2.6 Internal Printer
An internal thermal printer option is available for the SiteSentinel®
iSite™ Console. The printer will install inside the cabinet. The printer will
be used for printing the various reports the SiteSentinel® iSite™ has
available.
2.6.1 Installation Procedure
1.
Mount Printer Power Supply above the existing power supply.
2.
Slide printer onto mounting bracket.
3.
Mount printer and bracket in Si
teSentinel® iSite™ Console
fixing to four (4) pre-drilled holes.
4.
Connect power cable to 3-connector power plug (CN1) on left-
hand side of power supply board.
5.
Connect printer power cable to 6-connector plug (CN2) on right-
hand side of board.
6.
Connect printer ribbon cable to J22 on right-hand side of main
communication board.
Figure 2-19 Internal Printer
Figure 2-19 Main Board Printer Connections
CN2
CN1
J22
Summary of Contents for OPW SiteSentinel iSite
Page 15: ...Page 15 of 145 www opwglobal com Figure 2 4 Console Connectivity ...
Page 17: ...Page 17 of 145 www opwglobal com Figure 2 6 Wiring Connections ...
Page 22: ...Page 22 of 145 www opwglobal com Figure 2 11 Standard Twisted Pair Petro Net Installation ...
Page 25: ...Page 25 of 145 www opwglobal com Figure 2 14 Petro Net Over Ethernet Option ...
Page 33: ...Page 33 of 145 www opwglobal com ...
Page 34: ...Page 34 of 145 www opwglobal com Figure 4 1 924B Probe Installation ...
Page 61: ...Page 61 of 145 www opwglobal com Figure 5 22 In Tank Probe Setup ...
Page 74: ...Page 74 of 145 www opwglobal com Figure 9 3 Dry Well Monitoring Single Wall Tank ...
Page 78: ...Page 78 of 145 www opwglobal com Figure 9 7 Double Wall Tank with Well Monitoring ...
Page 90: ...Page 90 of 145 www opwglobal com Figure 13 7 ACR RIM Jumper Board ...
Page 142: ...Page 142 of 145 www opwglobal com Declaration of Conformity ...
Page 143: ...Page 143 of 145 www opwglobal com ...