Installation/Operating Manual

dp-control III(+)

Summary of Contents for dp-control III

Page 1: ...Installation Operating Manual dp control III ...

Page 2: ...ust neither be distributed copied reproduced edited or processed for any other purpose nor otherwise transmitted published or made available to a third party without the manufacturer s express written consent Subject to technical modification without prior notice D P Industries B V Alphen aan den Rijn Netherlands 30 05 2022 ...

Page 3: ... 10 3 2 Transport 10 3 3 Storage 10 3 4 Disposal 10 4 Description 12 4 1 General description 12 4 2 Product information as per Regulation No 1907 2006 REACH 12 4 3 Designation 12 4 4 Name plate 12 4 5 Functions 12 4 6 Technical data 13 4 7 Combination options 15 4 8 Scope of supply 15 4 9 Dimensions and weight 16 5 Installation at Site 17 5 1 Safety regulations 17 5 2 Checking ambient conditions 1...

Page 4: ...2 VC system 31 8 3 SVP system 32 8 4 General settings 32 8 4 1 Setpoint bandwidth 32 8 4 2 Alternative setpoint 32 8 4 3 Additional setpoint increase 32 8 4 4 Dynamic pressure setpoint compensation 32 8 4 5 Pump operating mode 33 8 4 6 Operating frequency range 33 8 4 7 Units displayed 33 8 4 8 Saving loading settings 33 8 5 Pump protection 33 8 5 1 Start delay and stop delay 33 8 5 2 Minimum runt...

Page 5: ...0 1 2 Pump settings 42 10 1 3 Input outputs 46 10 1 4 Further configuration settings 51 10 2 Settings 52 10 2 1 Pressure settings 52 10 2 2 Pump operating mode 53 10 2 3 Timers 54 10 2 4 Pump protection 55 10 2 5 System protection 57 10 2 6 Accumulator 60 10 2 7 Tank 60 10 2 8 Control algorithms 63 10 2 9 Display 63 10 3 Modbus 64 11 Messages 67 11 1 Messages for specific pumps 67 11 2 Messages fo...

Page 6: ...r warranty 1 2 Target group This operating manual is aimed at the target group of trained and qualified specialist technical personnel 1 3 Other applicable documents Table 1 Overview of other applicable documents Document Contents Circuit diagram Description of electrical connections and performance data For accessories and or integrated machinery components observe the relevant manufacturer s pro...

Page 7: ...s signal word indicates a hazard which if not avoided could result in damage to the machine and its functions General hazard In conjunction with one of the signal words this symbol indicates a hazard which will or could result in death or serious injury Electrical hazard In conjunction with one of the signal words this symbol indicates a hazard involving electrical voltage and identifies informati...

Page 8: ...pecified in the technical product literature for the mains voltage mains frequency ambient temperature and in compliance with any other instructions provided in the operating manual or other applicable documents The product must not be used in potentially explosive atmospheres 2 3 Personnel qualification and training All personnel involved must be fully qualified to install operate maintain and in...

Page 9: ...nsent Use only original spare parts or parts components authorised by the manufacturer The use of other parts components can invalidate any liability of the manufacturer for resulting damage The operator ensures that maintenance inspection and installation are performed by authorised qualified specialist personnel who are thoroughly familiar with the manual Any work on the product shall only be pe...

Page 10: ...rosion contamination of the control unit Ø For outdoor storage cover the packed or unpacked control unit and accessories with water proof material Table 4 Ambient conditions for storage Ambient condition Value Relative humidity Min 5 to max 90 Ambient temperature 10 C to 70 C Store the control unit in dry vibration free conditions and if possible in its original packaging Store the control unit in...

Page 11: ...parate and sort the materials e g by Aluminium Plastic cover recyclable plastic 3 Dispose of materials in accordance with local regulations or in another controlled manner PCBs power electronics capacitors and electronic components are all special waste The requirements pertaining to RoHs 2002 95 EC are fulfilled ...

Page 12: ...r 4p Number of pumps that can be connected 4 4 Name plate Made in Belgium Kalkovenweg 13 Alphen aan den Rijn NL DOM 03 2021 7A 42769 000011 P N SPBB10079122 24VAC 50 60 Hz 20W IP20 IP55 dp control III F 4p 6p VC SVP 6p www dp pumps com WARNING HIGH VOLTAGE 1 2 3 4 5 6 Fig 1 Name plate example 1 Type series 2 Size 3 Serial number 4 Year of construction 5 Input voltage mains frequency power input 6 ...

Page 13: ... Fire alert recognition with corresponding system configuration Monitoring of the inlet tank valve with corresponding system configuration Dry running protection Leakage detection External stop Monitoring of the water temperature or ambient temperature Communication Communication with field bus systems via the following interfaces Modbus RTU RS485 Profibus DP optional Bacnet MSTP optional Bus comm...

Page 14: ...A Volt free output NO normally open contact Parameterisable digital outputs 5 12 Max 250 V AC max 3 A Volt free output NO normally open contact External warning and alert Max 250 V AC max 3 A Volt free output NC NO SPDT Max length of electric cable 30 m Analog inputs Parameterisable analog inputs 1 2 4 20 mA input impedance 850 Ohm Parameterisable analog input 3 galvanically isolated 4 20 mA input...

Page 15: ...ons of frequency inverter and operating mode are recommended by DP Table 7 Combinations of frequency inverters and operating modes Operating mode Frequency inverter F system Without frequency inverter mains operation VC system Danfoss MicroDrive FC51 Danfoss MidiDrive FC280 Danfoss AquaDrive FC202 SVP system DP Var DP Var 4 8 Scope of supply Control unit with installed software ...

Page 16: ...16 76 4 9 Dimensions and weight 175 3 150 2 155 3 205 2 75 3 18 2 93 5 5 130 3 156 70 3 Fig 2 Dimensions Table 8 Weight Design Gewicht kg dp control III 0 50 dp control III 0 62 ...

Page 17: ...ent conditions other than indicated 3 Verify that the place of installation meets the following requirements Sufficient space for installation removal and proper ventilation No direct sunlight Protected against freezing Flood proof 5 3 Installing the control unit Fig 3 Installing the control unit in the control cabinet Fig 4 Inserting the control unit 1 Tilt the control unit to insert it into the ...

Page 18: ...ained electrician only DIN VDE 0105 Part 1 07 83 Ø Before commencing any work on the electrical installations de energise the system and make sure it cannot be re started unintentionally Ensure staff safety by PELV1 Ø Only motor protection devices with safe isolation to EN 50178 VDE 0160 may be connected directly CAUTION Improper electrical connection Damage to property Ø All connections shall be ...

Page 19: ... this connection has to be set to ON if it is the end of the communication cable B2 A B3 GND C1 R1_NO Switching relay Alert Normally open when one or several alert messages are present or when the control unit is off C2 R1_C C3 R1_NC C4 R2_NO Switching relay Warning Normally open when one or several warning messages are present or when the control unit is off C5 R2_C C6 R2_NC D1 DO1_C Digital outp...

Page 20: ...I10 G5 DI11 G6 DI12 H1 24V 24 V connections for digital inputs 1 to 12 H2 24V J1 B RS485_2 communication cable A terminating resistor located next to this connection has to be set to ON if it is the end of the communication cable J2 A J3 GND K1 B RS485_3 communication cable A terminating resistor located next to this connection has to be set to ON if it is the end of the communication cable K2 A K...

Page 21: ...10 Connections of the extension board Code Designation Description R1 DO5_C Digital outputs 5 to 12 with configurable function R2 DO5_NO R3 DO6_C R4 DO6_NO R5 DO7_C R6 DO7_NO R7 DO8_C R8 DO8_NC S1 DO9_C S2 DO9_NO S3 DO10_C S4 DO10_NO S5 DO11_C S6 DO11_NO ...

Page 22: ...the control unit to a power supply system suitable for its technical data 5 4 3 Using a motor contactor for F systems only DP recommends using motor contactors for switching the pump sets on and off The motor contactors used have to correspond with the pump set input power 5 4 4 Motor protection switches DP recommends using motor protection switches to electrically protect the pump sets The motor ...

Page 23: ...symbol is always the lock unlock symbol Turning the turn push button Turning the turn push button makes all selectable symbols flash one after the other in a specific sequence depending on the system configuration After the flashing cycle of all selectable symbols has been completed the selection returns to the lock unlock symbol To increase a value turn the turn push button clockwise To decrease ...

Page 24: ...warning messages are active as well as any messages of a lower priority Red continuous One or more alert messages are active as well as any messages of a lower priority 6 2 Symbols on the screen 1 4 2 3 5 Fig 9 Overview of all symbols on the screen 1 Operating status of the system ð Section 6 2 1 Page 25 2 Status of the Bluetooth connection 3 Locking unlocking the screen 4 Operating status of the ...

Page 25: ...ck the display and select this symbol Servicing required The service interval timer has detected that the control unit has not been serviced within the defined interval Lack of water Lack of water has been detected For more information see Section 11 list of messages message 800 6 2 2 Bluetooth connection Table 13 Bluetooth connection status symbols Symbol Description Flashing Looking for Bluetoot...

Page 26: ...em Symbols for a specific pump set in this example pump set 2 2 Active messages One or more warning messages or alert messages are active for pump set 2 3 Pump set running Indicates whether the pump set is currently running This symbol is extinguishes when the pump set has been stopped or is in idle state 4 Automatic mode The pump set is started up and stopped via the control unit F system or via ...

Page 27: ...or several pump sets in the system are running The corresponding messages are shown in position 7 4 Discharge side sensor The corresponding values and messages are shown in position 7 5 Accumulator The corresponding messages are shown in position 7 6 Temperature measurement The corresponding values and messages are shown in position 7 7 Display for the discharge side Displays information on the se...

Page 28: ...firm your selection 6 3 3 Resetting messages If a message is active for a part of the pressure booster system a red bar is displayed next to the corresponding symbol If a message is active the corresponding ID is displayed at the bottom right ð Section 11 Page 67 If several messages are active the corresponding IDs are displayed alternately All messages can be reset at once via the control unit If...

Page 29: ... Displaying the firmware version Every time the pressure booster system is re started the firmware version is displayed for a short time ð Section 6 2 5 Page 26 To have the firmware version displayed without re starting the pressure booster system proceed as follows 1 Turn the turn push button to select the Locking unlocking the screen symbol Then press the turn push button ð The symbol flashes 2 ...

Page 30: ...ymbol for wireless connection starts flashing 2 Open the app 3 Establish a connection between the app and the control unit 4 Tap the spanner symbol to access the Service level 5 Tap the second symbol to configure the parameters If 15 minutes pass without the app being used the connection ends automatically If the control unit does not receive any signals via the wireless connection for 2 minutes i...

Page 31: ...ep Height of Speed parameter 2 4 6 4 for the corresponding Step Interval parameter 2 4 6 3 If flow continues to be present the discharge pressure falls below the bandwidth and flow detection is deactivated If this is not the case the last pump set will be stopped when the Speed for Stopping Last Pump parameter 2 4 6 6 is reached 8 1 F system F system The F system controls several pump sets running...

Page 32: ...h The pressure booster system starts up and stops the pump sets and controls the speed of the pump sets in such a way that the discharge pressure corresponds with the configured Setpoint parameter 2 1 1 and is within the configured Bandwidth parameter 2 1 2 Pump sets are started up or stopped when the discharge pressure deviates from the setpoint by plus or minus half the bandwidth 8 4 2 Alternati...

Page 33: ...eset The settings made during commissioning can also be saved and reset ð Section 6 4 Page 29 8 5 Pump protection 8 5 1 Start delay and stop delay Start delay and stop delay Having several pump sets start up at the same time can be prevented by configuring a Start Delay parameter 2 3 1 or Stop Delay parameter 2 3 2 8 5 2 Minimum runtime Minimum runtime When a pump set is started up it can only be ...

Page 34: ...m Suction side Pressure for System Stop parameter 2 5 1 3 1 before a dry running condition is detected and the Minimum Suction side Pressure for Reset parameter 2 5 1 3 2 when the lack of water condition is no longer present When using a pressure switch Pressure switch has to be selected as the Source parameter 2 5 1 1 1 Dry running protection is then effected in accordance with the corresponding ...

Page 35: ...ia the Position parameter 2 5 2 4 The Response to any leakage being detected can be configured parameter 2 5 2 5 In the event of leakage at the pump system options are either Message only or Message and stop all pumps In the event of a tank overflow the options available are Message only Message and close inlet valve and Message close inlet valve and stop pumps referring to the rainwater pumps Set...

Page 36: ...Enabled parameter 1 1 7 1 The External On Off mode must be assigned a digital input one of parameters 1 3 3 1 to 1 3 3 18 8 9 Tank filling function 8 9 1 Tank control Tank control For pressure booster systems with an inlet tank filling of this tank can be controlled by the control unit To do so Drinking Water Filling must be activated parameter 2 7 1 1 1 For filling the tank the Inlet Valve Type h...

Page 37: ...opened for the Time for Flushing Drinking Water Supply parameter 2 7 1 5 4 Whether flushing is to be stopped in the event that the overflow level is exceeded can be configured under Overflow if High water Level is Exceeded parameter 2 7 1 5 5 8 9 5 Rainwater filling Rainwater filling If the tank is to be filled with rainwater instead of drinking water Rainwater Filling can be Enabled parameter 2 7...

Page 38: ...y pump a separate Minimum Runtime Jockey Pump parameter 2 3 5 can be set 8 11 Field bus Field bus A field bus Modbus RTU module with galvanically isolated RS 485 interface is integrated Modbus RTU communication has to be activated parameter 1 4 1 The corresponding Slave Address parameter 1 4 2 Baud Rate parameter 1 4 3 and Parity parameter 1 4 4 have to be set Diverse parameters and the status of ...

Page 39: ...ork and installation work can be carried out by DP Service or authorised workshops 9 2 Servicing Inspection 9 2 1 Supervision of operation Ensure sufficient cooling of the control unit Regularly check the control unit for any messages present ð Section 9 2 2 Page 39 9 2 2 Handling messages Some messages have to be reset manually These messages are displayed with a symbol There are different messag...

Page 40: ...y Service 1 1 1 4 System name for Bluetooth Full text max 30 characters BOOSTERCONTRO L Everybody Service 1 1 2 General 1 1 2 3 Operating mode Operation on frequency inverter Frequency driven Everybody Service Y Mains operation 1 1 2 4 Frequency inverter type KSB PumpDrive2 Eco PumpDrive2 Everybody Service Y DP Var Danfoss MicroDrive Danfoss MidiDrive Danfoss AquaDrive 1 1 2 5 Frequency control ty...

Page 41: ...r of all pumps Everybody Service 1 1 5 Manual 0 automatic mode 1 1 5 1 Manual 0 automatic mode of pumps Internal via display Internal via display Everybody Service External switches 1 1 6 Fire alarm 1 1 6 1 Fire alarm mode Disabled Disabled Everybody Service Enabled 1 1 7 External On Off 1 1 7 1 External On Off mode Disabled Disabled Everybody Service Enabled 1 1 8 Membrane rupture detection 1 1 8...

Page 42: ...ata Everybody Service 1 2 1 1 14 Flow rate 2 Pump data Everybody Service 1 2 1 1 15 Flow rate 3 Pump data Everybody Service 1 2 1 1 16 Flow rate 4 Pump data Everybody Service 1 2 1 1 17 Flow rate 5 Pump data Everybody Service 1 2 1 1 18 Flow rate 6 Pump data Everybody Service 1 2 1 1 19 Power 0 Pump data Everybody Service 1 2 1 1 20 Power 1 Pump data Everybody Service 1 2 1 1 21 Power 2 Pump data ...

Page 43: ...nimum speed for function at stop Motor data Everybody Service 1 2 1 2 9 Minimum motor speed Motor data Everybody Service 1 2 1 2 10 Maximum motor speed Motor data Everybody Service 1 2 1 2 11 Jog speed Motor data Everybody Service 1 2 1 2 12 Ramp up time Motor data Everybody Service 1 2 1 2 13 Ramp down time Motor data Everybody Service 1 2 1 2 14 Jog ramp time Motor data Everybody Service 1 2 1 2...

Page 44: ...verybody Service 2 Coast inverse 16 Preset bit 0 1 2 1 2 26 Function Relay 1 0 No operation Motor data Everybody Service 1 Control ready 2 Drive ready 4 Enable no warning 5 VLT running 6 Running no warning 9 Alarm 10 Alarm or warning 1 2 1 2 27 Function Relay 2 0 No operation Motor data Everybody Service 1 Control ready 2 Drive ready 4 Enable no warning 5 VLT running 6 Running no warning 9 Alarm 1...

Page 45: ... 2 33 Motor speed unit 0 RPM Motor data Everybody Service 1 Hz 1 2 1 2 34 Operating keys require login OFF ON Everybody Service ON 1 2 1 2 35 Motor PTC data analysis OFF ON Everybody Service ON 1 2 1 2 36 Motor direction of rotation Clockwise Anti clockwise Everybody Service Anti clockwise 1 2 1 2 37 Motor control method 0 Asynchronous motor V f control SuPremE vector control Everybody Service 1 A...

Page 46: ...erybody Service Pressure sensor on suction side Pressure sensor on discharge side Pressure sensor at tank Setpoint 1 3 2 Analog outputs Everybody Nobody Note To change a function the function first has to be removed by changing it to No function To set a function all pumps have to be set to Manual OFF 2 2 1 3 2 1 1 3 2 2 Output 1 Output 2 None None Everybody Service Pump speed Suction side pressur...

Page 47: ...tor circuit breaker pump 5 Failure motor circuit breaker pump 6 Manual mode at M 0 A switch pump 1 Manual mode at M 0 A switch pump 2 Manual mode at M 0 A switch pump 3 Manual mode at M 0 A switch pump 4 Manual mode at M 0 A switch pump 5 Manual mode at M 0 A switch pump 6 Automatic mode at M 0 A switch pump 1 Automatic mode at M 0 A switch pump 2 Automatic mode at M 0 A switch pump 3 Automatic mo...

Page 48: ...one Everybody Service Automatic mode at M 0 A switch rainwater pump 1 Automatic mode at M 0 A switch rainwater pump 2 Float switch in rainwater tank External On Off Fire alarm Acknowledge all Alternative setpoint Triggered check run Emergency power operation Forced flushing Module water quality sensor monitoring Membrane rupture detection Leakage detection by external device Failure supply valve F...

Page 49: ...mp 2 Start stop pump 3 Start stop pump 4 Start stop pump 5 Start stop pump 6 Pump running pump 1 Pump running pump 2 Pump running pump 3 Pump running pump 4 Pump running pump 5 Pump running pump 6 Pump fault pump 1 Pump fault pump 2 Pump fault pump 3 Pump fault pump 4 Pump fault pump 5 Pump fault pump 6 Tank filling solenoid valve Tank filling additional solenoid valve Flushing valve Dry running p...

Page 50: ...ody Service 1 3 7 1 4 Setpoint 1 3 7 1 4 1 Value at 4 mA 0 value at 20 mA 0 Everybody Service 1 3 7 1 4 2 Value at 20 mA Value at 0 4 mA 100 bar 16 bar Everybody Service 1 3 7 2 Output signal 1 3 7 2 1 Suction side pressure 1 3 7 2 1 1 Selection of output current range 0 20 mA 4 mA 20 mA Everybody Service 4 mA 20 mA 1 3 7 2 1 2 Value at 0 4 mA If selection 0 mA 20 mA 0 value at 20 mA Everybody Ser...

Page 51: ...rity None Odd Everybody Service Y Odd Even 1 5 Bluetooth 1 5 1 Time for login 0 600 s 150 s Everybody Service 1 6 Display Everybody Nobody 1 6 1 Time out lighting Everybody Nobody 1 6 1 1 Time out display 0 24 h 10 min Everybody Service 1 6 1 2 Time out display when message active 0 60 min 10 sec Everybody Service 1 6 1 3 Display lock time 0 24 h 10 min Everybody Service 1 6 2 Units displayed Ever...

Page 52: ...e interval for service required 0 3650 d 540 d Everybody Service 1 8 4 Reminder time for service interval expired 0 3650 d 540 d Everybody Service 1 9 VFD bus 1 9 1 Baud rate 9600 kBit s 38400 kBit s Everybody Service Y 19200 kBit s 38400 kBit s 57600 kBit s 115200 kBit s 1 9 2 Parity None Even Everybody Service Y Odd Even 10 2 Settings 10 2 1 Pressure settings Table 22 Pressure settings parameter...

Page 53: ...Customer 2 1 9 Additional setpoint increase 0 1 bar 0 3 bar Everybody Customer 2 1 10 Minimum set point 0 99 bar 0 bar Everybody Service 2 1 11 Maximum set point 0 99 bar 99 bar Everybody Service 10 2 2 Pump operating mode Table 23 Pump operating mode parameters Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re start required 2 2 Pumps Every...

Page 54: ... Rainwater pump 1 Automatic Manual Off Everybody Customer Manual Off Manual On 2 2 2 2 Rainwater pump 2 Automatic Manual Off Everybody Customer Manual Off Manual On 10 2 3 Timers Table 24 Timers parameters Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re start required 2 3 Timer Everybody Nobody 2 3 1 Start delay time 0 99 9 s 3 s Everybody...

Page 55: ...eed Run three pumps at fixed speed Run four pumps at fixed speed Run five pumps at fixed speed Run six pumps at fixed speed 2 4 1 5 Pump response to pressure sensor failure Stop all pumps Stop all pumps Everybody Service Freeze number of pumps running Run one pump Run two pumps Run three pumps Run four pumps Run five pumps Run six pumps 2 4 1 6 Pump speed on pressure sensor failure 0 100 0 Everybo...

Page 56: ...0 Everybody Service 2 4 4 6 Time stamp for execution minutes Day of week time Mo 12 00 00 Everybody Service 2 4 5 Short pressure deviations 2 4 5 2 Delay time for pump start 0 60 s 0 Everybody Service 2 4 5 3 Delay time for pump stop 0 60 s 0 Everybody Service 2 4 6 No flow detection Everybody Service 2 4 6 1 Pump speed for activation 0 100 1 Everybody Service 2 4 6 2 Time within bandwidth 0 600 s...

Page 57: ...ssure sensor at tank Pressure switch Float switch Flow switch 2 5 1 1 2 Delay time for system stop 0 99 s 10 s Everybody Service 2 5 1 1 3 Delay time reset 0 99 s 2 s Everybody Service 2 5 1 1 4 Maximum number of dry running protection events per hour 1 10 3 Everybody Service 2 5 1 1 5 Dry running protection stop delay 1 5 s 1 s Everybody Service 2 5 1 2 Additional source 2 5 1 2 1 Additional sour...

Page 58: ...ow of tank 2 5 2 5 Response Message only Message only Everybody Service Message and stop all pumps Message and close inlet valve Message close inlet valve and stop pumps 2 5 2 6 Delay time leakage detection 0 99 s 10 s Everybody Service 2 5 2 7 Delay time reset 0 99 s 2 s Everybody Service 2 5 3 Hygienic functions 2 5 3 1 General 2 5 3 1 1 Hygienic functions Disabled Disabled Everybody Service Ena...

Page 59: ...99 s 10 s Everybody Service 2 5 4 Emergency power operation Everybody Nobody 2 5 4 2 Maximum system load 1 maximum number of pumps 1 Everybody Service 2 5 4 3 Stop delay enabled disabled Disabled Enabled Everybody Service Enabled 2 5 5 Discharge pressure monitoring Everybody Nobody 2 5 5 1 High pressure alarm Everybody Nobody 2 5 5 1 1 Maximum discharge pressure 0 maximum pump head Maximum pump di...

Page 60: ...y Service 2 5 7 4 Redundant system scheduler start time minutes 0 60 min 0 Everybody Service 2 5 7 5 Redundant system scheduler stop time hours 0 24 h 0 Everybody Service 2 5 7 6 Redundant system scheduler stop time minutes 0 60 min 0 Everybody Service 10 2 6 Accumulator Table 27 Accumulator parameters Parameter Description Value range and dependencies Factory setting Access level Read Access leve...

Page 61: ...ody Service 2 7 1 2 13 Additional stop tank filling level Start tank filling level stop tank filling level 0 9 Everybody Service 2 7 1 2 14 Stop tank filling level Start tank filling level high water level 1 Everybody Service 2 7 1 2 15 Level for reset high water level Stop tank filling level high water level 1 2 Everybody Service 2 7 1 2 16 High water level Stop tank filling level according to se...

Page 62: ...e Enabled 2 7 2 2 Rainwater pumps Everybody Nobody 2 7 2 2 1 Source for dry running protection of rainwater pump No function None Everybody Service Float switch at rainwater tank 2 7 2 2 3 Delay time for stop 0 99 s 1 s Everybody Service 2 7 2 2 4 Delay time reset 0 99 s 1 s Everybody Service 2 7 2 2 5 Number of rainwater pumps 1 2 0 Everybody Service 2 7 2 2 8 Maximum runtime 0 3600 s 60 s Everyb...

Page 63: ...ue range according to controller TBD Service Service 2 8 3 System start up time delay 2 8 3 1 System start up time delay 0 60 s 10 s Service Service 2 8 4 Multi pump operation 2 8 4 1 Start flow rate 0 100 0 95 Service Service 2 8 4 2 Speed on percent 0 140 1 Service Service 2 8 4 3 Speed off percent 0 90 0 5 Service Service 2 8 4 4 Pump dynamic control 1 100 0 3 Service Service 10 2 9 Display Tab...

Page 64: ...ative fill level cm int16 r 47033 Level water tank relative fill level cm uint16 2 r 47034 Status opening solenoid valve uint16 r 47035 Status opening alternative solenoid valve uint16 r 47036 Rainwater pump load P1 uint16 r 47037 Rainwater pump load P2 uint16 r 47038 Operating mode rainwater pump 1 0 AUTOMATIC 1 MANUAL OFF 2 MANUAL ON uint16 r 47039 Operating mode rainwater pump 2 0 AUTOMATIC 1 M...

Page 65: ...Operating mode pump 4 0 AUTOMATIC 1 OFF 2 MANUAL uint16 r 47052 Operating mode pump 5 0 AUTOMATIC 1 OFF 2 MANUAL uint16 r 47053 Operating mode pump 6 0 AUTOMATIC 1 OFF 2 MANUAL uint16 r 47054 Status pump 1 0 IDLE 1 STARTING 2 RUNNING 3 STOPPING uint16 r 47055 Status pump 2 0 IDLE 1 STARTING 2 RUNNING 3 STOPPING uint16 r 47056 Status pump 3 0 IDLE 1 STARTING 2 RUNNING 3 STOPPING uint16 r 47057 Stat...

Page 66: ...Operating hours P1 0 136 years uint32 r 47102 Operating hours P2 0 136 years uint32 r 47104 Operating hours P3 0 136 years uint32 r 47106 Operating hours P4 0 136 years uint32 r 47108 Operating hours P5 0 136 years uint32 r 47110 Operating hours P6 0 136 years uint32 r 47112 Number of pump starts P1 uint32 r 47114 Number of pump starts P2 uint32 r 47116 Number of pump starts P3 uint32 r 47118 Numb...

Page 67: ...Auto 158 2 9 2 9 Undervoltage frequency inverter pump 1 Alert Auto 159 2 9 2 10 Overload frequency inverter pump 1 Alert Manual 160 2 9 2 11 Brake resistor frequency inverter pump 1 Alert Manual 161 2 9 2 12 Temperature fault frequency inverter pump 1 Alert Manual 162 2 9 2 13 AMA fault frequency inverter pump 1 Alert Manual 163 2 9 2 14 Short circuit frequency inverter pump 1 Alert Manual 164 2 9...

Page 68: ...ter pump 3 Alert Manual 365 2 9 6 16 Configuration invalid frequency inverter pump 3 Alert Manual 400 2 9 7 1 Failure motor circuit breaker pump 4 Warning Manual 401 2 9 7 2 Manual ON pump 4 Warning Auto 402 2 9 7 3 Manual OFF pump 4 Warning Auto 403 2 9 7 4 Excessive temperature motor pump 4 Alert Manual 450 2 9 8 1 Fault motor circuit breaker frequency inverter pump 4 Warning Manual 451 2 9 8 2 ...

Page 69: ...ncy inverter pump 6 Alert Auto 653 2 9 12 4 Incorrect check sum frequency inverter pump 6 Alert Auto 654 2 9 12 5 Internal fault frequency inverter pump 6 Alert Auto 655 2 9 12 6 Mains fault frequency inverter pump 6 Alert Manual 656 2 9 12 7 Phase failure frequency inverter pump 6 Alert Manual 657 2 9 12 8 Overvoltage frequency inverter pump 6 Alert Auto 658 2 9 12 9 Undervoltage frequency invert...

Page 70: ... 20 2 Starts per hour exceeded rainwater pump 1 Warning Auto 812 2 9 20 3 Manual OFF rainwater pump 1 Warning Auto 813 2 9 20 4 Manual ON rainwater pump 1 Warning Auto 814 2 9 20 5 Fault rainwater pump 2 Alert Manual 815 2 9 20 6 Starts per hour exceeded rainwater pump 2 Warning Auto 816 2 9 20 7 Manual OFF rainwater pump 2 Warning Auto 817 2 9 20 8 Manual ON rainwater pump 2 Warning Auto 818 2 9 ...

Page 71: ...ion failed Warning Auto 950 2 9 27 1 Service required Warning Manual 960 2 9 28 1 Too many failed login attempts Information Auto 970 Database invalid Alert Manual 971 Database not compatible Alert Manual 972 2 9 29 1 Extension board not available Alert Manual 973 2 9 29 2 Overcurrent detected Alert Manual 974 2 9 29 3 Power failure Information Auto 975 2 9 25 4 Failure of real time clock Informat...

Page 72: ...tection relay Check the current input of the pump Check the changeover time from star to delta required approx 3 seconds up to 22 kW power Thermal circuit breaker connection Ensure that inputs outputs and serial interface are galvanically isolated from the thermal circuit breaker inputs If the thermal circuit breaker has no safe isolation from the low voltage mains decouple the signals via coupler...

Page 73: ...14 53 EU Radio Equipment Directive The manufacturer also declares that the following harmonised international standards have been applied EN 62368 1 2014 A1 2017 EN 301 489 1 v2 2 3 EN 301 489 17 v3 2 4 IEC 61000 6 2 2019 EN 61000 6 3 2007 A1 2011 EN 62479 2010 EN 300 328 v2 2 2 2019 The notified body Telefication B V 560 verified the technical design in accordance with module B and module C and i...

Page 74: ...nput outputs 46 Intended use 8 J Jockey pump system 38 K Key to safety symbols markings 7 L Leakage detection 35 Locking unlocking the screen 26 M Mainboard connections 19 Membrane rupture detection 35 Messages Additional devices 69 Functions 70 Pumps 67 Minimum runtime 33 Motoranschlussleitung 17 N Name plate 12 O Operating frequency range 33 Operating mode 28 Operating status of the pump 26 Oper...

Page 75: ... 8 Start delay and stop delay 33 Status LED 24 Storage 10 Supervision of operation 39 SVP system 32 Symbols on the screen 24 System protection 57 System settings 40 T Tank 60 Tank control 36 Tank monitoring 37 Technical data 13 Temperature monitoring 36 Timers 54 Training 8 Transport 10 U Umgebungsbedingungen Lagerung 10 Units displayed 33 V VC system 31 W Warnings 7 Warranty claims 6 ...

Page 76: ...P O Box 28 2400 AA Alphen aan den Rijn The Netherlands t 0172 48 83 88 dp dp pumps com www dp pumps com dp pumps 30 05 2022 BE00001402 4043 811 01 EN ...