3.7 In-Tank Static Leak Test
Figure 3-1 In-Tank Static Leak Test
1. Push the Settings tab.
2. Push In-Tank Static Leak Test under the left-side Filters menu.
3. Select the tanks to be set up for auto leak test under the right-side Filters menu.
4. Select the type and when to run the In-Tank Static Leak Test.
a. Select the type of test; 0.1 gph or 0.2 gph.
b. To run immediately, select Run Now. To run at a later date and time select Run Later.
5. Push Duration: A pop-up will come into view (see below) to let you set the number of hours for the leak
test in 30-minute increments. Use the + and – buttons to increase or decrease the hours and minutes.
Push Set to save. To close this pop-up without saving, push Cancel.
6. Push Minimum Volume: A pop-up will come into view (see below) to let you set the Minimum Volume
as a percentage. Use the + and – buttons to increase or decrease the percentage. Push OK to save. To
close this pop-up without saving, push Cancel.
7. If Run Later is selected the Date box under SCHEDULE will be white. Set the desired Date of the leak
test from the pop-up (see below) using the + and – buttons to set the Day/Month/Year (the date cannot
be set in the past). Push Set to save. To close this pop-up without saving, push Cancel.