Technical data
Dräger Polytron 8200/8310
29
12.1 Torques
(The torques are valid for the aluminum and stainless steel
316 variants)
If an optional e-Box is being used, fasten the device securely
to the e-Box with 4 screws and a tightening torque of 8 Nm.
12.2 Tightening torque and cable size for field
wiring terminals
12.3 Factory settings
12.3.1 Alterable settings for the Polytron 8200/8310
Environmental conditions
Specifications for the sensor: see sensor data sheet
Pressure
700 to 1300 hPa (20.7 to 38.4 in. Hg)
Humidity
0 to 100 % R. H., non-condensing
Temperature
DrägerSensor DD, LC no relay
DrägerSensor DD, LC with relay
DrägerSensor IR no relay
DrägerSensor IR with relay
-40 to +80 °C (-40 to +176 °F)
-40 to +70 °C (-40 to +158 °F)
-40 to +65 °C (-40 to +149 °F)
-40 to +65 °C (-40 to +149 °F)
Environmental influences
See respective sensor data sheets.
Part
Torque Lb. In.
Torque Nm
Housing cover
min. 266
min. 30
Sensors
min. 266
min. 30
Plug
min. 266
min. 30
Cable bushing
min. 443
min. 50
Device to e-Box
71
8
Electronic
Torque Lb. In.
Cable size in AWG Cable size in mm
2
All field wiring
terminals
4.4–7.0
(0.5–0.8 Nm)
20–12
0.5–2.5
Standard setting
Menu
DrägerSensor
DD, IR
DrägerSensor
LC
A1 Alarm
20 %LEL
2.0 %LEL
A2 Alarm
40 %LEL
4.0 %LEL
A1 Relay alarm:
Direction
Rising
Rising
A2 Relay Alarm:
Direction
Rising
Rising
A1 latching mode
Non-latching
Non-latching
A2 latching mode
Latching
Latching
A1 Acknowledgement
mode
Acknowledgeable Acknowledgeable
A2 Acknowledgement
mode
Not
acknowledgeable
Not
acknowledgeable
A1 enrg / wired in e-Box Energized / NO
Energized / NO
A2 enrg / wired in e-Box Energized / NO
Energized / NO
Maintenance password
0000
0000
LCD setting
on
on
Configuration/SIL
password
_ _ _2
_ _ _2
SIL status
Off
Off
Language
English
English
Fault current
1.2 mA
1.2 mA
Warning current
3.0 mA
3.0 mA
Maintenance current
3.4 mA
3.4 mA
HART address
0
0
Auto-cal.
Off
Off
Calibration interval
360
360
Function key
Faults
Faults