
Chapter 4: Programming the Rhino2
86
4.4.5.3
ThermalRollbackStart / End
Parameter
Possible Values
Default
HHP
Lite
Std Adv
ThermalRollbackStart
0 – 70°C
70°C
ThermalRollbackEnd
70 – 80°C
80°C
Thermal rollback provides protection for the controller against overheating. The values of
these two parameters set the range for when the thermal rollback starts
(
ThermalRollbackStart
), and ends (
ThermalRollbackEnd
).
When the controller temperature exceeds
ThermalRollbackStart
and is less than the upper
temperature limit
ThermalRollbackEnd
, the controller rolls back the demand, load
compensation and current limit in order to control the temperature rise to protect the
controller against overheating. As the temperature falls back within this range, the control
allows the demand, load compensation and current limit to recover.
4.4.5.4
Motor Reverse
Parameter
Possible Values
Default
HHP
Lite
Std Adv
Motor Reverse
No / Yes
No
Yes
- The polarity of the motor pins on the
R
HINO
2
is reversed and the motor turns in the
opposite direction.
No
- The polarity of the motor pins is as described in section 3.5.
Note:
Do not use
Motor Reverse
to setup the scooter for left-handed use, set the
parameter (see 4.4.1.3) to 'Yes' instead.
Motor Reverse
only
swaps the motor polarity, not other forward/reverse features such as the
Forward/Reverse speed setting and the reversing beeper. Using
Motor Reverse
to
setup the scooter for left-handed use will result in the reversing beeper beeping
while the scooter drives forward.
4.4.5.5
Load Compensation
Parameter
Possible Values
Default
HHP
Lite
Std Adv
Load Compensation
0 - 225 mΩ
DS90:
60mΩ
DS120:
40mΩ
DS160:
28mΩ
Load Compensation
automatically compensates for changes in motor speed when the
scooter drives over loads such as sidewalks, curbs or slopes. Set
Load Compensation
to 'Yes' for
normal operation.
Note:
The
Load Compensation
parameter affects the performance of all other speed
and acceleration parameters, and it is important to set this parameter correctly
before you program these parameters
. If the
Load Compensation
parameter is
changed after the scooter has been set up, the complete speed/acceleration
programming and testing procedure must be repeated.