DOTECH DPX100 User Manual Download Page 1

-1-

 

DPX100 R20141014 

 

Digital Pressure Switch

 

 

CAUTIONS

 

1. This product may cause an electric shock in handling. Please do not attempt to open it with power turned on.   
2. This product should be installed in a place fixed secured by a rack or panel.   
3.This product can be used under the following environmental condition.   

①  Indoor  ②Pollution Degree 2  ③At an altitude of 2000m or below 

4. Power input must be within the designated ranges. 
5. To turn on or turn off power supply for this product, please the circuit breaker or switch of a standard product of IEC 

60947-1 or IEC 60947-3 product and install it within a close distance allowing convenient operation by user.   

6. Please be understood that if this product is dismantled or modified discretionary, after sales service will not 

be able to be provided.   

7. An output wire to be used for this product should be inflammable grade FV1 (V-1 grade or above), the thickness   

of the wire should be AWG No. 20 or above(0.50mm

2

).   

8. In order to prevent it from an inductive noise, please maintain the high-voltage wire and power wire separated.   
9. Please avoid installing the product in a place where a strong magnetism, noise, severe vibration and impact exist.   
10. When extending the sensor wire, use a shield wire and do not extend it unnecessary long.   
11. The sensor wire and signal wire should be away from the power and load wires using conduits separately installed.   
12. Please avoid using the product near a device generating strong high frequency noise (high-frequency welding machine, 

high-frequency sewing machine, high-frequency radiotelegraph, high capacity SCR controller)   

13. Product’s damages other than those decribed in the guarantee conditions provided by the manufacturer shall not be 

respoinsible by us. 

14. If this unit is used to control machineries (Medical equipment, vehicle, train, airplane, combustion apparatus, 

entertainment, processing and transportation equipment, elevator and various safety device etc.) enabling to effect 
on human or property, it is required to install fail-safe device. 

※ The Aforementioned precautions must be observed, and if you fail to do so, it may cause a product’s breakdown

※ The specifications, dimensions, and etc. are subject to change for enhancement without a prior notice.

 

DPX100

 

User Manual

 

  

 

DOTECH INC. 

6F, JOONGANG-ILBO B/D, 30, Dongsan-ro, Danwon-gu, Ansan-si, Gyeonggi-do, 
KOREA 
TEL: +82-31-495-3767  FAX: +82-31-495-3917 

www.dotech21.com  

 

1.

 

OVERVIEW

 

※ 

FEATURES

 

DPX100 is a digital pressure switch with functions of several pressure switch and 
gauges. It measures the low pressure of suction or the high pressure of discharge 
of compressor and controls the pressure within predetermined ranges.

 

: SPECIFICATIONS(STANDARD MODEL) 

 

Description 

Power 

100 

 240 Vac, 50/60 Hz 

Power Consumption 

MAX 10 VA 

Output 

3P Relay Outputs / 250Vac, 30Vdc, 5 A 

Pressure 

Sensors 

Measurement 
Range 

DPX100-115 : -0.10 ~ 1.50 MPa 
DPX100-150 : -0.10 ~ 5.00 MPa 

Accuracy 

±1.0 %FS 

Overpressure 

150 %FS 

Stability 

±0.5 %FS/year 

Shock 

20 g sinusoidal, 11 msec 

Vibration 

x-y-z directions of 5 -2000Hz / 10g 

Working Temp. 

-40 ~ 120 °C 

Connection 

7/16UNF” / MALE 

Pressure Type 

Gauge 

Dimensions 

159(W)mm X 128(H)mm X 58(D)mm 

Operation 

Temperature -10~50 °C / Humidity 90%RH or less 

Storage 

Temperature -20~60 °C / Humidity 90%RH or less 

 

: SELECTION GUIDE 

Model

 

Description

 

DPX100-115 / Low Pressure Sensor = -0.10 ~ 1.50 MPa 

DPX100-115-00-MPA 

Digital Pressure Switch Standard(Pressure Unit:: MPa ) 

DPX100-115-R4-MPA 

Digital Pressure Switch for Communication(RS485 Modbus ) 

DPX100-115-00-KGF 

Digital Pressure Switch Standard(Pressure Unit:: kgf/cm2) 

DPX100-115-R4-KGF 

Digital Pressure Switch for Communication(RS485 Modbus ) 

DPX100-115-00-BAR 

Digital Pressure Switch Standard(Pressure Unit:: bar ) 

DPX100-115-R4-BAR 

Digital Pressure Switch for Communication(RS485 Modbus ) 

DPX100-115-00-PSI 

Digital Pressure Switch Standard(Pressure Unit:: psi ) 

DPX100-115-R4-PSI 

Digital Pressure Switch for Communication(RS485 Modbus ) 

DPX100-150 / High Pressure Sensor = -0.10 ~ 5.00 MPa 

DPX100-150-00-MPA 

Digital Pressure Switch Standard(Pressure Unit:: MPa ) 

DPX100-150-R4-MPA 

Digital Pressure Switch for Communication(RS485 Modbus ) 

DPX100-150-00-KGF 

Digital Pressure Switch Standard(Pressure Unit:: kgf/cm2) 

DPX100-150-R4-KGF 

Digital Pressure Switch for Communication(RS485 Modbus ) 

DPX100-150-00-BAR 

Digital Pressure Switch Standard(Pressure Unit:: bar ) 

DPX100-150-R4-BAR 

Digital Pressure Switch for Communication(RS485 Modbus ) 

DPX100-150-00-PSI 

Digital Pressure Switch Standard(Pressure Unit:: psi ) 

DPX100-150-R4-PSI 

Digital Pressure Switch for Communication(RS485 Modbus ) 

 Communication is not supported in standard models. 

 Specify the pressure unit when ordering.

 

Supplied Contents

 

 

 

 

 This item is provided for securing the bracket tightening all bolts please. 

Bracket 1ea 

User Manual 