E. DOLD & SOHNE SAFEMASTER C UG 6980 Datasheet / Operating Instructions Download Page 17

17

 UG 6980 / 02.09.16 en / 756

Input

  

Nominal voltage U

N

 

DC 24 V

Voltage range: 

 

0.8 ... 1.1 U

N

Nominal consumption:

 

typ. 1.9 W

Short-circuit protection: 

 

Internal PTC

Overvoltage protection: 

 

Internal VDR

Duty-cycle ON button:

 

0.1 s < t

EIN

 < 3 s

Duty-cycle Reset button:

 

> 3 s

Safety function 
Safety mat / safety edge (4)

max. permitted 
safety edge contact resistance:  1000 

Ω

switching current at short circuit:  typ. 15 mA at U

N

Light curtains (8)

control current via S12, S22: 

typ. 8 mA at U

N

Min. voltage on terminals 
S12, S22 when relay activated:  DC 10 V

Output

Contacts

UG 6980.02 

2 NO contacts 

UG 6980.04 

4 NO contacts 

The NO contacts can be used for safe braking.

Thermal current I

th

 

max. 8 A 

   

(see quadratic total current limit curve)

Safety function
E-Stop (1) (6), Safety gate (2) (7),
Exclusive or contacts (5)

Start up at U

N

:  

< 65 ms

Release delay at U

and 

disconnecting the supply:  

< 40 ms

Release delay at U

and 

disconnecting S12,S22: 

< 60 ms

Two-hand control (3)

Start up at U

N

:  

< 110 ms

Release delay at U

and

disconnecting the supply:  

< 40 ms

Release delay at U

and 

disconnecting S12,S22: 

< 60 ms

simultaneity demand: 

max. 0,5 s

Safety mat (4)

Start up at U

N

:  

< 85 ms

Release delay at U

and 

disconnecting the supply:  

< 40 ms

Release delay at U

and 

disconnecting S12,S22: 

< 60 ms

Light curtains (8)

Start up at U

N

:  

< 35 ms

Release delay at U

and 

disconnecting the supply:  

< 40 ms

Release delay at U

and 

disconnecting S12,S22: 

< 25 ms

Switching capacity

to AC 15
NO contacts:  

3 A / AC 230 V  

IEC/EN 60 947-5-1

to DC 13
NO contacts:  

2 A / DC 24 V  

IEC/EN 60 947-5-1

Electrical life

at 5 A, AC 230 V cos 

j

 = 1:  

> 2.2 x 10

5

 switching cycles

Perm. operating frequency: 

max. 1800 switching cycles / h

Short circuit strength

max. fuse rating:  

6 A gL 

IEC/EN 60 947-5-1

Mechanical life: 

 

10 x 10

6

 switching cycles

Semiconductor monitoring output
(not safety): 

 

max. 50 mA DC 24 V, plus switching

 

Technical Data

Operating mode

Manual or auto start is chosen by wiring. On manual start S21 has to be 
connected to ST1! via an NO push button. For auto start S21 is connected 
to ST2. If both inputs are connected to S21 the unit goes into safe failure 
mode. A restart or new start of the device has to be made. When selecting 
the safety function 2-hand control (3), only automatic start is possible.

Line fault detection e.g. monitoring of ON-button

If the On-button pressed more than 3 s the adequate output contacts of the 
safety function can't be switch. The output contacts can be energized when 
the On-button pressed again (0.1 s < t

ON

 < 3 s).

A line fault is detected if the On-button more than 10 s is actuated. The 
output contacts of the adeauate safety function can only be energized with 
a reset or re-start with on an off switching of power supply. 

Reset and external failures:

The reset input is used to reset external failures (application failures or 
removable external failures as e.g. a line fault on reset button). If the reset 
signal is connected to the input for more than 3 sec the unit makes a reset. 
A new reset is only possible when the reset signal had been switched off 
temporarily.
If an external failure occurs because both input channels of a safety function 
did not switch on or off within the simultanious time, a reset is only possible 
if both channels are switched to off state after removing failure cause.
 

Setting

On the variant /0_ _ the safety function can be set via rotary switch. 
Possible functions:

Fct. 

Safety function

1

E-Stop

cross fault detection

2

Safety gate

3

Two-hand control

4

Safety mat / Safety edge

5

Exclusive or contacts

6

E-Stop

without 

cross fault detection

7

Safety gate

8

Light curtain

Practical Notes

Operating Potentiometer

Poti "Fkt"  

Adjustment of safety function

Summary of Contents for SAFEMASTER C UG 6980

Page 1: ...Multifunktionales Sicherheits modul UG 6980 0266730 Datenblatt Betriebsanleitung DEUTSCH E DOLD S HNE KG Postfach 1251 78114 Furtwangen Deutschland Telefon 49 7723 6540 Fax 49 7723 654356 dold relays...

Page 2: ...unktionsdiagramm 6 Blockschaltbilder 6 Blinkcodes zur Fehlermeldung 6 Hinweise 7 Bedienelemente 7 Technische Daten 7 Technische Daten 8 UL Daten 8 Standardtype 8 Bestellbeispiel 9 Vorgehen bei St rung...

Page 3: ...en wird wenn die entsprechenden Vorsichtsma nahmen nicht ge troffen werden WARNUNG Bedeutet dass Tod oder schwere K rperverletzung eintreten kann wenn die entsprechenden Vorsichtsma nahmen nicht getro...

Page 4: ...4 UG 6980 02 09 16 de 756...

Page 5: ...gef hrte Ausgangskontakte Ausgang max 4 Schlie er 1 Halbleitermeldeausgang LED Anzeigen Betriebsspannung verz gerte Kontakte und Fehler Ger teanschl sse UG 6980 PS steckbare Anschlussbl cke mit Schrau...

Page 6: ...chutzt r t max 3s Lichtschranken t max 1s t max 0 5s andere Zeiten auf Anfrage Antivalente Schalter Zweihandschaltung diff diff diff max Einschaltzeit des Ein Tasters Standart t max 3s andere Zeiten a...

Page 7: ...altend Hinweise Technische Daten Betriebsarteinstellung Die Einstellung der Betriebsart Hand oder Automatischer Start wird an hand der Verdrahtung festgelegt Beim Hand Start muss S21 ber einen Ein Tas...

Page 8: ...Schnellbefestigung Hutschiene IEC EN 60 715 Nettogewicht ca 210 g Ger teabmessungen Breite x H he x Tiefe UG 6980 PS 22 5 x 110 x 120 3 mm UG 6980 PC PT 22 5 x 120 x 120 3 mm Die Sicherheitsfunktionen...

Page 9: ...mp abnehmbare Klemmenbl cke mit Federkraftklemmen PS plugin screw abnehmbare Klemmenbl cke mit Schraubklemmen PT plugin TWIN cageclamp abnehmbare Klemmenbl cke mitFederkraftklemmen2 Leiter Kontakte Ge...

Page 10: ...S12 S1 M11124 S21 S22 S11 S12 M10753 Not Aus S21 Fkt Schaltmatte Schaltleiste 4 mit Querschlusserkennung SIL 3 PL e Kat 4 Fkt Antivalente Schalter 5 mit Querschlusserkennung SIL 3 PL e Kat 4 Fkt Not...

Page 11: ...Instructions ENGLISH E DOLD S HNE KG P O Box 1251 D 78114 Furtwangen Germany Tel 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold com Translation of the original instructions SAFEMASTER C...

Page 12: ...k Diagrams 16 Fault Indication by Flashing Code 16 Practical Notes 17 Operating Potentiometer 17 Technical Data 17 Technical Data 18 UL Data 18 Standard Type 18 Variants 19 Troubleshooting 19 Maintena...

Page 13: ...ranty DANGER DANGER Indicates that death or severe personal injury will result if proper precautions are not taken WARNING WARNING Indicates that death or severe personal injury can result if proper p...

Page 14: ...14 UG 6980 02 09 16 en 756...

Page 15: ...at external error green LED K1 K2 02 e g K1 K4 04 on when relay K1 and K2 02 energized e g when relay K1 K2 K3 and K4 04 energized flashes at external error S12 A2 14 GND S11 A1 13 RES S21 ST1 23 ST2...

Page 16: ...ted safety function E Stop safety gate t max 3s Light curtais t max 1s Two hand control t max 0 5s other times on request Exclusive or contacts diff diff diff max actuation time of start button Standa...

Page 17: ...106 switching cycles Semiconductor monitoring output not safety max 50 mA DC 24 V plus switching Technical Data Operating mode Manual or auto start is chosen by wiring On manual start S21 has to be co...

Page 18: ...12 Sol Str PT terminal AWG 24 16 Sol str nfo Technical data that is not stated in the UL Data can be found in the technical data section Technical Data UL Data Standard Type General Data Nominal oper...

Page 19: ...ls PS plug in screw pluggable terminal blocks with screw terminals PT plug in Twin cage clamp pluggable terminal blocks withcageclampterminals2 wire Contacts Type UG 6980 02 Quadratic total current li...

Page 20: ...S21 S22 S11 S12 M10753 Not Aus S21 Fct Safety mat Safety edge 4 with cross fault detection SIL 3 PL e Cat 4 Fct Exclusive or contacts 5 with cross fault detection SIL 3 PL e Kat 4 Fct E Stop 6 withou...

Page 21: ...nuel d utilisation FRAN AIS E DOLD S HNE KG B P 1251 78114 Furtwangen Allemagne T l 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold com Traduction de la notice originale SAFEMASTER C Mod...

Page 22: ...notements pour signalisation des d fauts 26 Remarques 27 Commande potentiom tre 27 Caract ristiques techniques 27 Caract ristiques techniques 28 Donn es UL 28 Versions standard 28 Variantes 29 Diagnos...

Page 23: ...que la mort ou des blessures graves vont survenir en cas de non respect des pr cautions demand es AVERTISSEMENT AVERTISSEMENT Indique que la mort ou des blessures graves peuvent survenir si les pr cau...

Page 24: ...24 UG 6980 02 09 16 fr 756...

Page 25: ...y Level SIL 3 selon IEC EN 61508 et IEC EN 61511 Selon EN 50156 1 pour installations de chauffage D tection de d faut de court circuit sur le bouton Marche Activation manuelle par le bouton Marche ou...

Page 26: ...3s Barri res immat rielles t max 1s Commande bimanuelle t max 0 5s autres temps sur demande porte de protection contacts antivalents diff diff diff Temps d enclenchement du B P Marche Standard t max 3...

Page 27: ...Long vit m canique 20 x 106 manoeuvres Sorties de signalisation semi conducteurs non s curitaires 50 mA DC 24 V max com front positif Remarques Caract ristiques techniques Mode de service La programm...

Page 28: ...echniques qui ne sont pas sp cifi es ci dessus sont sp cifi es dans les valeurs techniques g n rales Caract ristiques techniques Donn es UL Versions standard Caract ristiques g n rales Type nominal de...

Page 29: ...PS plug in screw d brochables avec bornes vis PT plugin Twin cageclamp d brochables avec bornes ressorts 2 cond Garnissage en contacts Type d appareil M10700_a I I I I I I I I I 2 2 2 2 2 1 2 3 4 App...

Page 30: ...124 S21 S22 S11 S12 M10773 d arr t d urgence S21 Fct Tapis bandeaux de s curit 4 avec d tection des courts circuits transversaux SIL 3 PL e Cat 4 Fct Interrupteur compl mentaire 5 avec d tection des c...

Page 31: ...24 to 12 2 x 0 2 1 0 mm2 2 x AWG 24 to 18 A 10 mm 1 x 0 2 2 5 mm2 1 x AWG 24 to 12 A 8 mm 1 x 0 2 1 5 mm2 1 x AWG 24 to 16 M10249 A A 7 mm 1 x 0 25 2 5 mm2 1 x AWG 24 to 12 2 x 0 25 1 0 mm2 2 x AWG 2...

Page 32: ...FR Dimensions dimensions en mm M4345_a M4345_a 35 115 3 0 0 7 122 6 0 0 7 B A 106 9 DE Montage Demontage der PS PC PT Klemmenbl cke EN Mounting disassembly of the PS PC PT terminal blocks FR Montage...

Page 33: ...ktion an das Ger t Intervall f r zyklische berpr fung der Sicherheitsfunktion Demand to our device based on the evaluated neccessary safety level of the application Intervall for cyclic test of the sa...

Page 34: ...34 UG 6980 02 09 16 de en fr 756 DE EG Konformit tserkl rung EN CE Declaration of Conformity FR D claration de conformit europ enne...

Page 35: ...35 UG 6980 02 09 16 de en fr 756 DE Notizen EN Notice FR Note...

Page 36: ...36 UG 6980 02 09 16 de en fr 756 E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Reviews: