Adjusting the Flame Monitor
64
D
−
LX 200, D
−
LX 720
Range B are used, the settings for each range must be made
separately!
Please also note the information for the Range selection from page 59.
6.6 Safety
time
The safety time is the response time of the flame monitor to an outage of the
flame signal (digital signal from the (
) flame radiation and the resulting
switch-off of the relay contact for the Flame ON signal).
The Compact Flame Monitor D
−
LX 200, D
−
LX 720 has a default safety time of
1 second. Further default values (2 s, 3 s and 5 s) are available on request.
The safety time noted on the type plate must match the safety time set on the
device.
Burner controls and flame monitors are type-approved devices.
Any
interventions or modifications will result in loss of the approval.
Repairs may
therefore only be carried out by the manufacturer or his representatives.
The adjustment of flame monitors should also only be performed by
appropriately trained personnel, in the interest of safety.
DURAG offers suitable training for this purpose.
Particular care must be taken not to change switch positions 1 and 2 (see
Figure 6.6 and Table 6.1 on page 58) when setting the gain characteristic
curves at DIP switches S3 and S4. The switch position corresponding to the
safety time noted on the type plate can be verified in Table 6.2.
Summary of Contents for D-LX 200
Page 1: ...D LX 200 D LX 720 Compact Flame Monitor GmbH Kollaustra e 105 22453 Hamburg www durag de...
Page 8: ......
Page 10: ......
Page 14: ......
Page 16: ......
Page 22: ......
Page 24: ......
Page 32: ......
Page 42: ......
Page 52: ......
Page 66: ......
Page 68: ......
Page 80: ......
Page 82: ......
Page 92: ......
Page 94: ......
Page 100: ......
Page 106: ......
Page 108: ...Declaration of conformity 108 D LX 200 D LX 720...
Page 114: ......
Page 116: ...GmbH Kollaustra e 105 22453 Hamburg www durag de...