6
DRISTEEM RTS HUMIDIFIER SDU INSTRUCTIONS
Steam outlet
Throw
Air intake
grille
OM-8114
Rise
FIGURE 6-1: SDU-E-RX RISE, SPREAD, AND THROW
Spread
INSTRUCTIONS
Nonwetting distances
Table 6-1:
SDU-E-RX minimum nonwetting distances
kW
Maximum steam
capacity
40% RH @ 70 °F (21 °C)
50% RH @ 70 °F (21 °C)
60% RH @ 70 °F (21 °C)
Rise
Spread
Throw
Rise
Spread
Throw
Rise
Spread
Throw
lbs/hr
kg/h
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
ft
m
2
6
2.7
1.0
0.3
1.0
0.3
5.0
1.5
1.5
0.5
1.5
0.5
6.5
2.0
2.5
0.8
2.5
0.8
7.5
2.3
4
12
5.4
1.0
0.3
1.0
0.3
5.0
1.5
1.5
0.5
1.5
0.5
6.5
2.0
2.5
0.8
2.5
0.8
7.5
2.3
6
18
8.2
1.0
0.3
1.0
0.3
5.0
1.5
1.5
0.5
1.5
0.5
6.5
2.0
2.5
0.8
2.5
0.8
7.5
2.3
8
24
10.9
1.0
0.3
1.0
0.3
5.5
1.7
1.5
0.5
1.5
0.5
6.5
2.0
2.5
0.8
2.5
0.8
7.5
2.3
10
30
13.6
1.5
0.5
1.5
0.5
6.0
1.8
2.0
0.6
2.0
0.6
7.0
2.1
3.0
1.0
3.0
1.0
8.0
2.5
12
36
16.3
1.5
0.5
1.5
0.5
6.0
1.8
2.0
0.6
2.0
0.6
7.0
2.1
3.0
1.0
3.0
1.0
8.0
2.5
14
42
19.1
2.0
0.6
2.0
0.6
7.0
2.1
2.0
0.6
2.0
0.6
7.0
2.1
3.0
1.0
3.0
1.0
9.0
2.7
16
48
21.8
2.0
0.6
2.0
0.6
7.0
2.1
2.0
0.6
2.0
0.6
7.0
2.1
3.0
1.0
3.0
1.0
9.0
2.7
21
63
28.6
2.0
0.6
2.0
0.6
7.5
2.3
2.5
0.8
2.5
0.8 10.0 3.0
3.0
1.0
3.0
1.0 12.0 3.7
25
75
34.0
2.0
0.6
2.0
0.6
8.0
2.5
2.5
0.8
2.5
0.8 10.5 3.2
3.5
1.1
3.5
1.1 12.5 3.8
30
90
40.9
2.0
0.6
2.0
0.6
8.0
2.5
2.5
0.8
2.5
0.8 10.5 3.2
3.5
1.1
3.5
1.1 12.5 3.8
34
102
46.3
2.0
0.6
2.0
0.6
8.0
2.5
2.5
0.8
2.5
0.8 10.5 3.2
3.5
1.1
3.5
1.1 12.5 3.8
Notes:
• Surfaces or objects directly in the path of steam discharge may cause condensation and dripping.
• To avoid steam impingement on surrounding areas, observe the minimum nonwetting dimensions in this table.
• Rise: The minimum nonwetting height above the steam outlet of the SDU-E-RX.
• Spread: The minimum nonwetting width from the steam outlet of the SDU-E-RX.
• Throw: The minimum nonwetting horizontal distance from the steam outlet of the SDU-E-RX.