20
GTS HUMIDIFIER LX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
If the ambient temperature in the enclosure is below 50 ºF (10 ºC), the heater
is powered up. The heater remains powered up until the enclosure reaches
50 ºF (10 ºC). When there is no call for humidity, an aquastat maintains tank
temperature at the factory default of 50 ºF (10 ºC). This temperature can be
reset in the field to be from 50-180 ºF (10-82 ºC). If for any reason the tank
temperature falls below 40 ºF (4 ºC), the tank will drain to keep the unit from
freezing.
When the temperature of the enclosure reaches 85 ºF (29 ºC), the ventilation
fans turn on to cool the electronic components. If the enclosure temperature
reaches 150 ºF (66 ºC), the Vapor-logic controller will extinguish any
operating burners and allow the ventilation fans to cool the enclosure. When
the enclosure temperature falls below 150 ºF (66 ºC), the GTS humidifier
automatically resumes normal operation.
INSTALLATION
Outdoor enclosure: Operation