SETUP AND CONFIGURATION
Configuration of BACnet
®
humidistat devices
CONFIGURATION OF BACNET HUMIDISTAT DEVICES
The communication parameters may be set via operation terminals. Login to the
controller as follows:
1. Press UP/DOWN buttons simultaneously for three seconds. The display will
show firmware version and revision number. Press the OPTION button to
start login.
2. CODE is shown in small display.
3. Select 241 using UP/DOWN buttons.
4. Press OPTION after selecting the correct code.
5. Once logged in with 241 control modules are displayed (Lp1, Lp2, 1u,
2u, etc.) – select with UP/DOWN the communication parameters CO and
open with OPTION. As soon as the module is open its parameters are
displayed.
6. Select the parameters with the UP/DOWN buttons. Change a parameter
by pressing the OPTION button. Three arrows are displayed to indicate
that the parameter may be modified. Use UP/DOWN buttons to adjust the
value.
7. After you are done, press OPTION to save the new value and return to
the selection level (arrows disappear when selection is saved). Pressing left
hand POWER button without pressing OPTION will discard the value and
return without saving. For control parameters press POWER again to leave
parameter selection and return to control module selection.
Press the POWER to leave the menu. The unit will return to normal operation if
no button is pressed for more than 5 minutes.
CHANGING PARAMETERS OF THE CONTROLLER THROUGH BUS COMMUNICATION
It is possible to remotely changing parameters through an indirect read/write
mode using objects AV12 and AV13. Find details on the procedure required
and how to interpret values in the application note: Parameters access through
AEX-BAC V1.2 at www.vectorcontrols.com
15
DRISTEEM TCI AND TRI2 HUMIDISTAT INSTALLATION, OPERATION, AND MAINTENANCE MANUAL