User Manual EE160 Humidity and Temperature Sensor for HVAC Applications

4.5  Modbus Register Map

The measured data is saved as a 32 bit floating point values (data type FLOAT) and as 16 bit signed 

integer values (data type INTEGER).

FLOAT 32 bit:

Parameter

Unit

Register number

1)

 [Dec]

Register address

2) 

[HEX]

Read register: function code 0x03

Temperature T 

°C, °F

3)

26

0x19

Relative humidity RH, Uw 

% RH

28

0x1B

1) Register number starts from 1.

2) Register address starts from 0.

3) The choice of measurement units (metric or non-metric) is done at the time of ordering, see the ordering guide in the EE160 data sheet. It is not 

possible to switch from metric to non-metric or vice versa by means of the EE-PCS.

INTEGER 16 bit:

Parameter

Unit

Scale

1)

Register number

2)

 [Dec]

Register address

3) 

[HEX]

Read register: function code 0x03

Temperature T

°C, °F

4)

100

301

0x12C

Relative humidity RH, Uw

% RH

100

302

0x12D

1) Example: For scale 100, the reading of 2550 means a value of 25.5.

2) Register number starts from 1.

3) Register address starts from 0.

4) The choice of measurement units (metric or non-metric) is done at the time of ordering, see the ordering guide in the EE160 data sheet. It is not 

possible to switch from metric to non-metric or vice versa by means of the EE-PCS.

4.6  Modbus Message Example

Example of Modbus RTU command for reading the temperature (float value) T = 23,290008 °C 

from the register 0x19.

Device EE160; slave ID 245 [0xF5] 

Reference document, chapter 6.3: 

www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf

See Application Note Modbus AN0103 (available at 

www.epluse.com/EE160

)

Modbus ID 

address

Function 

code

Starting 

address Hi

Starting 

address Lo

No. of 

register Hi

No. of 

register Lo

CRC

Request [Hex]:

F5

03

00

19

00

02

01

0F

Modbus ID 

address

Function 

code

Byte 

count

Register 1 

value Hi

Register 1 

value Lo

Register 2 

value Hi

Register 2 

value Lo

CRC

Response Hex]:

F5

03

04

51

F0

41

BA

98

10

Decoding of floating point values:

Floating point values are stored according IEEE754 standard. The byte pairs 1, 2 and 3, 4 are inverted 

as follows:

MMMMMMMM

MMMMMMMM

SEEEEEEE

EMMMMMMM

Byte 3

Byte 4

Byte 1

Byte 2

Example:

Response [Hex]

Value in decimal

 Byte 1 (Register 2 - Hi)

Byte 2 (Register 2 – Lo)

Byte 3 (Register 1 - Hi)

Byte 4 (Register 1 - Lo)

41

BA

51

F0

23.290008

Summary of Contents for EE160

Page 1: ...BA_EE160 v2 0 Modification rights reserved User Manual EE160 Humidity and Temperature Sensor for HVAC Applications...

Page 2: ...equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmf...

Page 3: ...2 Scope of Supply 5 3 Product Description 6 3 1 General 6 3 2 Dimensions 6 3 3 Electrical Connection 6 4 Setup and Adjustment 7 4 1 EE PCS Product Configuration Software 8 4 2 Address Setting 8 4 3 B...

Page 4: ...al Safety Instructions The device and mainly the filter cap shall not be exposed to unnecessary mechanical stress When replacing the filter cap make sure not to touch the sensing elements The device m...

Page 5: ...by the operator of the facility to carry out the mentioned activities The qualified staff must have read and understood this user manual and must follow the instructions contained within All process a...

Page 6: ...the E E sensor coating ensure long term stable and accurate measurements The user can set the RS485 interface parameters the output scaling and perform one or two point adjustment for RH and T with an...

Page 7: ...adapter on adapter connected to EE160 and PC no communication with EE PCS flashing communication in progress with EE PCS off adapter not connected to EE160 and PC 4 Setup and Adjustment The EE160 is...

Page 8: ...cted device 5 Click on the desired setup or adjustment mode from the main EE PCS menu on the left and follow the online instructions of the EE PCS 4 2 Address Setting Address Switch Address Switch Add...

Page 9: ...firmware version is located in the register address 0x08 bits 15 8 major release bits 7 0 minor release The sensor name is located in register address 0x09 The beforementioned registers can be read o...

Page 10: ...choice of measurement units metric or non metric is done at the time of ordering see the ordering guide in the EE160 data sheet It is not possible to switch from metric to non metric or vice versa by...

Page 11: ...eplusecal com Calibration and adjustment by the user Depending on the level of accuracy required the humidity reference can be Humor 20 Humidity Calibrator please see www epluse com Omniport30 handhe...

Page 12: ...0 mA 10 V RL x 20 mA UV 35 V DC Current consumption typ 4 20 mA output 0 10 V output RS485 24 V DC supply max 40 mA 5 mA 5 mA 24 V AC supply 13 mArms 15 mArms Connection Screw terminals max 1 5 mm2 Ho...

Page 13: ...lin 69130 Ecully Tel 33 4 74 72 35 82 E mail info epluse fr E E Elektronik Germany Sch ne Aussicht 8 C 61348 Bad Homburg Tel 49 6172 13881 0 E mail info epluse de E E Elektronik Italy Via Alghero 17 1...

Reviews: