Dungs FRM 100025 Instruction Manual Download Page 1

MF …68

Edition 02.22 • No

. 270 442

1 … 68

The target group of this manual is qualified personnel of the 

gas safety and regulating technology. Due to their specialist 

training, knowledge and experience, they should be capable 

of evaluating the work assigned to them and recognising 

possible dangers. Only they are permitted to carry out as

-

sembly, commissioning, settings and maintenance on the 

devices in compliance with the recognised rules for occupa

-

tional safety.

Instruction Manual

FRM 100025 - 100050

2. Warnings                         

Never carry out work as long as gas 

pressure or voltage is applied. Avoid 

open fire. Please observe public regula-

tions. 

The device must be protected from vi-

brations and mechanical impacts.

All adjustments and settings should only 

be performed in accordance with the 

instruction manuals of the connected 

machines. 

The recognised occupational safety 

rules and accident prevention regula-

tions must be observed and, if neces-

sary, personal protective measures must 

be taken.

Connected line systems must be free 

from dirt and contamination.

Hang this instruction manual in a readily visible place 

inside the installation room! Do not carry out any work 

until you have read the safety instructions of this in-

struction manual and are qualified to do so.

The device may only be operated in 

compliance with the operating condi-

tions stated on the type plate.

Prior to assembly, the device must be 

inspected for transport damage.

The device must not be used in areas 

with increased seismic risk.

Protection from environmental impacts 

and weather conditions (corrosion, rain, 

snow, icing, humidity (e.g. by conden-

sation), mould, UV radiation, harmful 

insects, poisonous, corrosive solutions/

liquids (e.g. cutting and cooling fluids

), 

must be guaranteed. Depending on the 

installation site, it may be necessary to 

take protective measures.

The device must not be exposed to open 

fire. Protection against lightning strikes 

must be guaranteed.

2.1 General warnings                         

1. Target group 

 

 

 

 

                    

Explanation of the symbols

1, 2, 3,...    =  

Order of 

  action

•        =  

Instruction

Summary of Contents for FRM 100025

Page 1: ...served and if neces sary personal protective measures must be taken Connected line systems must be free from dirt and contamination Hang this instruction manual in a readily visible place inside the installation room Do not carry out any work until you have read the safety instructions of this in struction manual and are qualified to do so The device may only be operated in compliance with the ope...

Page 2: ... of misuse If used in accordance with their designated use the devices are safe to operate Non observance of the regulations may result in per sonal injury or material damage financial damage or environmental damage 3 Approval EU declaration of conformity Operator errors or misuse present risks to life and limb of the operators and also to the device and other mate rial property commercial grade n...

Page 3: ...e sur les dispositifs sous pression sont des éléments d équipement à fonction de sécurité Ce communiqué n est plus valable si nous effectuons une modification libre de l appareil L objet décrit ci dessus de la pré sente déclaration correspond aux prescriptions légales applicables en matière d harmonisation de l Union Le fabricant porte l entière res ponsabilité pour l établissement de la présente ...

Page 4: ...pring exchange Wdsu 28 12 Commissioning decommissioning and recommissioning FRM or SAV 30 12 1 General information 30 12 2 Initial Pressurization of FRM 30 12 3 Leakage test 30 12 4 SAV Resetting and Setting of SAV FRM 31 12 5 Recommissioning 33 12 6 Decommissioning 33 13 Faults and their causes 33 14 Maintenance 35 14 1 General information 35 14 2 Maintenance instructions of the regulator 37 14 2...

Page 5: ...loses MOP Maximum admissible operating pressure pd Outlet pressure pd abs Output pressure as absolute pressure pu Inlet pressure pu abs Inlet pressure as absolute pressure pdo Overpressure shut off OPSO pdu Underpressure shut off UPSO pmax Maximum operating pressure PN Nominal pressure rating of the flange PS Maximum admissible pressure SAV Safety shutoff valve Slam shut valve same as ASE but with...

Page 6: ...pressure for ND versions 200 mbar 20 kPa 80 W C 2 9 PSI Minimum inlet pressure for MD version 300 mbar 30 kPa 120 W C 4 3 PSI Minimum inlet pressure for HD versions 750 mbar 75 kPa 301 W C 10 9 PSI Minimum inlet pressure for UHD versions 1 500 mbar 150 kPa 600 W C 21 PSI Materials Main body housing cast iron GJS 400 15 GJS 400 18 LT ductible iron on request Diaphragm housing steel Diaphragms NBR A...

Page 7: ... 250 25 000 mbar 250 kPa 2 500 W C 360 PSI Nominal diameter 025 DN 25 1 040 DN 40 11 2 050 DN 50 2 Pressure range outlet pressure ND Low pressure MD Medium pressure HD High pressure UHD Ultra high pressure Safety device SAV Integrated safety shutoff valve Pressure range trip pressure ND Low pressure MD Medium pressure HD High pressure UHD Ultra high pressure Flange type ANSI with standard PN 25 wi...

Page 8: ... FRM 100040 ND SAV ND DN 40 ND AC 10 SG 20 30 100 mbar 12 40 W C 10 115 mbar 4 46 W C AG 10 40 240 mbar 16 96 W C AG 10 FRM 100040 MD SAV MD DN 40 MD AC 5 10 SG 10 20 90 420 mbar 36 168 W C 35 400 mbar 14 160 W C AG 10 180 800 mbar 72 321 W C AG 10 FRM 100040 HD SAV HD DN 40 HD AC 5 SG 10 400 1 500 mbar 160 602 W C 150 1 400 mbar 60 562 W C AG 5 500 3 500 mbar 200 1406 W C AG 5 FRM 250040 UHD SAV ...

Page 9: ...alues control quality and lock up pressure class that can be guaranteed at a volume flow of 1 10 were deter Abbrevia tion Description AC Accuracy class pd Outlet pressure pu1 2 Inlet pressure pds Set nominal value of the outlet pressure SG Lock up pressure class Qmin pu1 2 AC minimum flow volume at a specific inlet pressure pu lower limit of the volume flow at which the stable operating conditions...

Page 10: ... W C Blue 270347 8 0 300 65 80 100 mbar 32 40 W C 240 330 mbar 96 132 W C Black 270348 9 0 300 68 330 420 mbar 132 168 W C 400 580 mbar 160 233 W C Purple 270349 10 0 300 69 560 850 mbar 225 341 W C Orange 270350 11 0 300 71 800 1 200 mbar 321 482 W C 1 000 1 600 mbar 402 652 W C Pink 270352 12 0 300 73 1 100 1 500 mbar 442 602 W C White 271113 13 0 300 75 1 500 2 500 mbar 603 1 004 W C Red 271132...

Page 11: ...5 0 1 200 3 000 mbar 482 1 205 W C 6 6 Selection of SAV springs Specific adjustment range overpressure Wdso Spring colour Order number Wire mm Length mm mm Setpoint range ND MD HD UHD Silver 270361 2 2 60 30 0 40 130 mbar 16 52 W C Green 270366 2 5 60 30 0 60 190 mbar 24 76 W C 180 290 mbar 72 116 W C Red 270367 2 7 60 30 0 90 240 mbar 36 98 W C 230 370 mbar 92 148 W C Yellow 270368 3 2 60 30 0 30...

Page 12: ...e is damaged or in the event of a breakdown of the impulse line pressure the SAV closes pd Outlet pressure pu Inlet pressure PN Nominal pressure of the flange PS Maximum admissible pressure SAV Safety shutoff valve slam shut valve ASE without housing SG Lock up pressure class 20T60 Operating temperature 20 C 60 C 4 F to 140 F SN Serial number Wds Specific guide range Wdo Adjustment range for the o...

Page 13: ...ol ume decreased in this way reduces the outlet pressure until the set nominal value outlet pressure is reached again and a balance of forces at the working diaphragm F is established If the outlet pressure drops the force on the working diaphragm F in the lower diaphragm shell C decreases also The working diaphragm F is thus pushed down wards until the force of the setpoint spring H is equal to t...

Page 14: ...1 000 145 40 380 223 69 505 830 1 2 G 12 36 79 4 lbs FRM 100040 HD 270280 10 1 000 145 40 380 223 69 515 840 1 2 G 12 40 88 2 lbs FRM 250040 UHD 271118 25 2 500 360 40 380 223 69 515 840 1 2 G 12 40 88 2 lbs FRM 100050 ND 270284 10 1 000 145 50 500 254 80 515 840 1 2 G 12 49 108 lbs FRM 100050 MD 270285 10 1 000 145 50 380 254 80 515 840 1 2 G 12 43 94 8 lbs FRM 100050 HD 270286 10 1 000 145 50 38...

Page 15: ...83 10 1 000 145 40 380 223 247 515 1 090 1 2 G 12 42 92 6 lbs FRM 250040 UHD SAV UHD 271119 25 2 500 360 40 380 223 247 515 1 090 1 2 G 12 42 92 6 lbs FRM 100050 ND SAV ND 270287 10 1 000 145 50 500 254 252 515 1 090 1 2 G 12 51 112 0 lbs FRM 100050 MD SAV MD 270288 10 1 000 145 50 380 254 248 515 1 090 1 2 G 12 45 99 2 lbs FRM 100050 HD SAV HD 270289 10 1 000 145 50 380 254 256 525 1 100 1 2 G 12...

Page 16: ...itable bonding straps Prevent contact voltage and ignitable flashover The performance data on the type plate corresponds to the purchase ordering data Flanges on the inlet side and outlet side of the connect ing lines are parallel with the FRM flanges The sealing surfaces of the flange are undamaged and clean The maximum inlet pressure of the system is lower than the maximum admissible pressure of...

Page 17: ...egrated SAV 6 Stabilisation section 7 SBV 8 Ball valve 9 Pressure gauge outlet side 10 Test burner 11 Venting ball valve 12 Impulse line SAV 13 Impulse line regulator 14 Shutoff valve outlet side e g ball valve or butterfly valve 15 Vent line regulator 16 Vent line SAV 17 Relief line for SBV section is clean and free from burrs Distance 5 x DN Maximum flow velocity in the stablisation section 30 m...

Page 18: ...ief valve vent Do not manifold the SAV vent with a relief valve vent Do not manifold other vents of similar devices regula tor to regulator relief valve to relief valve etc unless permitted by and manifolded in accordance with the applicable installation code Requirements for Vent Line Length and Size for FRM and SAV vents The diameter of vent line shall be the same size at the vent connection The...

Page 19: ...on the roof does not cover or isolate the termination point from the atmosphere To limit the consequences of rain or debris getting into the vent always turn the outlet of the vent down towards the ground Bug Screens Some bugs are attracted to the smell of the natural LP gas odorant and could nest in the vent line which could seal the termination point Install a bug screen on the termination point...

Page 20: ...lled The SAV is designed to shut down the gas supply in the event of a fault condition The SAV complies with the requirements of EN 14382 as safety shutoff valve Main components A Valve disc B Closing spring C Ball catch trigger mechanism D Chamber with the pressure to be monitored E Working diaphragm F Push rod G Setpoint spring for pdo H Setpoint spring for pdu I Protective cap Function Chamber ...

Page 21: ...housing using a hook wrench 60 90 mm 3 Remove the O Ring B 4 Place the new O Ring B of the maintenance kit 6 on the ASE C 5 Screw the ASE C in the housing using a hook wrench 60 90 mm 6 Align the ermeto swagelok screw connection D of the pulse connection to the connection of the external pulse line 7 Tighten four hexagonal socket grub screws M 5x8 in the ASE C using an internal hex key SW 2 5 2 5 ...

Page 22: ...he protective cap A 2 Turn the adjusting screw B using an open ended wrench SW 24 mm 3 Turning clockwise the preload of the setpoint spring is increased and the outlet pressure pds is increased 4 Turning counter clockwise the setpoint spring is re leased and the outlet pressure pds reduced 5 After the setting screw on the protective cap A again C A B D E F ...

Page 23: ...nder pressure setpoint first If an adjustment to the under pressure setpoint is ever made the upper over pressure setting might need to be re adjusted A mutual influence of the pressure regulator and the safety shutoff valve must be excluded Calculation of the recommended set values according to the outlet pressure pd of the regulator The SAV must lock as soon as it reaches the 1 1 times max opera...

Page 24: ...ressure SAV AGo 10 Response pressure group of the lower under shut down pressure SAV AGu 10 Response group of the SBV AG 5 Result Device group Device data Pressure graduation Safety devices against excessive pressure Gas pressure regulator Safety device against insufficient pressure AGo 10 SAV AGo 10 AG 5 SBV AG 5 440 mbar 176 W C 400 mbar 160 W C 360 mbar 144 W C 315 mbar 126 W C 300 mbar 120 W C...

Page 25: ...or springs Unscrew the sealing cap C from the spring dome F using a hinged hook wrench 90 155 mm B Remove the protective cap A A 2 F C 3 4 Release the setpoint spring E unscrew the adjusting screw B counter clockwise until it stops Remove the sealing cap C C 1 ...

Page 26: ...red spring preload is reached Reinsert the protective cap A 10 Stick on the type plate the label corresponding to new spring range Take label included on the spring kit and cut the range corresponding to the same type as the type plate on the regulator ND MD HD UHD Example label for spring kit 270345 Never have your head above or near the aluminium cap when removing regulator spring The spring ten...

Page 27: ...o 270 442 27 68 11 5 Replacement of SAV springs 11 5 1 Spring replacement Wdso 1 Unscrew the adjusting spring B from the spring dome G using a tube socket wrench SW 22 mm B Remove the protective cap A A 2 B D G 2 1 G ...

Page 28: ...Install the new spring 3 Tighten the adjust ing screw B and the washer D in the spring dome G using an open ended wrench until the required spring preload is reached 4 E 11 5 2 Spring replacement Wdsu 1 Remove the adjusting screw C from the inter nal black spring dome H using an open ended wrench SW 17 mm 2 C H ...

Page 29: ... until the desired spring preload is reached H F 4 Screw on the protective cap A again A 5 Stick on the type plate the label corresponding to new spring range Take label included on the spring kit and cut the range corresponding to the same type as the type plate on the regulator ND MD HD UHD Example label for spring kit 270183 ND Wdso 0 09 0 24 bar 9 24 kPa MD Wdso 0 23 0 37 bar 23 37 kPa ...

Page 30: ...setting or block the line upstream of the SBV and test at 1 1 x system specific operating pressure maximum PS of the device 7 Observe the waiting time necessary for the pressure com pensation pressure equilibrium according to the system specific volumes A minimum of one minute is required to reach pressure equilibrium External leakage test 8 Use a suitable leak detection spray on the device 9 Moni...

Page 31: ...d and screw it again on the spring dome G 4 0 Venting the test section to atmosphere 4 1 If venting fuel gas to test the setting of the FRM or SAV use a manual valve connected to a suitable hose to release the fuel gas to a safe location Or if a relief valve is installed it might be possible to use it to vent some or all of the fuel gas for proper testing Do not use a test burner for venting and s...

Page 32: ...he outlet side Stop applying pressure immediately after the SAV has tripped 6 7 Once the SAV trips read the upper over response pressure on the pressure gauge on the outlet side 6 8 If necessary correct the SAV set points according to the specifications in section 11 2 SAV setting and check it again 7 0 Check of the lower under response pressure pdu setting 7 1 Release the pressure in the test sec...

Page 33: ...de the outlet pressure Replace the SAV The SAV cannot be acti vated The impulse line is not installed Connect install the pulse line The impulse line is clogged Clean the impulse line The impulse line is leaky Seal the impulse line The impulse line is broken Replace the impulse line The impulse pressure is outside the adjustment range Set the shut down pressure of the SAV The adjusting springs are...

Page 34: ...During operation the outlet pressure corresponds to the inlet pressure The pulse impulse is not installed Close the impulse line The pulse impulse is blocked Check the impulse line The pulse impulse is leaky Seal the impulse line The working diaphragm is damaged Replace the working diaphragm The admission pressure compensation diaphragm is damaged Replace the admission pressure compensation diaphr...

Page 35: ...not use alcohol based or solvent containing cleaning solutions for cleaning the rubber parts Greases adhesives sealing material must be ap proved Prior to maintenance Shut off valves both on the inlet and outlet side are closed Lines are unstressed and free from combustible gas Prevent explosive gas air mixture the room atmosphere must constantly be monitored through gas concentration measuring de...

Page 36: ...36 68 Edition 02 22 No 270 442 X Y R Q T S U V W H M C A B D E G F J I K L N O P ...

Page 37: ... 17 mm 2 14 2 2 Replacement of the working diaphragm 4 Unscrew the sealing cap C from the spring dome using a jointed hook wrench 90 155 mm 5 Remove the spring washer D incl ball and the setpoint spring E 1 Loosen the impulse line and the vent line and remove them 2 Remove the protective cap A 3 Completely release the setpoint spring at the adjusting screw B using an open ended wrench SW 24 mm 1 G...

Page 38: ...2 No 270 442 3 Remove the upper diaphragm shell F Remove the O Ring H HD version only Remove the reducing washer I HD version only F H I Remove the upper diaphragm shell F FRM MD HD UHD FRM ND FRM HD UHD FRM HD UHD 5 4 F ...

Page 39: ...39 68 Loosen the nut J M 8 using an open ended wrench SW 13 mm Remove the spring washer K J K 6 FRM MD HD UHD FRM ND FRM MD HD UHD FRM ND 7 Loosen the nut J M 8 using an open ended wrench SW 13 mm Remove the spring washer K J K ...

Page 40: ... of damage or wear If neces sary reassemble a new working diaphragm M maintenance kit 2 L M FRM MD HD UHD FRM ND FRM MD HD UHD FRM ND 8 9 Remove the safety spring L Remove the working diaphram M from the guide rod N and check for signs of damage or wear If neces sary reassemble a new working diaphragm M maintenance kit 2 M L N N ...

Page 41: ...ement of the control plate valve seat 1 4 Loosen the screws Y 2 Remove the lower diaphragm shell O from the housing X To do this the diaphragm shell O has to be turned carefully 3 Remove the O Ring Q from the lower diaphragm shell O 4 O Q Q Y O X ...

Page 42: ...the inside of the regulator housing X Remove the assembly of the control plate S incl the sleeve U from the housing X Remove the control plate S from the control plate sleeve U and check it for damage If necessary replace the control plate S incl the sleeve U Check the valve seat V for dirt or damage ...

Page 43: ...lve seat V from the housing X by using a socket wrench Tighten the new valve seat V with the new O Ring W maintenance set 4 in the housing X Place the new O Ring T maintenance kit 3 or 5 in the turned groove in the housing X Insert the control plate S with the sleeve U mainte nance set 3 in the housing X again ...

Page 44: ...hell O by turning it cautiously Attention Risk of crushing 16 P V Attention Risk of crushing Place fingers at the marked positions ê Fingers may be squeezed between the diaphragm disc P and the diaphragm shell O Do not slide fingers under the diaphragm disc Q O O 14 O P R Make sure that the connection pin R 45 is oriented opposite to the direction of the flow non aligned Insert the new O Ring Q ma...

Page 45: ...22 No 270 442 45 68 R Z P When the connection pin R is locked in the lever sys tem Z both middle lever arms are pushed upwards To do this push the lower diaphragm disc P downwards Attention Risk of crushing P Z R ...

Page 46: ...F Re fit the diaphram cover using the 20 off G M10 screws with an open ended spanner SW 16 mm Insert the setpoint spring E in the spring dome F In sert the spring washer D incl ball on the spring Tighten the sealing cap C in the spring dome F Tighten the adjusting screw B such that the required preload is reached Install the protective cap A Reinsert the working diaphragm M on the guide rod N Put ...

Page 47: ... G Upper diaphragm disc HD version only H Allen screw 6 pieces I Spring dome ASE J Over pressure adjustment nut K Under pressure adjustment nut L Protective cap M Housing ASE N O Ring O Connecting piece ASE housing P Hexagonal socket grub screws 4 pieces Q ASE SAV mechanism only M O N P Q 1 1 Remove the impulse and vent lines 2 Remove the protective cap L 3 Release the setpoint springs at the adju...

Page 48: ...2 14 3 2 Removing the ASE SAV mechanism only from the housing Q Loosen four hexagonal socket grub screws M5x8 using an internal hex key SW 2 5 mm Remove the ASE Q from the housing using a hook wrench 60 90 mm 3 Remove the ASE Q Q Q P P ...

Page 49: ...ng N maintenance kit 4 or 5 in the turned groove in the housing M 2 Tighten the threads of the connecting piece O in the housing M using a hook wrench 60 90 mm 3 Fix the connecting piece O of the ASE Q using 4 hexagonal socket grub screws P M5x8 14 4 Required tools A B C2 D C1 E Order no 271170 ...

Page 50: ...SW 17 Open ended spanner A SW 13 SW 13 SW 13 4 Replace the control plate Open ended spanner A ND MD HD SW 13 SW 17 SW 17 5 Replace the valve seat Tube socket wrench B valve wrench E ND MD HD SW 30 SW 46 D 60 Regulator 14 5 SAV Leakage test Go to section 12 Commissioning decommissioning and recommissioning FRM or SAV for performing functional and leakage testing of SAV 14 6 Recommended maintenance ...

Page 51: ...Edition 02 22 No 270 442 51 68 B C 15 Spare parts A D E F G H I J ...

Page 52: ...D FRM 100025 MD FRM 100025 HD 270387 FRM 100040 ND FRM 100040 MD FRM 100040 HD 270388 FRM 100050 ND 270389 FRM 100050 MD FRM 100050 HD 271092 4 Valve seat with sealing ring and O Ring FRM 100025 ND FRM 100025 MD FRM 100025 HD 270390 FRM 100040 ND FRM 100040 MD FRM 100040 HD 270391 FRM 100050 ND FRM 100050 MD FRM 100050 HD 270392 5 Kit O Rings FRM 100025 ND FRM 100025 MD FRM 100025 HD 270393 FRM 10...

Page 53: ...uest 2 ASE with O Ring SAV 100025 ND SAV 6010 ND SAV 6015 ND 270375 SAV 100025 MD SAV 6010 MD SAV 6015 MD 270376 SAV 100025 HD SAV 6010 HD SAV 6015 HD 270377 SAV 100040 ND SAV 6020 ND 270378 SAV 100040 MD SAV 6020 MD 270379 SAV 100040 HD SAV 6020 HD 270380 SAV 100050 ND 270381 SAV 100050 MD 270382 SAV 1000050 HD 270383 J I M 15 2 List of spare parts of SAV ...

Page 54: ...RM 100025 MD 271094 FRM 100025 HD 271095 FRM 100040 ND 271096 FRM 100040 MD 271097 FRM 100040 HD 271098 F G C E D H D E F C G H 15 3 Complete regulator sets F G C E D H D E F C G H F G C E D H C D E B F G H B F G C E D H D E F C G H F G C E D H D E F C G H F G C E D H C D E B F G H B ...

Page 55: ... 15 4 Accessories Spare Part Version Order number Contents Adapter 1 4 G to 1 4 NPT SAV ASE 231944 no picture available Adapter 1 2 G to 1 2 NPT FRM 231945 no picture available Connector 1 4 G to 1 2 tubing USA for feedback impulse lines SAV ASE 267783 Connector 1 2 G to 1 2 tubing USA for feedback impulse lines FRM 278100 Nozzle set 8 pc Ø 1 5 9 mm 270712 Venting cap cover FRM 100025 100050 27794...

Page 56: ...ber products applies to the storage of diaphragms and O Rings The ageing process mostly depends on the following factors Temperature Thermal radiation Solar radiation Humidity Relative humidity Ozone Stress conditions of the components Proper storage Storage temperature between 5 C and 20 C No direct solar radiation No direct heat sources in the storage area No exposure to ozone Tension free stora...

Page 57: ...AC 10 FRM ND MD HD Outlet pressure pu PSI Inlet pressure pd PSI 0 400 0 500 1 00 1 50 1 50 2 00 3 00 4 00 5 00 6 00 6 00 10 00 15 00 20 00 22 00 Inlet pressure pd W C 11 1 13 9 27 7 41 6 41 6 55 4 83 1 110 8 138 5 166 2 166 2 277 1 415 6 554 2 609 6 3 0 3548 3718 4370 3974 3980 4047 5 0 4604 4853 5967 5759 5752 5684 3504 3011 2575 2113 2113 0 0 0 10 0 6836 7253 9299 9402 9387 9242 9073 8413 7851 7...

Page 58: ...45 3663 4185 FRM ND MD HD Outlet pressure pu PSI Inlet pressure pd PSI 0 400 0 500 1 00 1 50 1 50 2 00 3 00 4 00 5 00 6 00 6 00 10 00 15 00 20 00 22 00 Inlet pressure pd W C 11 1 13 9 27 7 41 6 41 6 55 4 83 1 110 8 138 5 166 2 166 2 277 1 415 6 554 2 609 6 3 0 5092 5334 7115 6645 5717 5093 5 0 6634 6989 9751 9616 8380 8416 6234 5878 4975 4600 3408 0 0 10 0 9868 10458 15206 15663 13772 14938 16161 ...

Page 59: ...00 3867 4100 FRM ND MD HD Outlet pressure pu PSI Inlet pressure pd PSI 0 400 0 500 1 00 1 50 1 50 2 00 3 00 4 00 5 00 6 00 6 00 10 00 15 00 20 00 22 00 Inlet pressure pd W C 11 1 13 9 27 7 41 6 41 6 55 4 83 1 110 8 138 5 166 2 166 2 277 1 415 6 554 2 609 6 3 0 5378 5636 7529 7007 6038 5366 5 0 7001 7380 10303 10156 8851 8885 6590 6219 5256 4856 3595 10 0 10408 11035 16061 16539 14546 15762 17057 1...

Page 60: ...679 463 339 4 506 760 535 480 6 708 1063 764 831 766 8 910 1366 982 1079 1084 10 1112 1669 1200 1318 1332 12 1314 1972 1419 1558 1574 14 1517 2275 1637 1797 1816 16 1719 2578 1855 2037 2058 18 1921 2881 2073 2276 2300 20 2123 3184 2291 2515 2542 25 2628 3941 2836 3114 3147 FRM UHD pd bar pu bar 1 1 5 2 3 4 1 5 583 2 825 852 2 5 1011 1205 770 3 1167 1476 1089 3 5 1312 1704 1334 976 4 1458 1905 1541...

Page 61: ...79 3293 10 3381 4100 3648 4006 4049 12 3995 4300 4300 4300 4300 14 4609 4900 4900 4900 4900 16 5223 5400 5400 5400 5400 18 5500 5500 5500 5500 5500 20 5590 5590 5590 5590 5590 25 5700 5700 5700 5700 5700 FRM UHD pd bar pu bar 1 1 5 2 3 4 1 5 308 2 436 516 2 5 533 730 407 3 616 894 575 3 5 693 1032 704 515 4 769 1154 813 729 6 1076 1615 1162 1262 1164 8 1383 2075 1493 1639 1646 10 1690 2536 1824 20...

Page 62: ...283 54108 140 39335 49905 42709 45124 62143 160 44421 56365 48247 50971 70178 180 49514 62825 53783 56813 78213 200 54624 69276 59302 62639 86248 250 67344 85406 73115 77239 106335 300 80061 101534 86916 91812 126423 360 95320 120880 103492 109332 150529 FRM UHD Inlet pressure pd PSI Outlet pressure pu PSI 15 00 25 00 35 00 45 00 58 00 22 19517 587187 30 30154 19235 40 39157 41009 50 46720 53455 3...

Page 63: ...2 170812 170812 250 190662 192883 192883 192883 192883 300 197941 197941 197941 197941 197941 360 201155 201155 201155 201155 201155 FRM 250050 UHD DN 50 max flow volume CFH natural gas of density 0 81 kg m AC 5 FRM UHD Inlet pressure pd PSI Outlet pressure pu PSI 15 0 25 0 35 0 45 0 58 0 22 10317 355614 30 16098 11521 40 20912 23697 50 24991 30765 21032 60 28855 36359 28512 24546 80 36587 46363 3...

Page 64: ...35 1335 1335 1335 1335 1335 1335 1335 1335 10 1044 1334 1469 1469 1469 1469 1469 1469 1469 1469 1469 1469 1469 1469 1469 1469 1469 FRM ND MD HD pd bar pu bar 0 03 0 05 0 075 0 1 0 1 0 15 0 2 0 25 0 3 0 35 0 4 0 4 0 5 0 75 1 1 25 1 5 0 2 115 139 166 149 129 107 0 0 0 0 0 0 0 0 0 0 0 0 5 192 241 307 297 259 284 310 266 291 230 218 162 0 0 0 0 0 0 75 237 301 387 378 330 373 419 377 437 375 408 301 33...

Page 65: ...8 1650 1901 1754 2105 1881 2149 1588 1985 2130 2143 1990 2388 7 1155 1475 1911 1881 1640 1886 2173 2004 2404 2149 2455 1814 2268 2434 2449 2274 2729 8 1299 1659 2151 2116 1845 2121 2443 2254 2705 2417 2763 2041 2551 2737 2754 2558 3069 9 1443 1843 2389 2350 2050 2356 2715 2504 3005 2685 3069 2267 2834 3041 3060 2842 3410 10 1587 2027 2628 2586 2254 2591 2986 2754 3305 2953 3375 2494 3117 3344 3366...

Page 66: ...114 16 2000 2999 2157 2369 2395 18 2234 3352 2411 2648 2676 20 2469 3704 2665 2927 2957 25 3057 4585 3299 3622 3661 FRM 250050 UHD DN50 max air flow volume Nm3 h AC 10 FRM UHD pd bar pu bar 1 1 5 2 3 4 1 5 498 0 0 0 0 2 704 834 0 0 0 2 5 862 1180 657 0 0 3 996 1445 929 0 0 3 5 1119 1669 1138 833 0 4 1244 1865 1314 1178 0 6 1740 2610 1878 2040 1882 8 2236 3354 2413 2650 2661 10 2733 4099 2948 3238 ...

Page 67: ...gulator Therefore to calculate the mass flow through a nozzle a distinction is made between two ranges a subcritical or critical pressure ratio b supercritical pressure ratio with QN power of the regulator under standard conditions QN pd 1 013 pu pd KG QN 2 pu 1 013 KG pd abs pu abs 0 53 0 53 pd abs pu abs Abbreviation Description pd bar Outlet pressure pd abs bar Outlet pressure as absolute press...

Page 68: ... 298 Gaz EN 230 Oil Flame detector UV probes 1 N A 10 000 Operating hours Gas pressure regulators1 N A 15 EN 88 1 EN 88 2 Gas valve with valve testing system2 after error detection EN 1643 Gas valve without valve testing system2 50 000 200 000 depends on diameter 10 EN 161 Gas air ratio control system N A 10 EN 12067 2 EN 88 1 1 Performance decrease due to ageing 2 Gas families I II III N A not ap...

Reviews: