36
Dräger Polytron 8100
Factory default settings
7
Factory default settings
7.1
Settings which can be changed via the menu
Menu
Factory Default Setting
Range
Relay active on alarm / No alarm
Active on alarm
On / Off
A1 Alarm
Depending on the sensor
A2 Alarm
Depending on the sensor
A1 alarm: direction
(falling for DrägerSensor O2)
Rising
Falling / Rising
A2 alarm: direction
Rising
A1 latch mode
Non-latching
Latching / Non-Latching
A2 latch mode
Latching
A1 acknowledgment mode
Acknowledgeable
Acknowledgeable / Not acknowledgeable
/ Pre-acknowledgeable
A2 acknowledgment mode
Not acknowledgeable
Normal operation A1 relay
Energized
Energized / Not energized
Normal operation A2 relay
Energized
Hysteresis for A1 alarm at direction rising 0
0 to A1
Hysteresis for A2 alarm at direction rising 0
0 to A2
Calibration password
_ _ _1
Settings password
_ _ _2
LCD setting
On
On / Off
SIL status
Off
On / Off
Language
EN
DE / EN / FR / ES / RU / ZH
Fault current
1.2 mA
0 to 3.5 mA
Warning
Off
On / Off
Warning current
3.0 mA
0 to 3.5 mA
Warning cycle time T1
10 sec
5 to 60 sec.
Warning cycle time T2
1 sec
1 to 59 sec.
Maintenance
static
Static / Dynamic
Maintenance current
3.4 mA
0 to 3.5 mA
Analog offset
0 mA
-0.5 to 0.5 mA
Analog span
0 mA
-0.5 to 0.5 mA
HART address
0
0 to 15
Auto-calibration
Off
On / Off
Calibration interval
Depending on sensor
0 to 720
Function key
Faults
Graph, fault, warning, vitality, bump test
Display capture offset at O2 sensor
20.9 Vol%
0 to 25 Vol% (EC O2 LS)
0 to 100 Vol% (EC O2)
Display capture low at O2 sensor
-0.25 Vol%
0 to -0.75 Vol%
Display capture high at O2 sensor
0.25 Vol%
0 to 0.75 Vol%
Modbus address
2)
126
2-126
Modbus parity
2)
even (default)
even, odd parity, no parity
Modbus baudrate
2)
9600 bps
9600 or 19200 bps
Profibus address
2)
126
2-126
2)
Fieldbus interfaces are not in accordance with the BVS 13 ATEX G001 X. Using the fieldbus interface no relays are available.
Summary of Contents for Polytron 8100
Page 2: ......
Page 3: ...1 5 4 3 2 5 1 4 3 10 7 8 9 2 6 3 4 5 2 1 3 9 5 2 1 14 13 3 4 5 6 7 8 14 2 11 12 15 A B C D E...
Page 223: ...Dr ger Polytron 8100 223 4 5 2 4 5 3 OK OK 4 5 4 OK 5 OK 3 3 2 2...
Page 250: ...250 Polytron 8100 Additional Approvals A 3 Control Drawings...
Page 252: ...252 Polytron 8100 Additional Approvals A 4 Declaration of conformity...
Page 253: ......