Before activating air calibration mode:
• Close all windows and doors�
• Ensure that all duct openings in the DucoBox are fully closed and that the
DucoBox cover is closed!
• Avoid air leaks in the ventilation ducts�
• Set all window ventilators to the open position� Any Tronic ventilators will open
automatically�
open
3
Pull the plug out of the socket and wait a few seconds�
Iteration
Rev. Date
Name
Description
23-Nov-17
Status Date
Status
STEKKER_STOPCONTACT
mm³
dm²/m
kg/m
mm
Handelsstraat 19 - 8630 VEURNE
tel. 0032-58/330033 - fax.0032-58/330044
email: info @ duco.eu www.duco.eu
This drawing is property of Vero Duco NV and can not be copied, neither shown to
third party/externally without written permission.
0.000
0.000
Drawing Number
Volume
Coat. Surf.
Weight
Outline
STEKKER_STOPCONTACT
Format: A3
Production Number:
Mat.:
Draftsman: -
Tol.: -
Scale: 1.000
POWERCABLE
Date: 23-Nov-17
4
Put the plug back into the socket� The DucoBox will be configured automatically on
start-up� Calibration takes 30 s 1 minute per connected control valve�
Iteration
Rev. Date
Name
Description
23-Nov-17
Status Date
Status
STEKKER_STOPCONTACT
mm³
dm²/m
kg/m
mm
Handelsstraat 19 - 8630 VEURNE
tel. 0032-58/330033 - fax.0032-58/330044
email: info @ duco.eu www.duco.eu
This drawing is property of Vero Duco NV and can not be copied, neither shown to
third party/externally without written permission.
0.000
0.000
Drawing Number
Volume
Coat. Surf.
Weight
Outline
STEKKER_STOPCONTACT
Format: A3
Production Number:
Mat.:
Draftsman: -
Tol.: -
Scale: 1.000
POWERCABLE
Date: 23-Nov-17
* Depending on the software version of the User controller / CO
2
/Humidity sensor�
08.B
Checking
The steps set out below can be used to check whether flow rates have been set correctly�
Checking configured flow rate
1
Open the DucoBox cover�
2
Press ‘HIGH’ briefly� The DucoBox will remain in configuration mode for 30 minu-
tes (as standard)�
3
Close the cover�
4
Wait at least one minute to allow the ventilation system to stabilise�
5
Measure the vents� If a flow rate differs from the desired output, this can be adjus-
ted via the display menu or using the Duco Network Tool�
6
If you finish before the standard setting of 30 minutes, re-open the DucoBox cover
and press ‘HIGH’ again� Then replace the cover on the DucoBox�