background image

-1-

 

DP100-AR R20200810 

Differential Pressure Transmitter

 

  

※ Cautions

 

Cautions 

1. This product may cause an electric shock in handling. Please do not attempt to open it with power turned on.  
2. This product should be installed in a place fixed secured by a rack or panel.  
3.This product can be used under the following environmental condition.  

① Indoor ②Pollution Degree 2 ③At an altitude of 2000m or below 

4. Power input must be within the designated ranges. 
5. To turn on or turn off power supply for this product, please the circuit breaker or switch of a standard product of IEC 60947-1 or IEC 60947-3 product and install it  

within a close distance allowing convenient operation by user.  

6. Please be understood that if this product is dismantled or modified discretionary, after sales service will not be able to be provided.  
7. An output wire to be used for this product should be inflammable grade FV1 (V-1 grade or above), the thickness  
of the wire should be AWG No. 20 or above(0.50mm2).  
8. In order to prevent it from an inductive noise, please maintain the high-voltage wire and power wire separated.  
9. Please avoid installing the product in a place where a strong magnetism, noise, severe vibration and impact exist.  
10. When extending the sensor wire, use a shield wire and do not extend it unnecessary long.  
11. The sensor wire and signal wire should be away from the power and load wires using conduits separately installed.  
12. Please avoid using the product near a device generating strong high frequency noise (high-frequency welding machine, high-frequency sewing machine,  

high-frequency radiotelegraph, high capacity SCR controller)  

13. Product

s damages other than those decribed in the guarantee conditions provided by the manufacturer shall not be respoinsible by us. 

14. If this unit is used to control machineries (Medical equipment, vehicle, train, airplane, combustion apparatus, entertainment, processing and transportation 

equipment, elevator and various safety device etc.) enabling to effect on human or property, it is required to install fail-safe device. 

※ The Aforementioned precautions must be observed, and if you fail to do so, it may cause a product’s breakdown. 
※ The specifications, dimensions, and etc. are subject to change for enhancement without a prior notice.

 

DP100-AR 

User

s manual 

  

 

 

DOTECH INC.    

6F, JOONGANG-ILBO B/D, 30, Dongsan-ro, Danwon-gu, Ansan-si, 
Gyeonggi-do, KOREA 
Phone: +82-31-495-3767, Fax : +82-31-495-3917 

www.dotech21.com 

 

 

1.

 

Overview 

 

※ Features 

- Optimization of FAN Control by Differential Pressure 
- Various Analog Control Outputs  
- Current, voltage output selectable 
- RS485 Modbus RTU 
- Relay Alarm Output 

: Basic Specifications 

Items 

Description 

Power 

100 

 240 Vac, 50/60Hz 

Power Consumption 

MAX 5VA 

Connection 

Screw Terminal, wire range : 24~16AWG 

Span Accuracy 

± 3 % 

Zero point Accuracy 

± 0.2 Pa 

Operation Condition 

Temp. 

 10~50℃, (Non condensation) 

Storage Condition 

Temp. 

 20~60℃, Humidity below 90%RH 

Size (W x H x D mm) 

115 x 80 x 40 

Weight 

220g 

 

: Ordering Guide 

Model 

Description 

DP100-AR-

A1R4-500 

Measuring range : -500 ~ 500Pa 

Analog output (4~20mA or 0-10V) 

RS485 model : MODBUS RTU MODE 

DP100-AR-

A1R4-125 

Measuring range : -125 ~ 125Pa 

Analog output (4~20mA or 0-10V)  

RS485 model : MODBUS RTU MODE 

 

 

: Packing 

 

 

DP100-AR 

User

s manual 

※ Silicon Tube Φ6.0 * 3.0 2M (※Standard scope of supply)

 

 

: Display range for pressure 

Unit 

Measuring range 

Display range of decimal point 

(Automatic Switching) 

Pa 

-500 ~ 500 

-199.9 ~ 500.0 / -500 ~ -200 

mmAq 

-50 ~ 50 

-19.99 ~ 50.00 / -50.0 ~ -20.0 

 

 

 

 

Reviews: