1 of 3
October 15, 2015
RMF
‐
4012
AC
to
DC
Power
Supply
Owners
Guide
(These instructions are intended for use by a technician familiar with electronic products)
Auto
range
voltage
input
85
to
264
VAC,
47
to
63
Hz
or
120
to
370
VDC
Available
in
12,
24,
48
VDC
output
(adjustable)
Built
‐
in
TTL
remote
control
/
remote
sense
DC
‐
OK
TTL
signal
Short
circuit
/
over
load
/
over
voltage
/
over
temperature
protections
3
year
warranty
DESCRIPTION
The RMF-4012 has an auto range voltage input of 85 to 264 VAC, with 47 to 63 Hz or 120 to 370 VDC. This unit comes with
three available outputs that are adjustable; these outputs are available in 12, 24, and 48 VDC. All RMF devices have a built-in TTL
remote control and remote sense along with a DC-OK TTL signal, along with short circuit, over load, over voltage, over temperature
protections, and hold UL, CE, TUV, CUL approvals. To guarantee DuraComm’s durability DuraComm offers a 3 year warranty for all of
their RMF series products.
SPECIFICATIONS
Output Voltage ....................................................................................................................................................................... 13.8 VDC
Output Adjustment Range ............................................................................................................................................. 11 to 14.5 VDC
Output Voltage Tolerance ........................................................................................................................................................ +/- 1 pct
Output amperage, max continuous ......................................................................................................................................... 45 Amps
Maximum Power, continuous ................................................................................................................................................ 600 Watts
Maximum ripple and noise .......................................................................................................................................... 120 mV p-p max
Input voltage range (auto-ranging) ..................................................................................................................................... 85-264 VAC
Input frequency range ............................................................................................................................................................. 47-63 Hz
Maximum AC current ................................................................................................................. 8.5 Amps/115 VAC; 5 Amps/230 VAC
Typical Efficiency .......................................................................................................................................................................... 88 %
Max inrush current, single cycle ...................................................................................... 35 Amps @ 115 VAC, 70 Amps @ 230 VAC
Overload Protection (operates) ............................................. typical 85 to 115 %, Constant Current Limiting, Recovers Automatically
Line Regulation ............................................................................................................................................................................ 0.3 %
Load Regulation ........................................................................................................................................................................... 0.5 %
Fan Control ........................................................................................................................ LOAD 35+/-15% or RTH2>/=50 C, Fan On
Over Temperature ....................... +80 C Power Transistor or +100 C Output Choke, Shutdown Output Voltage, Automatic Recovery
Rise Time following ON (Full Load) ............................................................................................................................................. 50 mS
Hold Time following OFF (Full Load) ............................................................................................................................................ 16mS
Working Temperature range ................................................................................................................... -40 to 158 F (-40 C to +70 C)
Storage Temperature .............................................................................................................................. -40 C to 185 F (-40 to +85 C)
Withstand Voltage ...................................................................................................................................... 3 KVAC @ 10 ma (I/P-O/P)
(Continued) ................................................................................................................................... 2 KVAC @ 10 ma (I/P-F/G)
(Continued) .................................................................................................................................. 500 VAC @ 10 ma (O/P-FG)
Dimensions ................................................................................................................................. 3.5H x 19W x 5.25D inches, nominal
Weight ............................................................................................................................................................................. 7 lbs, nominal
INSTALLATION WARNING