User Manual EE360
Moisture in Oil Sensor | 23
Fig. 17 Ethernet Module - DHCP setting
The setup of the Modbus TCP communication can be performed via PCS10 Product Configuration Software or via
display and push buttons (see 10 Appendix, Fig. 42 IP settings).
Changing the IP address via PCS10 or the display is only possible if the DHCP jumper is set to “Static”.
Otherwise the IP settings are read-only.
NOTICE
Supported Ethernet standard: 802.3i/u/x and af. IPv6 is not supported.
5.4.3. Retrofit with Ethernet Module
The EE360 can be retrofitted with an Ethernet Module. Before retrofitting please make sure, that the EE360
firmware is updated to the latest version by using the Product Configuration Software PCS10.
▪
Firmware for sensor: V 1.0.22 or higher
▪
Firmware for display: V 1.0.9 or higher
Description
Order Code
Ethernet Module for remote probe
HA010606
Tab. 7
Accessories order code
5.5 Modbus Register Map
The measured data is saved as a 32 bit floating point values (data type FLOAT32) and as 16 bit signed integer
values (data type INT16).
FLOAT 32
Parameter
Unit
Register number
1)
[DEC]
Protocol address
2)
[HEX]
Read register: function code 0x03 / 0x04
Relative humidity
1)
%
31021
3FC
Temperature
°C
31003
3EA
Temperature
°F
31005
3EC
Temperature
K
31009
3F0
Water activity
a
w
31135
46E
Water content
x
31141
474
1) Register number starts from 1.
2) Register address starts from 0.
Tab. 8
EE360 FLOAT32 measured data registers