4.4.6.3 Output on High Example
In this example, a sensor is monitoring the temperature of an engine. If the temperature rises above 325°F, a fan will turn on to
cool the engine. Once the temperature drops to below 200°F the fan will turn off.
Relevant Settings (Auxiliary Sensor)
Setting
Value
Signal Source
Same as Engine Temperature
Display
Disable (If enabled, controller will display Engine Temperature twice)
Sensor Type
Same as Engine Temperature
Sender Table Name
Engine Temp.
Active Range
Global
Mode Select
Output on High
Mode Settings -> Active Time
1
Disabled
Mode Settings -> Start Level
325°F
Mode Settings -> Stop Level
200°F
1
Active time is disabled because the fan needs to stay on indefinitely or until 200°F is reached.
Relevant Settings (Switched Outputs)
Setting
Value
Switched Output X
Auxiliary Sensor X (Choose based on which Auxiliary Sensor is being used)
The chart above shows the connection between engine temperature and time. At approximately 10 minutes run time, the
temperature rises above the 325°F start threshold and the fan turns on. The fan continues to run as the temperature declines.
When the temperature falls below the 200°F stop threshold, the fan turns off.
Summary of Contents for Tough Series
Page 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Page 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...