7

.3

.

 

Operation Functions

7

.3.1

.

 

Standby (OFF Mode):

 

The mode where boiler

 

can 

be set to standby mode. In this mode, no requests for heating 
water and domestic water can be made. To activate the OFF 
mode, it is necessary to keep button no. 1 (position selector) 
pressed  for  3  seconds  continuously.  When  -OFF-

 

is 

displayed on screen, mode is activated.

7

.3.2

.

 

Air Purge

 

Mode (AP Mode):

 

It is the process that the 

boiler

 

automatically  activates  to  discharge  air  in  the  central 

heating  installation  for  160  seconds.  In  this  mode,  "AP"  is 
displayed  on  the  screen.  The  circulation  pump  runs  for  15 
seconds and

 

then stops every 5 seconds in intervals of every 

20 seconds. The three-way valve motor also changes position 
between a CH-DHW in 40 seconds. The situations where this 
mode is activated is listed here below.

9

 

Once the boiler

 

is powered for the first time or after the 

electricity has been

 

switched off and on,

9

 

After the reset operation following the overheating fault 

(E03),

9

 

After elimination of high water pressure (F40) or low water 

pressure (F37) error,

CAUTION: Do not press 'RESET' while 
AP mode is active.

7

.3.3

.

 

Winter  mode-Radiator

 

Heating:

 

If  the  boiler

 

in  the 

standby  position  is  set  to  the  winter  position,  it

 

will  heat  the 

water in the heating circuit until the domestic water is needed. 
In  the  winter  mode,  both  the  tap  and  the  radiator  icon  are 
displayed on the LCD screen. 

When a

 

request for heating is made for radiator, radiator icon 

flashes  (once/second),  tap  icon  stays  fixed.

 

When  a  request 

for  domestic  water  is  made,  tap  icon  flashes  (once/second), 
radiator  icon  stays  fixed.  In  this  mode,  radiator  heating 
circuit's  temperature

 

can  be  set  between  30-

80  °

C.  For 

under floor heating applications, the temperature range can be 
set between 30-45 

°

C.

7

.3.4

.

 

Summer Mode:

 

If the boiler

 

in the OFF position is set 

to

 

the  summer  position,  the  boiler

 

will  only  respond  to  the 

domestic  hot  water  demands.  In  summer  mode,  the  tap 
symbol  appears  fixed  on  the  LCD  screen,  the  radiator  icon 
does  not  appear.  When  the  domestic  hot  water  is  heating 
request, the tap symbol flashes (1 time/sec). In this mode, the 
domestic  hot  water  temperature  can  be  adjusted  between 
30-

65 °C.

7

.3.5

.

 

Comfort Mode:

 

The standard operating mode of the 

boiler

 

is Comfort mode. By pressing the "Reset" button, Eco-

Comfort  modes  can  be  switched.  When  Comfort  mode  is 
active,  "Comfort"  icon  is  displayed  on  the  LCD  screen. 
Comfort  mode  is  only  for  radiator  heating  circuit.  It  has  no 
effect on use of domestic water circuit. In this mode, the boiler

 

responds to fast heating demands by running in modulation

.

7

.3.7

Annual  Maintanence 

Reminder

:

 

This  mode  reminds 

user that “annual maintanence time 
is  very  soon”.

 

When  this  mode  is 

active,  only  "ASE"  is  displayed  on 
screen and boiler

 

continues to meet 

heating 

requests. 

Electrical 

connection of boiler must be always 
connected  to  mains,  otherwise 
function  will  not  work  properly. 
When  you  see  "ASE"  on  screen, 
please  check  your  boiler  start  up 
date  and  contact  with  gas  safe 
engineer  if  annual  maintanence 
period  is  arrived.  If  maintance  of 
the  boiler

 

is 

done  before  “ASE” 

appears  on  screen,  you  can  skip  it 

by pressing “R” button.

7

.3.8

Anti-Frost  Mode:

 

During  the  winter 

season, when the installation water temperature falls 
below 

6  °  C,  the  anti

-freeze  function  is  activated 

and the boiler

 

continues to operate until the water 

output of 

installation rises to 15 ° C. In order for anti

-

freeze  function  to  be  activated,  the  following 
conditions  must  be  checked  and  ensured  by  the 
customer.

9

 

The power supply of the boiler

 

must be switched 

on.

9

 

The gas valve and radiator valves must be open.

9

 

Water

 

pressure of system should be at 

appropriate level.

9

 

The anti-freeze function helps protect your boiler, 

it does not protect your installation.

9

 

If the boiler

 

will not be operated for a while in 

places where there is risk of freezing, then it is 
necessary

 

to

 

drain the water

 

or to use an anti-freeze 

agent

7.3.6. ECO Mode:

 

By pressing the "Reset" button, 

Eco-Comfort  modes  can  be  switched.  When  Eco 

mode  is  active,  "Eco"  icon  is  displayed  on  the  LCD 

screen. Eco mode is only for radiator heating circuit. 

It has no effect on use of domestic water circuit. This 

mode  allows  savings  on  fuel  by  performing  on-off 

operation. 

14

Summary of Contents for 8116450010

Page 1: ...3527 86 35 0 0 67 3527 86 35 0 21 16 1 2 5 23 5 7 1 167RUCTIONS ...

Page 2: ...ombi Boiler in Terms of Safety and Energy Consumption 3 2 Clogging in Installation 3 3 Cleaning of Boiler 3 4 Boiler Features 3 5 Additional Recommendations by ECA to Customer To Have High Heating Performance 4 4 TECHNICAL DATA 5 5 ERP TECHNICAL DATA 5 1 PACKAGE LABEL CALCULATIONS 10 6 6 USING THE BOILER 13 6 1 Switching Off the Boiler 13 7 7 CONTROL PANEL 13 7 1 Functions of Buttons 13 7 2 LCD Sc...

Page 3: ...nstalled in accordance with national and local requirements gas safety regulations relevant standarts and this manual by gas safe engineer 9 The boiler must be mounted against a closed wall 9 The boiler can not be positioned having direct contact to steam detergent or gases 9 Any change of flue position must not be made without consulting gas safe engineer 9 Sunlight can cause color change on the ...

Page 4: ...t centralheating co uk or installersfirst co uk for more information PRODUCT NAME PRODUCT CODE GC NUMBER PROTEUS PREMIX 14 HM NG ERP UK 8116941010 47 814 30 PROTEUS PREMIX 20 HM NG ERP UK 8116944010 47 814 29 PROTEUS PREMIX 24 HM NG ERP UK 8116450010 47 814 01 PROTEUS PREMIX 28 HM NG ERP UK 8116451010 47 814 02 PROTEUS PREMIX 30 HM NG ERP UK 8116452010 47 814 03 PROTEUS PREMIX 35 HM NG ERP UK 8116...

Page 5: ...tial start up of the boiler Instructions are given below 9 Check Operating Instructions Installation and Maintenance Instructions and follow instructions before installation 9 Carry out installation in compliance with the prevailing legislation and standarts 9 Be sure that the system is flushed and inhibitor added 9 Only gas safe engineer must operate the boiler 9 Explain the user about installati...

Page 6: ... unauthorized service or staff 3 4 Boiler Features Control panel is ergonomic and easy to use The Proteus Premix condensing boiler with elegant plastic control panel and advanced LCD screen provides ease of use and service On a LCD display with black instrument panel you can see the operating state icons heating circuit and operating water adjustment values the fault failure codes and the heating ...

Page 7: ...5 Seasonal Space Heating Energy Efficiency 91 11 91 4 92 2 92 4 92 92 9 Water Heating Energy Efficiency 83 6 83 6 83 6 83 9 82 8 82 8 Sound Power Level db A 49 49 49 49 49 49 Efficiency at Rated Heat Output At High Temperature Regime ƞ4 87 9 87 9 87 9 87 9 87 9 87 9 Efficiency at 30 of rated Output At Low Temperature Regime ƞ1 97 97 97 2 97 4 97 97 9 At Full Load elmax kW 0 028 0 035 0 04 0 051 0 ...

Page 8: ...D Expansion Vessel lt 8 Weight Net kg 28 5 28 5 28 5 30 30 32 Weight Net only for HCH model kg 22 5 22 5 22 5 24 24 26 Dimesions HxWxD mm 678 410 288 Flue Lenghts C13 60 100 Max m 10 10 10 10 10 10 C13 80 125 Max m 20 20 20 20 20 20 C33 60 100 Max m 10 10 10 10 10 10 C33 80 125 Max m 20 20 20 20 20 20 C43 60 100 Max m 10 10 10 10 10 10 C53 60 100 Max m 10 10 10 10 10 10 C83 80 80 Max m 28 28 28 28...

Page 9: ...B 49 Specific precautions for assembly installation and maintanence All specific precautions for installation assembly and maintanence are described in the installation and service manual Proteus Premix Boiler ERP Units HCH 67 MODEL Supplier s name or trademark E C A Proteus Proteus Proteus Proteus Proteus Proteus Supplier s model identifier Premix Premix Premix Premix Premix Premix 14 20 24 28 30...

Page 10: ...ion from fiche of solar device III The value of the mathematical expression 294 11 Prated whereby Prated is related to the preferential space heater IV The value of the mathematical expression 115 11 Prated whereby Prated is related to the preferential space heater 1 If tank rating is above A use 0 95 1 T Class I 1 Class II 2 Class III 1 5 Class IV 2 Class V 3 Class VI 4 Class VII 3 5 Class VIII 5...

Page 11: ...r in this fiche may not correspond to its actual energy efficiency once installed in a building as this efficiency is influenced by further factors such as heat loss in the distribution system and the dimensioning of the products in relation to building size and characteristics Package Fiche Combination Heaters Boilers or Heat Pumps Water heating energy efficiency of combination heater Declared lo...

Page 12: ...e dimensioning of the products in relation to building size and characteristics I The value of the water heating energy efficiency of the combination heater expressed in II The value of the mathematical expression 220 Qref Qnonsol where Qref is taken from Regulation EU 811 2013 Annex VII Table15 and Qnonsol from the product fiche of the solar device for the declared load profile M L XL or XXL of t...

Page 13: ... Comfort mode Once the Reset button is pressed when operating in Comfort mode the boiler will switch to Eco mode Then when Reset button is pressed again the unit will switch to Comfort mode C Domestic Hot Water Increase Temperature Button The temperature of the domestic water can be increased up to 65 C thanks to the domestic water temperature increase button D Central Heating Water Increase Tempe...

Page 14: ...domestic hot water is heating request the tap symbol flashes 1 time sec In this mode the domestic hot water temperature can be adjusted between 30 65 C 7 3 5 Comfort Mode The standard operating mode of the boiler is Comfort mode By pressing the Reset button Eco Comfort modes can be switched When Comfort mode is active Comfort icon is displayed on the LCD screen Comfort mode is only for radiator he...

Page 15: ... is still present or persists after reset notify gas safe engineer 1 Press reset button 2 If the error is still present or persists after reset notify gas safe engineer 1 Check that water valves of boiler installation are open 2 If the combi boiler triggers this error in winter mode check that at least 1 radiator is open 3 Press reset button 4 If the error is still present or persists after reset ...

Page 16: ...when the temperature of the flue gas exceeds 95 o C F07 1 Notify gas safe engineer F13 Repeated Reset Fault Pressing of Reset button more than 5 times in an hour 1 Notify gas safe engineer F25 Electronic Card Fault Electronic Card Firmware Fault 1 Notify gas safe engineer F34 Low Supply voltage It occurs when the supply voltage falls below 170V 1 Notify gas safe engineer 1 Press reset button 2 If ...

Page 17: ...lue gas The flue gas temperature sensor is in short or open circuit state F53 1 Notify gas safe engineer Flue Gas Lock Out at High Temperature If it gives an error F07 twice in 1 month this error will occur F58 1 Notify gas safe engineer F81 Temperature sensor deviation test delay Temperature sensors might be defective 1 Notify gas safe engineer Table 1 Error Code Table 1 Check water pressure in h...

Page 18: ...any third party who undertakes any work carried on the product or fits parts unless approval is given by the means mentioned in point 5 such work in advance of it being carried out 7 The boiler has to be installed at an accessible area where Engineers can perform servicing without health and safety risk 8 Cupboard installations must provide minimum working clearances as detailed in the installatio...

Page 19: ...then be debited from your account i You are required to provide telephone contact numbers to enable us to contact you in the course of arranging and fulfilling your appointment In the course of arranging and fulfilling your appointment we may choose to contact you via phone text fax or e mail Charges xServicing and Commissioning appointments are charged at a fixed price inclusive of VAT with the p...

Page 20: ...gesi 3 Kısım Mustafa Kemal Bulvarı No 13 45030 MANİSA 90 236 213 00 21 SALES TECHNICAL SUPPORT Call Center Tel 44 800 640 9988 Office Tel 44 203 978 1212 FWඈYDWඈQJ RXU TXDUDQWHH ඈV TXඈFN DQG VඈPSOH EXW UHDOO ඈPSRUWDQW 5HJඈVWHU DW www ecaboilers co uk warranty registration complate and return in the envelope provided 45 FRGH VFDQ PH ...