background image

 

6.5.

 

INSTALLATION OF PUMPING UNITS / PLUGS 

The pumping units are not included in the pump and must be selected and purchased separately. The plugs are included in 
the pump and already mounted in the pumping holes. 
To mount the pumping units, proceed as indicated below: 

 

Identify the most correct position, distributing them evenly on the holes. 

 

Remove the plugs from the holes using a 16-mm fixed wrench or a 6 mm Allen wrench for Multi-line systems and 12 
mm Allen wrench for progressive systems. 

 

Screw  in  the  pumping  units  and  tighten  to  a  torque  of  12Nm  (Multi-line)  and  20  Nm  (Progressive)  using  a  16  mm 
(Multi-line) and 27 mm (Progressive) fixed wrench. 

 

WARNING:  Introduce  the  pumping  unit  into  the  pre-established  output,  taking  particular  care  for  correct 

engagement in the threading. 

7.

 

INSTRUCTIONS FOR USE 

7.1.

 

OPERATIONS TO CARRY OUT BEFORE START-UP 

 

The unit can be started up only by specialized personnel. 

 

Using the pump submerged in fluids or in particularly aggressive or explosive/flammable elements is prohibited unless it 
has been prepared ahead of time by the supplier for this purpose. 

 

Use gloves and eye protection as required by the lubricant safety data sheet. 

 

DO NOT use lubricants that are aggressive to NBR gaskets. If you are unsure, contact the Dropsa S.p.A. technical office 
for a detailed list of recommended lubricants. 

 

Never ignore health hazards and follow sanitary regulations. 

 

Always use suitable piping for the operating pressure. 

 

Check the integrity of the pump. 

 

Check the lubricant level in the tank (min/max indication on the tank). If the level is low, proceed as described in section 
7.2.1. Filling the tank. 

 

Ensure that the pump operates at the operating temperature and that the piping is free of any air bubbles. 

 

Check for proper connection of the electrical devices. 

 

To determine the maximum operating pressure, you must know the pressure drop for the piping connected to the pumping 
units based on the length, operating temperature and type of lubricant. 
Based on these variables for correct distribution to the point, you must always ensure that the piping pressure loss, summed 
with the pressure required on the point to be lubricated, is not  higher than the maximum potential pressure at the pump 
delivery. 

7.2.

 

LOADING LUBRICANT 

Ensure that all the pumping unit / plug lodging holes have been occupied. 

 

WARNING: In order to prevent any malfunctions and voiding of the warranty, we recommend topping up the 

lubricant without impurities exclusively from the dedicated loading system. 

 

7.2.1.

 

FILLING THE TANK (FOLLOWER PLATE VERSION) 

The feeder is filled using a dedicated device complete with a filter. In case it is necessary to perform the initial filling (with the 
pump completely empty and no remaining grease from the previous load), the pump must be positioned vertically to remove 
the air in the tank until the vent point corresponding to the red maximum level indicator is reached (the lubricant is supplied 
from the base). To speed up the air bleeding operation, we recommend pressing the indicator until all the air is evacuated, 
releasing it at the same time as interrupting the filling of the tank. Subsequently, filling can be performed based on different 
guidelines, checking that the maximum level line is not exceeded. If the line is exceeded, lifting of the maximum level will be 
indicated

 

up to a maximum of 10mm (0.39”). After that, if filling is not interrupted, a leakage of lubricant will be noticed from 

the central part of the follower plate (air vent). This will not cause a problem or malfunctioning, but grease may leak from the 
drain hole of the tank if there is an excessive amount. 
 

Summary of Contents for 888580

Page 1: ...INGS OF LUBRICATION CONTROL 10 APPLICATION EXAMPLES 11 PROBLEMS AND SOLUTIONS 12 MAINTENANCE PROCEDURES 13 DISPOSAL 14 ORDERING INFORMATION 15 DIMENSIONS 16 HANDLING AND TRANSPORT 17 PRECAUTIONS FOR U...

Page 2: ...variables such as the volume and frequency of the grease required for each point the number of points the management conditions and the pressure of the pump 2 2 DIRECT LUBRICATION TO THE POINT MULTI L...

Page 3: ...L TECHNICAL CHARACTERISTICS Pumping system Type Cam with spring return Flow rate Multi line cm 3 rev in 3 rev 0 005 0 01 0 015 0 025 0 05 0 0003 0 0006 0 0009 0 0015 0 003 Progressive cm 3 min in 3 mi...

Page 4: ...flow rate value refers to the following test conditions grease with NLGI 2 consistency class standard environmental conditions Temperature 20 C 68 F pressure 1bar 14 5psi counter pressure of 50bar 73...

Page 5: ...H CARTRIDGE 700CC 400CC 5 3 PROGRESSIVE PUMPING UNIT FIXED FLOW RATE ADJUSTABLE FLOW RATE Magnet for minimum level Preloaded cartridge Cartridge guard Minimum level with reed Notches M22x1 5 Output G1...

Page 6: ...INE PUMPING UNIT 5 5 KIT BY PASS OPTIONAL WITHOUT pressure gauge WITH pressure gauge 5 6 KIT VENT VALVE OPTIONAL Solenoid valve DIN 43650 Connection to the pumping unit Pos B Progressive G1 4 Discharg...

Page 7: ...tures Do not install the pump near heat sources or electrical equipment that may disrupt correct operation of the electronics Ensure that pipes and cables are appropriately secured and protected from...

Page 8: ...DC Ground 4 Black Input 1 4 Black Output 1 max 1A 5 Green Ground Input signals Omega connector System sensors Pin Description Connection NPN PNP CONTATTO 1 3 2 Input 2 4 Input 1 Input signals Omega co...

Page 9: ...g is free of any air bubbles Check for proper connection of the electrical devices To determine the maximum operating pressure you must know the pressure drop for the piping connected to the pumping u...

Page 10: ...10 EMPTY LOADING MAXIMUM LEVEL with air MAXIMUM LEVEL without air OVER MAXIMUM LEVEL SAFETY DISCHARGE Max liv 10mm Grease outlet Air venting Min liv Air Grease...

Page 11: ...ensuring that you evacuate all the air in the mouth Taking care not to allow the air to come back in screw the cartridge onto the pump all the way tightening it moderately Insert the magnet in the ne...

Page 12: ...remains on hold before the start of the next lubrication cycle or the standby phase if only one lubrication cycle is set The lube can be adjusted in five ways PS SEP Discharging of lubricant is contr...

Page 13: ...u can view additional information concerning the status of the alarm warning present BASE MENU Allows you to enter the base programming menu STATUS BAR Displays active Alarms Warnings current date and...

Page 14: ...the entire system 3 LUBRICANT From the Lubricant menu it is possible to activate deactivate notifications corresponding to filling and or reorganization of the lubricant contained in the pump 4 SYSTEM...

Page 15: ...the interface navigation between the settings menus and it contains a detailed explanation of every parameter and the possible values that they can assume The pump can be managed with 2 MAIN MENU BASI...

Page 16: ...nd consequently the pump does not start the lubrication cycle To resolve this error you need to change the parameter s with a correct combination of parameters 9 1 1 1 PARAMETERS RELATING TO THE OPERA...

Page 17: ...ted Pulse Count Pulse Count Suspensions 6 Pulse count Not Connected Pulse Count Pulse Count Suspensions 7 Time Pulses Not Connected Pulse Count Pulse Count Suspensions 8 Pulses Timeout Not Connected P...

Page 18: ...TERS RELATING TO LUBRICATION SETTING The following table shows the operating parameters present only in the ADVANCED MENU relating to lubrication and the possible values that can be set The Operating...

Page 19: ...ixed e Pause lamp Conduct of lubrication status output Only lubrication Lub fixed and Pause lamp Lub status output Lubrication output status contact Type P Lubrication Status Output signal type Type N...

Page 20: ...oot Device Device reboot button Time zone Time zone 2H 00M Time zone setting 12H 00M 12H 00M Device Info Device Info Pump general information display button Current date Current date Setting of curren...

Page 21: ...SEP a typical application can be implemented using operating mode 2 PS SEP Pulses with the following settings Basic parameters o Interval Pulses 2 Advanced Parameters o Input 1 Pulses Count o Input 2...

Page 22: ...00s Advanced Parameters o Input 1 Pulses Count o Input 2 Not connected o Number of cycles 1 With this configuration the lubrication phase is formed of a single cycle Number of cycles 1 that starts ev...

Page 23: ...ations shown on the display The pump begins the greasing phase but ends it immediately Defective motor or high output absorption Allow to cool for a few minutes and try again If the problem persists r...

Page 24: ...hours Every 1500 hours Check the fitting connection Check fixing to the parts of the machine Tank level As required Restore the lubricant level in the tank Filling filter As required Check and replace...

Page 25: ...133645 Laser probe tank kit 0039976 Power supply connector 3133646 Venting valve kit 24VDC 0039830 4 pin signals connector 0039976 DIN 43650 connector without cable 0888520 700cc cartridge guard 00390...

Page 26: ...26 15 DIMENSIONS Version 700cc Cartridge Version 400cc Cartridge Version 400cc Cartridge Dimensions in mm in...

Page 27: ...tive 93 112 EEC related to the type of lubricant selected and supplied by the manufacturer NOTE The pump is designed to work with maximum NLGI 2 grade lubricants Use NBR gasket compatible lubricants A...

Reviews: