background image

 

8. 

PLUMBING FIXTURE 

 

          Connection of heaters to plumbing fixtures is illustrated on Figures 1 and 2. For potential disconnection of 
the heater, the service water inlets and outlets must be provided with screw coupling Js 3/4“. Safety valve is 
mounted on the cold water inlet identified with a blue ring. 

 

Each hot service water pressure heater must have a membrane spring loaded with a safety valve. Nominal clearance 
of safety valves is defined in the ČSN 0 60830 standard. The heaters are not equipped with a safety valve. The 
safety valve must be easily accessible, as close to the heater as possible. The input pipes must have at least the 
same clearance as the safety valve. The safety valve is placed high enough to secure dripping water drain by 
gravity. We recommend mounting the safety valve onto a branch pipe. This allows easier exchange without having 
to drain the water from the heater. Safety valves with fixed pressure settings from the manufacturer are used for the 
assembly. Starting pressure of a safety valve must be identical to the maximum allowed heater pressure, and at least 
20% higher than the maximum pressure in the water main. If the water main pressure exceeds such value, a 
reduction valve must be added to the system.

 

No stop valves can be put between the heater and the safety valve. 

During the assembly, follow the guide provided by the safety equipment manufacturer. It is necessary to check the 
safety valve each time before putting it into operation. It is checked by manual moving of the membrane from the 
seat, turning the make-and-break device button always to the right. After being turned, the button must click back 
into a notch. Proper function of the make-and-break device results in water draining through the safety valve outlet 
pipe. In common operation, such a check needs to be implemented at least once a month, and after each heater 
shutdown for more than 5 days. Water may be dripping off the drain pipe of the safety valve; the pipe must be open 
into the air, pointed down; environment temperatures must not drop below zero. 

 

When draining the heater, use a recommended 
drain valve. First, close water input into the 
heater.

 

Find necessary pressure values in the following 
table. 

 

For proper safety valve operation, a backflow 
valve must be mounted on the inlet pipes, 
preventing spontaneous heater draining and hot water penetrating back into the water main. 
We recommend that the hot water distribution from the heater was as short as possible to minimise heat losses. 

 
Heaters must be provided with a discharge valve

 mounted on the cold service water inlet to the heater (Fig. 2) 

for potential disassembly or repair. 

 

When assembling the security equipment, follow ČSN 06 0830. 
 

9. 

ELECTRIC INSTALLATION 

The electric wiring scheme is attached to the water heater on the side of the electric installation guard (see also 
Fig.). 

 

Connection, repairs, and wiring inspections may only be implemented by a company (person) authorised to such 
activity. 
Expert connection must be confirmed on the warranty certificate. 
The heater is connected to the 400 V/50 Hz electric network using a fixed moving conductor with a switch that 
turns off all network poles and the circuit breaker (protector). 
Installations in bathrooms, laundromats, rest rooms, and showers, 33 2000-7-701 must be obeyed. 
The degree of protection of electric parts of the heater is IP 45.  
Respect the rules of protection against electrical injuries in accordance with ČSN 33 2000–4-41. 

 
 
 
 
 
 
Wiring scheme:

 

 

 
 

Safety valve 

starting pressure 

(MPa)

 

Admissible operating 

water heater 

pressure (MPa)

 

Max. pressure in 

the cold water pipe 

(MPa)

 

0.6 

0.6 

up to 0.48 

0.7 

0.7 

up to 0.56 

up to 0.8 

Summary of Contents for OKCE 100 NTR/2,2kW

Page 1: ...TATIONARY WATER HEATERS OKCE 100 NTR 2 2kW OKCE 125 NTR 2 2kW Družstevní závody Dražice strojírna s r o Works Cooperative Dražice Machine Plant Ltd Dražice 69 294 71 Benátky nad Jizerou Tel 326 370 911 Fax 326 370 980 www dzd cz dzd dzd cz ...

Page 2: ... Thanks to their construction and number of variants the OKCE 100 125 NTR series water heaters enable economic preparation of hot service water HSW by means of various power sources Their nominal performance provides sufficient amount of hot water for flat units premises restaurants and similar establishments For HSW reheat electricity various types of central heating boilers recoverable energy so...

Page 3: ...ctrical and plumbing fixture the warranty shall be void The Mg anode has to be checked regularly and exchanged if needed No stop valves can be put between the heater and the safety valve All outlets of hot water must be equipped with a combination faucet Before the first filling of water heater it is recommended to tighten the nuts of the flange joint of the tank It is not allowed to handle the th...

Page 4: ... a hot water heating system Check proper placement of operating and safety thermostat sensors The sensors must be inserted all the way in first the thermostat and then the safety fuse b Open the hot water valve on the combination faucet c open the cold water inlet valve to the heater d when the water starts flowing through the hot water valve the filling of the heater is finished and the valve nee...

Page 5: ...ocked Regulation limited pull off the thermostat knob it will be tough at first and you will find two cylindrical pins 2 15mm on the back side of the knob pull off one pin and insert it to the corresponding hole of the selected maximum temperature put the knob back on to the stop Setting blocked set the selected temperature pull off the thermostat knob without changing the setting and you will fin...

Page 6: ...6 A 881 1046 B 621 751 C 521 621 Typ OKCE 100 NTR 2 2 kW OKCE 125 NTR 2 2 kW 7 TECHNICAL PARAMETERS OKCE 100 NTR 2 2 kW OKCE 125 NTR 2 2 kW Cold water inlet Hot utility water outlet ...

Page 7: ...raining through the safety valve outlet pipe In common operation such a check needs to be implemented at least once a month and after each heater shutdown for more than 5 days Water may be dripping off the drain pipe of the safety valve the pipe must be open into the air pointed down environment temperatures must not drop below zero When draining the heater use a recommended drain valve First clos...

Page 8: ...xchanger MPa 1 1 Maximum rating water temperature C 110 110 Maximum temperature of HSW C 80 80 Lower exchanger heat delivery surface m 2 1 1 45 Bottom top exchnger output at rating water temperature of 80 C and flow 720 l h kW 24 32 Permanent HSW l h 610 990 Time of heating by exchanger from 10 C to 60 C min 14 14 Time of rating with electricity from 10 C to 60 C hod 3 3 5 Power input kW 2 2 Elect...

Page 9: ...allation instructions of the three way valve s manufacturer Connecting a Heater to a Hot Water Distribution Cold water shall be connected to an inlet marked with a blue ring and writing HSW INLET Hot water shall be connected to an outlet marked with a red ring or writing HSW OUTLET If the hot service water HSW distribution is equipped with circulation circuit it shall be connected to the outlet ma...

Page 10: ... the hardness of water heated its temperature and amount of hot water consumed We recommend checking and cleaning the tank from scale and eventual replacement of the anode rod after two years of operation The anode life is theoretically calculated for two years of operation however it changes with water hardness and chemical composition in the place of use Based on such an inspection the next term...

Page 11: ... 73 6660 Internal water mains ČSN 07 7401 Water and steam for thermal energy equipments with working steam pressure up to 8 MPa ČSN 06 1010 Tank water heaters with water and steam heating and combined with electric heating Technical requirements Testing ČSN EN 12897 Water supply Indirectly heated closed tank type water heaters Both the electric and water installation must follow and meet the requi...

Reviews: