PowerRack HV4 User Manual
19
3.2.4 Battery system self-test
Switch the DC BREAKER of BDU to the "ON" state
Switch on the “POWER ON” switch
3.2.4.2 Press the “POWER WAKE” button for about 3S. The system start-up.
3.2.4.3 Use a multimeter to measure the output voltage on the positive and negative
ports of the BDU. Confirm the voltage is within the normal range
3.2.4.4 The output voltage should conform to the voltage range in the table
“
Table 2-1/2
The parameter of PowerRack HV4 system
”
. Otherwise, the system will be not working
properly.
Danger:
The voltage of the battery is too high, please pay attention to do self-protection
during the measurement.
3.2.5 Shut down the system
Switch off the “POWER ON” switch.
Switch the BDU
“
DC BREAKER
”
to the "OFF" state .
Press and hold on 3s