10.1.2 Advanced Configuration
Fig. 10.3
- The Advanced Base Alarms Config screen
Editing Base Alarms - Advanced
Pnt (Point)
Alarm point number.
Description
User-definable description for the discrete alarm input.
On Set
User-definable description (condition) that will appear for the discrete alarm input on Set.
Example: "Alarm"
On Clear
User-definable description (condition) that will appear for the discrete alarm input on Clear.
Example: "Clear"
Qual. Time
(Qualification Time)
The length of time that must pass, without interruption, in order for the condition to be
considered an Alarm or a Clear.
Example
: If you have a loose door contact and you receive a false alarm every time the
wind blows, you might want to set a 3-second qualification time. This means the door
would have to be in the Alarm state for at least 3 seconds before the alarm is triggered and
a notification is sent.
Qual. Type
(Qualification Type)
Allows you to choose whether you want to apply the Qualification Time to the alarm Set,
Clear, or Both. (Most people use only Set.)
Monitoring Base Alarms
10.2
This selection provides the status of the base alarms by indicating if an alarm has been triggered. Under the
State
column, the status will appear in red if an alarm has been activated. The status will be displayed in green when the
alarm condition is not present.
Fig 10.4
Click on Base Alarms in the Monitor menu to see if any base alarms have been triggered.