71
/
96
10.2.1.4 Further configuration settings
Table 29:
Further configuration settings parameters
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
1-4
Field bus
-
-
Everybody
Nobody
-
1-4-1
Modbus RTU
Disabled
Disabled
Everybody
Service
Y
Enabled
1-4-2
Slave address
1 … 247
247
Everybody
Service
Y
1-4-3
Baud rate
9600 kBit/s
115200 kBit/s
Everybody
Service
Y
19200 kBit/s
38400 kBit/s
57600 kBit/s
115200 kBit/s
1-4-4
Parity
None
Odd
Everybody
Service
Y
Odd
Even
1-5
Bluetooth
-
-
-
-
-
1-5-1
Time for login
0 … 600 s
150 s
Everybody
Service
-
1-6
Display
-
-
Everybody
Nobody
-
1-6-1
Time-out lighting
-
-
Everybody
Nobody
-
1-6-1-1
Time-out display
0 … 24 h
10 min
Everybody
Service
-
1-6-1-2
Time-out display when message
active
0 … 60 min
10 sec
Everybody
Service
-
1-6-1-3
Display lock time
0 .. 24 h
10 min
Everybody
Service
-
1-6-2
Units displayed
-
-
Everybody
Nobody
-
1-6-2-1
Pressure
bar
bar
Everybody
Service
-
PSI
1-6-2-2
Height
cm
cm
Everybody
Service
-
%
1-6-2-3
Temperature
°C
°C
Everybody
Service
-
°F
1-7
Time and date
-
-
Everybody
Nobody
-
1-7-1
Time
-
-
Everybody
Nobody
-
1-7-1-1
Hours
0 … 23
0
Everybody
Service
-
1-7-1-2
Minutes
0 … 59
0
Everybody
Service
-