Modbus
D
−
LX 200, D
−
LX 720
87
Modbus FunctionCode(0x10)
Write
Multiple 16BitRegisters
(for details see Modbus Specification)
Request
Slave Address
1 byte
0, 1..254
FunctionCode
1 byte
0x10
Starting Address
2 bytes
0x0000 to 0xFFFF
Quantity of…
…Registers
2 bytes
0x0001 to 0x007D
Byte count of…
…Registers
1 byte
2 x
N
*
Register Value
N
* x 2 bytes
Value
CRC
2 bytes
SA, FC
DATA
*
N
= Quantity of Registers
Table 8.8: Modbus FunctionCode(0x10) Write Multiple 16BitRegisters Request
Response
Slave Address
1 byte
0, 1..254
FunctionCode
1 byte
0x10
Starting Address
2 bytes
0x0000 to 0xFFFF
Quantity of…
…Registers
2 bytes
1 to 123 (0x7B)
CRC
2 bytes
SA, FC
DATA
*
N
= Quantity of Registers
Table 8.9: Modbus FunctionCode(0x10) Write Multiple 16BitRegisters Response