3.6 In-Tank Auto Leak Test
Figure 3-1 In-Tank Auto Leak Test
This screen will let you set up the schedule for an In-Tank Auto Leak Test.
1. Push the Settings tab.
2. Push In-Tank Auto Leak Test under the left side Filters menu.
3. select the tanks to be set up for an auto leak test under the right-side Filters menu.
4. select Recurrence as necessary. Push the applicable button; Daily, Weekly, Monthly or Yearly.
5. Push the Duration box: A pop-up will come into view (see below) to let you set the number of hours for
the leak test in 30-minute increments. Use the + and – buttons to increase or decrease the hours and
minutes. Push Set to save. To close this pop-up without saving, push Cancel.
6. Push the Leak Test Warning box: A pop-up will come into view (see below) to let you set the number of
days for Leak Test Warning (this will vary by Recurrence: Up to six (6) days Weekly, up to 28 days
Monthly, up to 364 days Yearly). Use the + and – buttons to increase or decrease the days. Push OK to
save. To close this pop-up without saving, push Cancel.
7. Push the Minimum Volume box: A pop-up will come into view (see below) to let you set the Minimum
Volume as a percentage. Use the + and – buttons to increase or decrease the percentage. Push OK to
save. To close this pop-up without saving, push Cancel.
Doc. No.: M2012 Rev.: 3
Page 23 of 49