74
/
96
10.2.2.4 Pump protection
Table 32:
Pump protection parameters
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-4
Pump protection
-
-
Everybody
Nobody
-
2-4-1
General
-
-
-
-
-
2-4-1-1
Minimum frequency
0 … maximum frequency
60 Hz
Everybody
Service
-
2-4-1-2
Maximum frequency
Minimum frequency … 150 Hz
100 Hz
Everybody
Service
-
2-4-1-4
Pump response to pressure sensor
failure
Stop all pumps
Stop all pumps
Everybody
Service
-
Freeze number of pumps running and speed
Run one pump at fixed speed speed
Run two pumps at fixed speed
Run three pumps at fixed speed
Run four pumps at fixed speed
Run five pumps at fixed speed
Run six pumps at fixed speed
2-4-1-5
Pump response to pressure sensor
failure
Stop all pumps
Stop all pumps
Everybody
Service
-
Freeze number of pumps running
Run one pump
Run two pumps
Run three pumps
Run four pumps
Run five pumps
Run six pumps
2-4-1-6
Pump speed on pressure sensor
failure
0 … 100 %
0
Everybody
Service
-
2-4-2
Changeover within pump group
-
-
-
-
-
2-4-2-1
Changeover within pump group
Disabled
Enabled
Everybody
Service
-
Enabled
2-4-2-2
Maximum runtime
1 s … 24 h
24 h/number of
pumps
Everybody
Service
-
2-4-2-3
Over-/undersupply
Oversupply
Oversupply
Everybody
Service
-
Undersupply
2-4-2-4
Time of over-/undersupply
0 … 60 s
0
Everybody
Service
-
2-4-2-5
Ramp up time
0 … 60 s
0
Everybody
Service
-
Summary of Contents for Hydro-Unit Utility Line F
Page 29: ...29 96 1 2 Fig 12 PE connection 1 Earthing terminal 2 Location of power connection ...
Page 58: ...58 96 ...
Page 92: ...92 96 T Tank 79 Timers 73 W Warnings 9 Warranty claims 7 ...
Page 93: ......
Page 94: ......
Page 95: ......