Chapter 7 Troubleshooting Your Array
7-19
Figure 7-11
Front-Panel LEDs Flowchart, 5 of 5
7.7.4
I/O Controller Module
The following flowchart provides troubleshooting procedures for the I/O controller
module.
3E
Front panel LEDs problem
(SCSI)
Check that LED
ribbon cable in right
ear is not loose.
Verify the air
conditioning is
working properly.
Fix if needed.
End
Yes
Resolved?
Temp LED
Resolved?
No
No
Replace controller
that reported over
temperature error.
Resolved?
Replace chassis.
Ensure adequate
ventilation.
Resolved?
Yes
End
End
Yes
Yes
No
No
End
--Reseat the FRU that is not operating correctly.
--Swap the questionable FRU with a known-good
FRU from the same array.
Notes
55 degrees Celsius equals 131 degrees
Fahrenheit.
Prior to replacing a chassis, try the following:
Summary of Contents for SANnet II 200
Page 32: ...3 4 SANnet II 200 SCSI Array Installation Operation and Service Manual June 2005...
Page 64: ...4 32 SANnet II 200 SCSI Array Installation Operation and Service Manual June 2005...
Page 74: ...5 10 SANnet II 200 SCSI Array Installation Operation and Service Manual June 2005...
Page 106: ...7 22 SANnet II 200 SCSI Array Installation Operation and Service Manual June 2005...
Page 130: ...B 20 SANnet II 200 SCSI Array Installation Operation and Service Manual June 2005...
Page 146: ...E 10 SANnet II 200 SCSI Array Installation Operation and Service Manual June 2005...
Page 154: ...F 8 SANnet II 200 SCSI Array Installation Operation and Service Manual June 2005...
Page 160: ...G 6 SANnet II 200 SCSI Array Installation Operation and Service Manual June 2005...
Page 178: ...I 10 SANnet II 200 SCSI Array Installation Operation and Service Manual June 2005...
Page 180: ...J 2 SANnet II 200 SCSI Array Installation Operation and Service Manual June 2005...
Page 186: ...6 SANnet II 200 SCSI Array Installation Operation and Service Manual June 2005...