important note:
The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling,
installation, wiring, power supply and maintenance of the device.
Analogue Output
Digital Output
User Interface - LED Indication