![DURAG D-R 290 Operating Manual Download Page 92](http://html.mh-extra.com/html/durag/d-r-290/d-r-290_operating-manual_2541137092.webp)
5 | Installation
92
D-R 290
Configuring the protective device
After installation of all the components of the protective device (shutter, control elec
tronics, air flow sensor) the D-R 290 measuring head configuration must be parame
terised for the protective device (the presence of the air flow sensor and fail-safe shut
ter(s)).
Setting path:
> Specific parameters > D-R 290 configuration > Purge air sensor 1 present and
> Specific parameters > D-R 290 configuration > fail-safe shutter 1 present
or
> Specific parameters > D-R 290 configuration > Purge air sensor 2 present and
> Specific parameters > D-R 290 configuration > fail-safe shutter 2 present
The fail-safe shutter is closed during installation and parameterisation. It opens once
the air flow sensor has detected the presence of the purge air.
WARNING
High risk of injury due to sudden closure of the shutter
▶
Never insert fingers into the closing area of the fail-safe shutter.
▶
Before maintenance work:
Unplug the connection plug at the measuring head for the fail-safe shutter.
(Caution,
when the connection is broken, the fail-safe shutter closes very quickly)
Checking the protective device
When the mains power is switched on (check the charge status of the
; see below) and the purge air is present, the fail-safe shutter automatically
switches to the “
OPEN“ position.
If the power supply or the purge air fails, the fail-safe shutter of the protective device
switches to the “
CLOSED“ position. In this case the D‑SK AE control electronics pro
vides the necessary power via the maintenance-free supercaps. After the failure has
been rectified the fail-safe shutter automatically switches back to the “
OPEN“ position.
The status feedback message
"Shutter OPEN“ is set at terminals 7 and 8 (connection
closed) in the control electronics.
The charge status of the supercaps is indicated by the green
“Battery check LED“ on
the front panel. When the supercaps are charged the LED lights up.
The LEDs indicate only the activation, but not the shutter position. The feedback
message for the shutter position is given via the cam switch in the rotary drive.
5.5.5
5.5.6
Summary of Contents for D-R 290
Page 12: ...12 D R 290 ...
Page 18: ...1 General 18 D R 290 ...
Page 20: ...20 D R 290 ...
Page 28: ...2 Safety 28 D R 290 ...
Page 30: ...30 D R 290 ...
Page 38: ...3 Delivery 38 D R 290 ...
Page 40: ...40 D R 290 ...
Page 60: ...4 Product description 60 D R 290 ...
Page 106: ...106 D R 290 ...
Page 152: ...152 D R 290 ...
Page 174: ...8 Maintenance 174 D R 290 ...
Page 176: ...176 D R 290 ...
Page 178: ...9 Appendix 178 D R 290 Fig 9 2 Measurement point questionnaire 2 ...
Page 194: ...9 Appendix 194 D R 290 ...
Page 200: ...11 Index 200 D R 290 ...
Page 202: ...GmbH Kollaustraße 105 22453 Hamburg Germany www durag com ...