User Manual EE160 Humidity and Temperature Sensor for HVAC Applications
EE160-MxTxAx (analogue output)
Using the EE-PCA Product Configuration Adapter with cable and the EE-PCS Product Configuration
Software.
PC
Please note:
The EE160 must be powered when using the EE-PCA kit.
Bus Termination
If required, the RS485 bus termination can be realized with 120 ohm resistor, jumper on the board.
4.1 EE-PCS Product Configuration Software
To use the software for performing adjustments and changes in settings, please proceed as follows:
1. Download the EE-PCS Product Configuration Software from
install it on the PC.
2. Connect the EE160 to the PC using the USB configuration adapter or the EEE-PCA product
configuration adapter, respectively.
3. Start the EE-PCS software.
4. Follow the instructions on the EE-PCS opening page for scanning the ports and identifying the
connected device.
5. Click on the desired setup or adjustment mode from the main EE-PCS menu on the left and follow
the online instructions of the EE-PCS
4.2 Address Setting
Address Switch
Address Switch
Address setting via EE-PCS Product Configuration Software:
All DIP switches at position 0 → address has to be set via EE-PCS
Modbus
(Slave device): factory setting EE160: 245 (permitted values:
1…247).
BACnet
(Master device): factory setting EE160: 2 (permitted values: 0…127).
Example:
Slave address is set via configuration software.
Address setting via DIP switch:
Modbus
(Slave device): Setting the DIP switch to any other address than 0,
overrules the slave address set via configuration software (permitted values:
1…247).
BACnet
(Master device): Setting the DIP switch to any other address than 0,
overrules the slave address set via configuration software.
BACnet Note:
permitted values are 0…127. The 8
th
bit of the DIP switch is
ignored
(ID 127 = 0111 111).
To set address 0 via DIP switch, the 8th bit shall be set to 1 ( ID 0 = 1000
0000).
Example:
Slave address set to 11 ( = 0000 1011 binary).
0
1
0
1
0 0 0 0 0 0 0 0
1 1 0 1 0 0 0 0