40 / 64
7.1.7 Quick menu
The Quick Menu allows access to the main parameters which may be required for adapting
the pressure booster system to site conditions. Press OK to call up the Quick Menu from the
start screen.
– PIN
– Proportional constant
– Integral constant
– Differential constant
– Setpoint
– Bandwidth
– Accumulator pressure
– Delta P correction (dynamic pressure compensation)
– High pressure alert
– Low pressure alert
– Minimum runtime
– Start delay
– Stop delay
– RDP delay
– High/low alert delay
7.1.8 Saving and restoring settings
Saving settings
ü
Logged in at Customer level.
1. Call up parameter 3-2-2-4 (saving customer settings).
2. Select OK.
Restoring settings
Restoring factory
settings
ü
Logged in at Customer level.
1. Call up parameter 3-2-2-1 (factory settings).
2. Select RESET OK.
ð
Resets the pressure booster system’s values and settings to factory-set defaults.
Resetting to saved
settings
ü
Logged in at Customer level.
1. Call up parameter 3-2-2-3 (customer settings).
2. Select RESET OK.
ð
Resets to settings saved on site.
Resetting to default
settings
ü
Logged in at Factory level (for manufacturers only).
1. Select parameter 3-2-2-6 (default settings).
2. Select OK.
ð
The control unit is reset to the pressure booster system type. No settings for pressure,
dry running protection, etc.
7.1.8.1 Saving settings
The changes made to the control unit parameters at the site can be saved under 3-2-2-4.