Dux RBP1-ABS Installation Instructions Download Page 1

1

RBP1 - ’ABS’ Recess Box V1 - 11-007 8/6/11

RBP1

 - ‘

ABS’ Recess Box - 

Installation Instructions

To suit the following Dux Endurance Continuous 

Flow water heater models:

ENDURANCE 16 - DEU-VR1620WG
ENDURANCE 20

 

- DEU-VR2020WG

ENDURANCE 26 - DEU-VR2626WG   

PLEASE NOTE:  Does not  suit the ENDURANCE 32  

RBP1 - ‘ABS’ RECESS BOX COMPONENTS 

The Dux RBP1 - ‘ABS’ Recess Box contains two components Cover and an Insert.

GENERAL PREPERATION

1. Prepare an opening in the wall approximately 1 metre above the ground. The

opening requirements are Height 1030mm, Width 390mm and a minimum Depth
of 160mm (see dimension diagrams page 2). Ensure the location complies with
the requirements of AS/NZS 5601 Fig. 6.2. 

2. Remove the transport tab 

 from the pipe entry point of the insert.

3. Determine the appropriate electrical access point and remove either the left or

right the knock out plug 

 located near the bottom of the side walls of the insert. 

SECURING OPTIONS

The RBP1 - ’ABS’ insert is designed to be surface mounted and may be secured using one of the following methods:

ASSEMBLY AND APPLIANCE INSTALLATION

4. The gas, cold water inlet and hot water outlet pipes can be brought through the pipe entry point at the base of the insert.

The pipe entry point is elevated to prevent water ingress. This can be sealed if required.

 

Securing the RBP1 - ‘ABS’ Insert externally

Secure to the wall surface via the 8 screw holes provided in the flange of
the insert using suitable fasteners.

Securing the RBP1 - ‘ABS’ Insert internally, through the side wall

Secure the insert into a solid fixture such as brickwork, timber studs etc,
through the side walls using suitable fasteners.

The excess space between the side walls of the insert and the
solid fixture may require packing to prevent distortion of the
insert.

At least two fasteners should be used through each side wall
approximately 125 mm from the inside top and bottom horizontal faces of
the insert

Securing the RBP1 - ‘ABS’ Insert internally, through the rear wall

Install two noggins 

 between wall studs 

, these are to be centred at

130 mm from the top and bottom of the opening. Secure the insert into the
noggins 

 through the rear wall using suitable fasteners.

Securing the RBP1 - ‘ABS’ Insert with the use of a brick tie

Secure a brick tie to the side walls of the insert with pop-rivets or screws. 
As the brickwork is being laid use the attached brick ties to secure the
insert into the brick courses. Use two brick ties per side, one near the top
and bottom of the insert.

Installing the RBP1 - ‘ABS’ to rendered surfaces

Use spacers 

 (not provided) to install the RBP1 - ’ABS’ insert, with

sufficient clearance for rendering. 

 

When the render is applied ensure that the gap provided by
the stand-off spacers is NOT exceeded as this will prevent the
RBP1 - ‘ABS’ cover from being fitted!

THE RBP1 - ‘ABS’ COVER AND INSERT ARE CONSTRUCTED FROM DURABLE ABS PLASTIC. 
NEVERTHELESS, TAKE CARE WHEN WELDING ANY PLUMBING CONNECTIONS TO ENSURE NO RBP1 
- ’ABS’ PARTS ARE SUBJECTED TO A NAKED FLAME OR EXCESSIVE HEAT.

THE RBP1 - ‘ABS’ IS NOT SUITABLE FOR INSTALLATION INTO WALLS WHICH ARE REQUIRED TO BE 
‘FIRE RESISTING’ AS DEFINED IN THE BUILDING CODE OF AUSTRALIA (BCA) UNLESS ALTERNATIVE 
PROVISIONS ARE MADE TO ACHIEVE THE REQUIRED FIRE RESISTANCE LEVEL (FRL). REFER TO THE 
BCA FOR MORE INFORMATION.