DSC PowerSeries PC585 Installation Manual Download Page 1

Installation 

Manual

WARNING

This manual contains information on limitations regarding product use and function and information on the 

limitations as to liability of the manufacturer. The entire manual should be carefully read.

PC585

Software Version 2.2C

DLS-3 v1.3 and higher

Summary of Contents for PowerSeries PC585

Page 1: ...al contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read PC585 Softwa...

Page 2: ...ate Testing Most problems that would prevent an alarm system from operating as intended can be found by regular test ing and maintenance The complete system should be tested weekly and immediately aft...

Page 3: ...ection 5 Program Descriptions 16 5 1 Programming Security Codes 16 5 2 Zone Programming 16 5 3 Zone Attributes 17 5 4 Assigning Keypad Zones 18 5 5 Communicator Dialing 18 5 6 Communicator Account Num...

Page 4: ...ii PC585 Wiring Diagram Please see the PC585 Installation Manual section 2 10 for important information 8...

Page 5: ...Supports GSM1000 cellular communication Two account numbers DTMF dialing DPDT line seizure R button feature Split reporting of selected transmissions to each tele phone number System Supervision Featu...

Page 6: ...will call both the land line and via the GSM1000 Cabinets Several different cabinets are available for the PC585 mod ules They are as follows PC5003C Cabinet Main control cabinet for the PC585 main p...

Page 7: ...ut the Programming Worksheets completely before attempt ing to program the system Step 10 Testing the System Test the panel thoroughly to ensure that all features and func tions are operating as progr...

Page 8: ...nected to the four Keybus terminals or wires of all modules The following restrictions apply to Keybus wiring Keybus should be run in minimum 22 gauge quad 0 5mm two pair twist is preferred The modul...

Page 9: ...than 1 000 305m from the panel the module does not have enough power For more information regarding module supervision troubles please refer to 2 Trouble Display 2 7 Removing Modules The panel must be...

Page 10: ...be configured for GSM1000 Supervision Program this zone as zone type 09 24 hr Supervisory in section 001 With a GSM1000 Supervi sory zone if the GSM1000 experiences a trouble the zone will be violate...

Page 11: ...this section one for each keypad slot Enter a 2 digit zone number for each of the keypad zones This number must be entered in the location corresponding to the keypad to which each zone is con nected...

Page 12: ...me when it will check the system again If the system is disarmed at the auto arm time the panel will sound the buzzer of all key pads for five minutes If the Bell Squawk During Auto Arm option is enab...

Page 13: ...visory The panel has lost communication with a module connected to the Keybus see section 2 6 Supervision The event buffer will log the event NOTE All tamper conditions must be physically restored bef...

Page 14: ...ess codes in use One time Use Codes If the panel is disarmed with a one time use code the code will be erased at the end of the exit delay the next time the panel is armed The code will also be erased...

Page 15: ...minute quick exit delay If a second Delay zone is tripped or if the zone is not restored after two minutes the panel will begin the entry delay NOTE If the Exit Delay is in progress performing a Quick...

Page 16: ...feature if enabled will override the clock display This option can be programmed in LCD programming section 66 option 4 24 hr Time Display Option Each LCD5500Z can be programmed to display time using...

Page 17: ...h sec tion requiring decimal data e g codes telephone numbers If a digit is entered for each program box the panel will auto matically exit from the selected programming section The Ready light will t...

Page 18: ...ys Fire Auxiliary or Panic to advance to the next digit When all the digits in a section have been viewed the panel will exit the section the Ready Light will turn OFF and the Armed light will turn ON...

Page 19: ...tem should be disarmed If the panel is disarmed before the entry time expires no alarm will be generated 02 Delay 2 Zone The Delay 2 entry delay time can be set independently of Delay 1 in programming...

Page 20: ...o gramming before the system can be armed NOTE Wireless zones should not be programmed as zone types 22 24 22 Momentary Keyswitch Arm Zone Momentary violation of this zone will alternately arm disarm...

Page 21: ...to Communicate FTC trouble condition The maximum number of dialing attempts that can be programmed is 15 The 3rd Telephone Number can be used to back up the 1st in the event of an FTC see section 5 7...

Page 22: ...Key regardless of this option Wireless Maintenance The panel will transmit a Wireless Device Low Battery Alarm reporting code if a low battery condition is indicated by a detector Transmission and log...

Page 23: ...B simulates the key on a touch tone telephone Hex C simulates the key on a touch tone telephone Hex D forces the panel to search for dial tone Hex E two second pause Hex F marks the end of the teleph...

Page 24: ...rform on site download ing To Initiate Local Downloading via the PC Link enter 8 Installer s Code 499 Installer s Code 499 All keypads will be busy for the duration of the PC Link connection The statu...

Page 25: ...ll activate the output by selecting some or all of the following attributes Attribute 1 Service Required battery bell general trouble general tamper general supervisory 2 AC Failure 3 Telephone Line T...

Page 26: ...set of attributes listed below the description of each output type PGM output options 01 03 05 08 11 28 have the following attributes Attribute ON OFF 1 Output Enabled Disabled 3 True Output Inverted...

Page 27: ...ne Test Transmission M D Section 702 3 5 15 Transmission Delay If the transmission delay zone attribute is selected for a given zone the panel will delay reporting an alarm for that zone for the numbe...

Page 28: ...during the last 10 sec onds to warn the user the system is about to go into alarm If there was an alarm during the armed period the keypad will pulse for the entire entry delay to warn the user of th...

Page 29: ...mper and Tamper Restoral Reporting Codes Section 338 System Tampers Req Installer Reset Section 701 4 NOTE After enabling keypad tampers it is recommended to tamper and restore all keypads to ensure p...

Page 30: ...base is Internal Crystal option If the 50 or 60Hz AC power input is very stable it can be used as the timebase by enabling the Timebase is AC line option Timebase Internal Crystal AC line Section 701...

Page 31: ...put for two seconds log the event to the event buffer and communicate the alarm to central station Each zone should be tested several times during the test Check the event buffer to ensure that all z...

Page 32: ...________________________________I Keypad 7 I_____________________________________________I I____________________________________________________________________________________________________________...

Page 33: ...I________I Basic Programming Zone Definitions NOTE Keypads must be installed to use 24 hr Buzzer zones 001 Zone 1 8 Definitions Section 5 2 Zone Programming Default Default 01 I_______I_______I Zone 1...

Page 34: ...For Future Use 17 Away Armed Status 03 Sensor Reset 18 Stay Armed Status 04 For Future Use 19 Command Output 1 7 1 05 System Armed Status 20 Command Output 2 7 2 06 Ready To Arm 21 For Future Use 07 K...

Page 35: ...ay Termination Disabled OFF I________I 8 Fire Bell is Continuous Fire Bell Follows Bell Cut off 015 Third System Option Code Default Option ON Off OFF I________I 1 Fire Keys Enabled Fire Keys Disabled...

Page 36: ...zone Default 00 I________I_______I Keypad slot 1 Zone Valid entries are zones 01 08 00 I________I_______I Keypad slot 2 Zone Valid entries are zones 01 08 00 I________I_______I Keypad slot 3 Zone Val...

Page 37: ...d on programming in section 001 Attribute 1 2 3 4 5 6 7 8 ON Audible Steady Chime Bypass Force Swing Tx Delay Wireless Zn OFF Silent Pulsed No No No No No No Zone Type 00 Null Zone N N N N N N N N 01...

Page 38: ...e Output Follows Timer Code Req OFF Output disabled Inverted On Off No Code Req PGM Option 01 Burg Fire Bell Y Y 03 Sensor Reset Y Y N 05 Armed Status Y Y 06 Ready To Arm Y Y 07 Kypd Bzz Follow Y Y 08...

Page 39: ...__I_______I_______I_______I 320 Alarm Reporting Codes Zones 1 8 Section 5 8 Communicator Reporting Codes on pg 18 Appendix A Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 I_______I_______I I...

Page 40: ...__I I_______I_______I I_______I_______I I_______I_______I I_______I_______I 345 Code 9 Code 10 Code 11 Code 12 Code 13 Code 14 Code 15 Code 16 I_______I_______I I_______I_______I I_______I_______I I__...

Page 41: ...ireless Device Low Battery Restore 354 User Walk Test Reporting Codes Section 5 8 Communicator Reporting Codes on pg 18 Appendix A I_______I_______I 1 Walk Test Lead In I_______I_______I 2 Walk Test L...

Page 42: ...e GSM1000 backup call directions will only back up their respective telephone numbers 370 Communication Variables Default 010 I_______I_______I_______I Swinger Shutdown Alarms and Rest 001 014 Transmi...

Page 43: ...I_______I_______I_______I_______I Program all unused digits with Hex F 392 GSM1000 Preamble Third Telephone Number Section 5 26 GSM1000 Cellular Communicator Default FFFF I_______I_______I_______I___...

Page 44: ...OFF I_______I 4 All System Tampers Require Installer ResetAll System Tampers Follow Restore OFF I_______I 5 6 Digit User Access Codes 4 Digit User Access Codes OFF I_______I 6 For Future Use OFF I____...

Page 45: ...ule transmitter Zones 01 8 Press to Cancel Placement Led Keypad LCD Keypad Bell Buzzer Good Light 1 ON Steady GOOD 1 Beep Squawk Fair Light 2 ON Steady FAIR 2 Beeps Squawks Bad Light 3 ON Steady BAD 3...

Page 46: ...pervisory Alarm Rest panel loses restores supervisory transmission over the Keybus from enrolled PC5132 module or keypads with zone inputs A R 1 43 UA 00 UH 00 328 Cross Zone Police Code Alarm two zon...

Page 47: ...00 UJ 00 352 Periodic Test periodic system test transmission T 6 A2 RP 00 352 System Test 6 bell communications test T 6 A1 RX 00 353 Wireless Device Low Battery Trouble Rest wireless zones WLS904 WLS...

Page 48: ...Default Zone 4 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I Default Zone 5 I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____...

Page 49: ...I_______I 1 F ire Keys Enabled F ire Keys Disabled ON I_______I 2 A uxiliary Keys Enabled A uxiliary Keys Disabled ON I_______I 3 P anic Keys Enabled P anic Keys Disabled OFF I_______I 4 8 For Future...

Page 50: ...46 99 Reset LCD EEPROM to Factory Defaults ASCII Characters...

Page 51: ......

Page 52: ...to Canada www dsc com Printed in Canada 29005990 R001 Direct all comments concerning this publication to pubs dscltd com Module Compatible Comments Classic Escort VPM 1 No Escort5580 TC No PC 16 Out N...