Unit Operation
Preparing the Unit for Operation
DryGair Energies Ltd
.
30
6.2.3
Configuring the Humidity Set-Point
The humidity controller is connected to the right-side door, enabling access to
the controller setup keys when the door is closed.
The DG-X unit also includes a remote control for the humidity controller.
Note
Configuring the humidity set-point can be done through the controller or
through the remote control (
Set
button).
Note
The factory default value is around 75% RH.
To set the required Humidity percentage:
Press the
Set
button once. The screen displays "
ST 1
".
When the
Set
button is released, the default humidity set-point will flash
on the display screen.
Figure 6-1. Humidity controller (and remote control)
2.
Set the required humidity percentage value using the
Up
/
Down
arrow
buttons.
3.
Press the
Set
button again to save the change.
The current humidity level that the sensor reads is displayed on the
screen (the actual humidity level is displayed).