Service Manual for
RCO Speed Oven
40
Inverter Settings
#
NAME
DESCRIPTION
SETTING DEF SETTING/RANGE
Initialization
A1-01 Access Level
Selection
Selects which parameters are
available via the digital operator.
2
2
0: Operation Only
A1-03
Initialize
Parameters
Resets all parameters to factory
default settings. (Initializes the
drive then returns A1-03 to 0)
0
0
0: No initialize
A1-04 Password 1
When the value set into A1-04 does
not match the value set into A1-
05, parameters A1-01 and A1-03
cannot be changed.
0
0
0 to 9999
A1-05 Password 2
0
0
Application
b1-01
Frequency
Reference
Selection
Selects the frequency reference
input source.
1
1
0: Operator - Digital preset speed
d1-01 to d1-17
1: Terminals - Analog input terminal
2: MEMOBUS/Modbus
communications (option)
3: Potentiometer (option)
b1-02 Run Command
Select
Selects the run command input
source.
1
1
0: Operator - RUN and STOP keys
on the digital operator
1: Digital input terminals
2: MEMOBUS/Modbus
communications (option)
b1-03 Stopping Method
Selection
Selects the stopping method when
the run command is removed.
1
0
0: Ramp to stop
1: Coast to Stop
b1-04
Reverse
Operation
Selection
Permits or prohibits reverse
operation.
0
0
0: Reverse enabled
1: Reverse disabled
b1-07 LOCAL/REMOTE
Run Selection
Determines the operation when the
Run command source is switched
from LOCAL to REMOTE or
between Run source 1 and 2 while
an external Run command is active
at the new source.
0
0
0: External Run command has to
be cycled at the new source to be
activated
1: External Run command at new
source is accepted immediately
b1-08
Run Command
Selection while
in Programming
Mode
0
0
0: Run command accepted only in
the operation menu
1: Run command accepted in all
menus
2: Prohibit entering Programming
Mode during Run
b1-14 Phase Order
Selection
Sets the phase order for drive
output terminals U/T1, V/T2 and
W/T3.
0
0
0: Standard
1: Switch Phase Order
b1-17 Run Command at
Power Up
Determines the operation when a
Run command is active at power
up of the drive.
0
0
0: Run command not issued, needs
to be cycled
1: Run command issued, motor
operation start
b2-02 DC Injection
Braking Current
Sets the DC Injection Braking
current as a percentage of the drive
rated current
50
50
0 to 75%
b2-03
DC Injection
Braking Time/DC
Excitation Time at
Start
Sets DC Injection Braking time at
start. Disabled when set to 0.00
seconds.
0.00
0.00 0.00 to 10.00 seconds
b2-04
DC Injection
Braking Time at
Stop
Sets DC Injection Braking time
at stop. When b1-03 = 0, this
parameter sets the amount of DC
Injection time applied to the motor
at the end of the decel ramp.
Disabled when set to 0.00.
0.50
0.50 0.00 to 10.00 seconds