1. Press the UP and DOWN button simultaneously for three seconds. The
display will indicate the firmware version in the upper large digits and the
revision in the lower small digits. Press the RIGHT or POWER key to start
login.
2. CODE is shown in the small display.
3. The code for accessing the user parameters is 0009, for control
parameters it is 0241.
4. Select this by using the UP or DOWN buttons.
5. Press the RIGHT or POWER button after selecting the correct code.
6. Once logged in the parameter group can be selected with the UP and
DOWN key. Enter the group with the RIGHT or POWER key.
7. Once the group is selected, the parameter is displayed immediately.
8. Select the parameters with the UP/DOWN buttons. Change a parameter
by pressing the RIGHT button. Arrows 8 to 10 show up and indicate that
the parameter may be modified now. Use UP or DOWN buttons to adjust
the value.
9. Once complete, press RIGHT or POWER in order to save the new value of
the parameter and return to the selection level. Pressing the LEFT key will
discard the value and return to the selection menu without saving.
10. Press the LEFT key again so as to leave the parameter menu and return to
the group selection. Press LEFT key again while in the group selection to
return to normal operation.
11. The unit will return to normal operation if no key is pressed for more than
five minutes.
SETUP AND CONFIGURATION
Changing the parameters
12
DRISTEEM TCI AND TRI2 HUMIDISTAT INSTALLATION, OPERATION, AND MAINTENANCE MANUAL