Dwyer Instruments 604D-0 Specifications-Installation And Operating Instructions Download Page 1

Series 604D Indicating Pressure Transmitter

Specifications - Installation and Operating Instructions

Bulletin E-34

DWYER INSTRUMENTS, INC. 

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. 

Fax: 219/872-9057

e-mail: [email protected]

Lit-By Fax: 888/891-4963 

The Dwyer Series 604D Indicating Transmitter 

simulta-

neously provides local indication on a compact, easy to
read analog scale while also converting that pressure into a
standard 2, 3 or 4 wire, 4-20 mA signal for ranges as low
as 0-0.5 in. w.c. Positive, negative or differential pressures
can be measured within ±5% of full scale (gage reading) or
±2% of full span output (transmitter signal). The basic
mechanical components of the Series 604D units are simi-
lar to those used in the popular, time-proven Minihelic

®

dif-

ferential pressure gage. However, the Series 604D models
add electrical conditioning and amplification of a resistance
change produced by a silicon strain gage cemented to the
range spring. This resistance change is the result of a slight
flexing which results from spring deflection as pressure is
applied to the diaphragm which is mechanically linked to
the spring.

PHYSICAL DATA
GENERAL
Maximum Pressure:

30 psig (207 kPa) continuous

50 psig (344 kPa) momentary surge.

Media Compatibility: 

Air and non-combustible, non-cor-

rosive gases. 

Materials:

Mineral and glass filled nylon housing, high

impact acrylic cover, silicone rubber diaphragm.

ELECTRICAL
Power Supply: 

10-35 VDC-2,3 or 4 wire

16-26 VAC-4 wire.

Connections:

4 screw terminal block

Cable Gland:

Fits .10 - .25 in (2.5 - 6 mm) O.D. cable.

Output Signal:

4-20 mA DC (limited at 38 mA DC).

Loop Resistance:

DC; 0-1300 ohms

AC; 0-1200 ohms.

Current Consumption:

DC; 38 mA max. AC; 76 mA

max.

Warm-Up:

10 minutes.

PERFORMANCE AT 70°F (21.1°C)
Zero Output:

4 mA DC. 

Full Span Output:

20 mA DC.

Accuracy, Gage:

±5% of full scale.

Accuracy, Transmitter:

±2% of full span output

(Includes linearity, hysteresis and repeatability).

Stability:

1% F.S./year.

ENVIRONMENTAL
Operating Temperature:

20-120°F (-6.7° to 49°C)

Thermal Errors: 

±1%/50°F

MECHANICAL
Weight:

8 oz. (227 grams)

Span and Zero:

Internally accessible potentiometers

Pressure Connections:

Barbed, for 3/16

(4-5 mm) I.D.

tubing.

STANDARD ACCESSORIES

(2) #10 x 1

″ 

pan head sheet metal screws, (1) .050

hex

allen wrench.

Model

Number

604D-0
604D-1
604D-2
604D-3
604D-5
604D-10
604D-20
604D-40
604D-60
604D-100

Ranges, Inches W.C. 

0-0.5 
0-1.0 
0-2.0 
0-3.0 
0-5.0 

0-10 
0-20 
0-40 
0-60 

0-100 

Minor Divisions

.02
.05
.10
.10
.20
.50
1.0
2.0
2.0
5.0

Series 604D Indicating Transmitter Model & Ranges