DryGair Dehumidification Unit Model DG-X
Troubleshooting and Repairing the Unit
Ver. 12/2020
41
8.
TROUBLESHOOTING AND REPAIRING THE
UNIT
8.1
Troubleshooting
The troubleshooting section provides malfunction symptoms, the possible
cause, and what may be done to overcome.
Symptom
Possible Cause
Remedy
Unit is not operating
No power to the unit
Check the power from the power
supply panel
Overload tripped
Reset the overloads
Little or no airflow
The fan motor is burnt
Replace the fan
Refrigeration coils are dirty
See section 7
—Maintaining the unit
Loose electrical wiring
connections
Check the wiring diagram to find
the fault and repair
Circuit breaker tripped
Reset the circuit breaker
Little or no water extraction
Insufficient airflow
Check and perform the suggestions
for the above "Little or no airflow"
symptom
Compressor fault
Contact the factory service center
Loss of refrigerant
Contact the factory service center
Unit vibrates excessively
Loose compressor
Tighten the nuts of the compressor
mounts
Damaged fan
Replace the fan
The compressor is not secured
Tighten the compressor's bolts
Water flooding inside the
machine
Drain-pipe is blocked/frozen
Clear the obstruction
Drain-pipe is too high
Ensure that no section of the drain
hose is above the level of the water
outlet
Crimped or blocked tubing
Straighten, clear, or replace the
tubing
The compressor is not
working while the fan is
working
High-pressure switch fault
Press the HP switch button
Circuit breaker tripped
Toggle circuit breaker (E3)
Compressor overload tripped
Reset the overload (ST3)
Fan is not rotating
Circuit breaker tripped
Press circuit breaker (E1)
Compressor overload tripped
Reset the overload (ST1)