DMC810GL 

Leading Edge Dimmer/HF Ballast Controller Installation Manual 

 
 
 
 
 
 
 
 
 
 
 
 
 

contents 

 

 

Warning…………………………………………….. 2 

Dimmable Lamps Chart……………………….….. 7 

Features…………………………………………….. 2 

Preset Programming Using The Program Key.… 8 

Important Safeguards……………………………..  2 

Hold Down Programming Of Presets.…………… 9 

Internal View……………………………………….. 3 

One Touch Button Operation…………………….. 9 

Mounting…………………………………….……… 4 

Troubleshooting……………………………………. 10 

Supply & Load Cable Connections.……………… 5 

Specification……………………………………….  10 

Connecting Serial Control Cables……………….. 6 

Useful DyNet Op Codes………………………….  11-12 

Hardware Controls …………………………………7 

 

 

……………………………………………………………………………………………………….... 

Summary of Contents for DMC810GL

Page 1: ...er HF Ballast Controller Installation Manual contents Warning 2 Dimmable Lamps Chart 7 Features 2 Preset Programming Using The Program Key 8 Important Safeguards 2 Hold Down Programming Of Presets 9 Internal View 3 One Touch Button Operation 9 Mounting 4 Troubleshooting 10 Supply Load Cable Connections 5 Specification 10 Connecting Serial Control Cables 6 Useful DyNet Op Codes 11 12 Hardware Contr...

Page 2: ...eck Connections Treat this device as a switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Dimmed and Switched Output Circuits The load on a circuit should no...

Page 3: ...DMC810GL Entry Gland Plate for Load Cables Circuit Breakers and Emergency Lighting line Outputs Dimmed or Switched 230V Outputs 40A Single Phase Supply Connections 4 x Side Entry Gland Knockouts DALI Broadcast 1 10V or DSI Control Outputs Earth Link Accessory Port DyNet Port Network Socket Service Switch Service LED Low Voltage Cable Gland ...

Page 4: ...g the Device The DMC810GL has integral mounting brackets attached to the enclosure The brackets are designed to accommodate 4 fixing screws up to 8mm diameter The DMC810GL can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can ...

Page 5: ...mmon neutral at a remote location Ballast Control Cables Ballast Control cables shall be terminated on the designated terminal block located directly below the Load terminals These terminals are labelled CH9 to CH12 and can operate in tandem with the corresponding Load Outputs or can be programmed to operate independently 1 10V DSI or DALI broadcast control are software configurable Emergency Ligh...

Page 6: ...r used for DATA and DATA Recommended Cable Colour Coding Green White pair Paralleled for GND Orange White pair Paralleled for 12V Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The recommended connecting method is to daisy chai...

Page 7: ...ti function accessory modules for optional features such as additional dry contact inputs 2nd DyNet port and Time clocks Consult your distributor for details on the available accessory modules dimmable lamps chart INCANDESCENT LAMPS Incandescent lamps are easily dimmed using all Dynalite controllers The soft start and voltage limit features will extend lamp life Lamp life can be further extended u...

Page 8: ...equired STEP 4 To set the level of an individual channel press 1 4 The button LED will indicate which channel you have selected When more than 4 channels are to be set press 1 twice for channel 5 press 2 twice to select channel 6 press 1 three times to get channel 9 etc Each press of the button increases the active channel number by 4 STEP 5 Press the up down or off buttons until the lamps on the ...

Page 9: ...enes are now stored and can be recalled by pressing the relevant buttons on this panel or other panels in the same area one touch button operation STEP 1 With a simple button push you can toggle between on and off STEP 2 By holding your finger on the button you can raise and lower the lighting circuit or circuits that are connected to the button To alternate between up and down stop pushing for a ...

Page 10: ...e breaker terminals are tight Fluorescent lights won t dim Wrong type of ballast or ballast incorrectly wired Check ballast type Check actual wiring against ballast manufacturer s diagram Check 1 10V DSI DALI Broadcast settings specification Supply 230V 14 50 60Hz Single Phase at 40A Outputs 4 x 10A dimmed leading edge phase control outputs 4 x 10A switched outputs 4 x HF ballast control outputs s...

Page 11: ...sed by the Set Area Links and Clear Area Links messages Byte 2 Bit 7 is the 1st Area and Bit 0 is 8th Byte 4 Bit 7 is the 9th and Bit 0 is the 16th Byte 5 Bit 7 is the 17th and Bit 0 is the 24th Set Area Links Byte 0 1C Byte 1 Area Byte 2 Data Areas to Link Byte 3 Opcode 20 Byte 4 Data Areas to Link Byte 5 Data Areas to Link Byte 6 Join Byte 7 Checksum Example Link Areas 4 5 assumes Base Area 3 1C...

Page 12: ... Byte 1 AREA Byte 2 Unused usually 0 Byte 3 7A hex Byte 4 Unused usually 0 Byte 5 Unused usually 0 Byte 6 Join usually FF hex Byte 7 Checksum Example Halt the Fade in Area 4 at the current level 1C 04 00 7A 00 00 FF 67 Toggle Channel State Preset Off or Off Preset Byte 0 1C hex Byte 1 AREA Byte 2 CHANNEL NUMBER 0 origin Byte 3 70 hex Byte 4 UNUSED usually 0 Byte 5 UNUSED usually 0 Byte 6 TBAR usua...