5. To check the follow designation at the master station, press the FOLLOW
pushbutton. The LED indicator next to the designated follow station pushbutton
lights.
6. Press FOLLOW again to return the master station to normal operation.
Note:
The FOLLOW pushbutton LED at the master station flashes whenever any remote
station is assigned as a follow station.
Removing a Remote Station from Follow
Note:
FOLLOW can be removed from either the master or the follow station. Only one
of the following procedures should be performed.
At the master station:
1. Press the FOLLOW pushbutton. The LED indicator next to the follow station
pushbutton lights.
2. Press the pushbutton of the follow station. The follow station LED indicator goes
out.
3. Press the FOLLOW button again. The FOLLOW LED indicator goes out.
The station is now removed from its follow designation.
At the follow station:
Press the CALL pushbutton. Within 2–3 seconds press the CANCEL pushbutton.
The station is now removed from its follow designation.
Reminder lets staff members delay answering non-critical calls by setting the calling
remote station to place a new call after a programmed length of time. Only 4A3100
Series enhanced stations can be placed on reminder. The reminder feature can be dis-
abled during system configuration.
Reminder Notes
— A station designated for FOLLOW cannot be set on reminder.
— Stations placing calls with a lavatory emergency priority or higher cannot be
placed on reminder.
16
ProCare 2000 Operation Manual
(Staff Follow)
Reminder
Summary of Contents for 4A3076B